Cable Size & Voltage Drop Calculationjignesh.parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com1
3
4
:Input Data Sheet::Calculation::Results:FALSE
5
6
7
Electrical Load6.25KwTotal Electrical Load6.25KW(1) No of Parallel Run of Cable:O.K1
8
Motor Load0.00KwTotal Electrical Load in KVA6.25KVA(2) Cable Short Circuit Capacity:Not Applicable10.86
9
Total Load6.25KwTotal Full Load Curent27.17Amp(3) Cable Voltage Drop:High0
10
Type of Supply SystemSingle PhaseElectrical Load Starting Current27.17Amp(4) Selection of Cable Type:Not Proper0
11
System Voltage V(L-N)230.00VoltElectrical Motor Starting Current0.00Amp(5) Motor Starting Voltage DropHigh0
12
System Voltage V(L-N)230VoltTotal Starting Current27.17Amp1
13
Demand Factor1.00Starting CosØ 0.75:Required Action for Proper Cable Selection:
14
Power Factor1.00Starting SinØ 0.66
15
Short circuit Current(If You Know)K.AmpRuning CosØ1.00
16
Allowable voltage drop at Running5%Runing SinØ0.00=>Select Higher Size of Cable to reduce Voltage Drop
17
Allowable voltage drop at Starting10%Cable Derating Factor:
18
Motor Lock Rotor Current (If You Know):AmpCable Installation MediaGround=>Select Other Type of Motor Starter
19
Motor Lock Rotor Current:2.00
X Full Load Current
Ground Temp. Correction Factor (K1)0.93=>Increase No's of Run of Cable to reduce Voltage Drop
20
Motor Starting Power Factor:0.75Group Factor for Ground (K4)1.00
21
Cable Detail:Cable Laying Depth Factor (K3)0.96Cable Selection is Not ProperFALSE
22
Type of Cable:LT XLPE (Up to 1.1 KV)Soil Correction Factor for Air (K2)1.05
23
Cable Conductor:CUTotal Derating Factor0.94
24
Size of Cable:4cX 6 Cable Calculation
25
No of Parallel Run of Cable1No'sConductor Resistance. 2.19Ohm / km
26
Cable Length (Distance)200MeterConductor Reactance0.1Mho/km Motor Starter is not Proper2
27
Cable Laying Method:Cable Current Capacity 55 Amp
28
Cable Installation MediaGround2Derating Current52Amp
29
Ground Temperature (K2)25°CMin.Required No of Runs of Cable1.00Nos
30
Type
Cable Laying ArrangementSingle Tire HorizontalVoltage Drop Calculation:
31
Distance Between each Cable0.25 mtReceving end Voltage206Volt
32
No's of Cable in Trench1Allowable voltage drop at Running11.5Volt
33
1Allowable voltage drop at Starting23Volt
34
Cable Laying on The Depth of1.5MeterS.C Capacity of Selected Cable 0.858 K.Amp
35
Soil Thermal ResistiivtyNot KnownKm/WattVoltage Drop at Starting10.3%
36
Nature of Soil (k3)Damp SoilVoltage Drop at Running10.3%
37
38
N.B: Enter Your Data in White Background Cell
39
Formula For % Voltage Drop:=
40
(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line VoltageXNo of RunX1000
41
42
43
44
45
46
47
48
49
50
51
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212