N.B Calculation is made on Infinitue Bus Method
3
Fault Current CalculationJignesh.Parmar www.electricalnotes.wordpress.com
4
5
Fault Current at Transformer Primary Side (Enter This Value if You know otherwise leave blank)AmpAlu1 Core CableNon-Metalic
6
Cu3 Core CableMetalic
7
Fault Current At TransformerYes
8
Transformer Kva75KvaNo
9
Secondary Voltage of Transformer (Line-Line)220Volt
10
Secondary Voltage of Transformer (Line-Neutral)127Volt
11
Transformer Impedance (Zt)5%
12
Transformer Secondary Full Load Current I (Line-Line)197Amp
13
Transformer Secondary Full Load Current I (Line-Neutral)295Amp
14
KVA Short Circuit At Primary Side
15
Source Impedance (Zu)0.0000
16
Total Impedance (Z =Zu+Zt)0.0500
17
Short Circuit Current RMS Symmetrical3937Amp
18
Fault Current At Transformer Secondary ( Isc(L-L)=I (L-L)/Total Impedance)3937Amp
19
Fault Current At Transformer Secondary ( Isc(L-N)=I (L-N)/Total Impedance)5905Amp
20
Fault Current At Main Panel
21
Cable Length from Transformer to Main Panel35Meter
22
Type of CableAlu3 Core Cable
23
No of Conductor/Phase2
24
Size of Phase Conductor55 mm2
25
Size of Neutral Conductor55 mm2
26
Type of Race WayNon-Metalic
27
Phase Conductor Constant (C1)5876
28
Neutral Conductor Constant (C2)5876
29
F1(L-L) [F(L-L)=(1.732 X Length X Isc)/(C1 X No of Conductor X Volt)]0.092
30
F2(L-N) [F(L-L)=(1.732 X Length X Isc)/(C2 X No of Conductor X Volt)]0.240
31
M1(L-L) [M=(1/(1+F1)]0.915
32
M2(L-N) [M=(1/(1+F2)]0.807
33
Fault Current at Main Panel Disconnection (L-L) [Isc X M1]3604Amp
34
Fault Current at Main Panel Disconnection (L-N) [Isc X M2]4763Amp
35
Fault Current At Sub Panel
36
Cable Length from Main Panel to Sub Panel20Meter
37
Type of CableCu3 Core Cable
38
No of Conductor/Phase1
39
Size of Phase Conductor30 mm2
40
Size of Neutral Conductor127 mm2
41
Type of Race WayNon-Metalic
42
Phase Conductor Constant (C1)4833
43
Neutral Conductor Constant (C2)19779
44
F1(L-L) [F(L-L)=(1.732 X Length X Isc)/(C1 X No of Conductor X Volt)]0.117
45
F2(L-N) [F(L-L)=(1.732 X Length X Isc)/(C2 X No of Conductor X Volt)]0.038
46
M1(L-L) [M=(1/(1+F1)]0.895
47
M2(L-N) [M=(1/(1+F2)]0.963
48
Fault Current at Sub Panel Disconnection (L-L) [Isc X M1]3225Amp
49
Fault Current at Sub Panel Disconnection (L-N) [Isc X M2]4589Amp
50
Fault Current At Distribution Board
51
Cable Length from Sub Panel to Distribution Board50Meter
52
Type of CableCu1 Core Cable
53
No of Conductor/Phase1
54
Size of Phase Conductor127 mm2
55
Size of Neutral Conductor127 mm2
56
Type of Race WayNon-Metalic
57
Phase Conductor Constant (C1)18594
58
Neutral Conductor Constant (C2)18594
59
F1(L-L) [F(L-L)=(1.732 X Length X Isc)/(C1 X No of Conductor X Volt)]0.068
60
F2(L-N) [F(L-L)=(1.732 X Length X Isc)/(C2 X No of Conductor X Volt)]0.097
61
M1(L-L) [M=(1/(1+F1)]0.936
62
M2(L-N) [M=(1/(1+F2)]0.911
63
Fault Current at Distribution Board Disconnection (L-L) [Isc X M1]3019Amp
64
Fault Current at Distribution Board Disconnection (L-N) [Isc X M2]4182Amp
65