COVID-19 Indoor Infection Risk through Airborne Transmission
2
Modified Wells-Riley Model (stochastic modeling using Monte Carlo method)
3
(Simplified inputs for steady-state modeling)
4
CategoriesParametersValuesUnit systemNotes
Inputs from users
5
ReferenceProposedSI Units
No need to change (automatically calculated)
6
InputsVirusStrain typeOriginal StrainTransmission factor: 1
Switch unit systems between SI and English units
7
RoomTypeClassroomSet building types
8
Area125.0125.0m^2The grey cells are reference values for specific building type. The green cells are for manual inputs. If no manual inputs, the reference values will be applied, otherwise, the manual inputs will be used.
Extreme risk
9
Height4.04.0m0.4
10
Volume500.0500.0m^3
Moderate risk
11
OccupantTotal number7070person0.8
12
Infector number11person
Low but not-zero risk
13
Exposure time88hour27.2775
14
Vaccination
Percentage of occupants vaccinated
080%56 occupants vaccinated
15
Effectiveness of vaccines93.7%e.g. (Pfizer 2 doses): 93.7%**
16
VentilationTotal supply air flow rate2286.02286.0m^3/hourTotal supply flow rate for entire room
17
Ventilation rate (fresh air)15.6Baseline
m^3/(hour*person)
Outdoor air ventilation rate for each person
18
Outdoor air fraction47.847.8%
19
FilterMERV8MERV8Set filter for recirculated air
20
In-room devices
Portable air cleaner CADR00
m^3/(hour*person)
None (Need to reselect CADRs when the unit system is changed)
21
MaskNoNoSet face masks (cloth)
22
OutputsRisk
Infection probability (unvaccinated)
18.985 (6.731)18.985 (6.731)%Mean (SD), for unvaccinated occupants
23
Infection probability (vaccinated)
1.196 (0.424)1.196 (0.424)%Mean (SD), for vaccinated occupants
24
New infection cases (total)13.1003.138person(s)Total infection cases among unvax & vax
25
Overall infection probability18.9854.548%= New infection cases / Susceptible number
26
Risk reduction ratio/76.0%Overall infection risk reduction of the proposed case to the reference case
27
Other parametersEquivalent air change rate4.294.29/hourEquivalent ACH due to HVAC, air cleaner, particle deposition, and virus inactivation
28
Portable air cleaner CADR for entire room00m^3/hourPortable air cleaner CADR for entire room
29
* Reference 10, 11
30
** Reference 12
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100