This spreadsheet is to be used to check the adequacy of roof purlins for a specified combination of loads. The designis based on the maximum yeild strength (Mn = FySx) as stated in the AISC Manual 13th Ed. This spread sheet can only be used for load combinations with two variables. In most cases the worst case scenario is 0.6DL+W, so this should be adequate. Only the values in the highlighted cells need to be changed. (
3
Design for Roof Purlins
4
5
Using an
8" CEE Purlins
with the following properties
Use
6
Fy =36ksiFu =55ksi8" CEE Purlins
7
Self Weight, sw =
2,92ppfwith tie bars
8
Thickness, t =
2,00mm0,07874015748in1,5@ 19 ft 8 in
9
Depth, d =
199mm7,834645669in200
10
Flange Width, f =
51mm2,007874016in49
11
Lip Length, l =
12,0mm0,4724409449in12,5
12
Cross Sectional Area, A =
650
mm2
1,007502015in2
13
Ixx =3695204,167mm4
14
Ixx =8,877763521in4
15
Y =99,5
mm me
3,917322835in
16
Sx =37137,73032mm32,27in3
17
18
19
Design Requirements
20
ASCE 7-05
Designing for worst case scenario
21
2.4.1.7
Wu =
0,9D+1,2W
22
Span, L =
21ft0in
Every
23
Spacing, s =
4ft0in4 ft 0 in
24
Weight of Roof Panels =
10,0psf
25
Weight of ceiling panels =
4,2psf
26
Dead Load Pressure =
10 + 4,2 = 14,2 psf
27
Wind Load =
-50,00psf
28
29
UDL,DL =
(10 + 4,2) x 4 = 56,8 ppf
30
UDL,WL =
-50 x 4 = -200 ppf
31
32
WUDL =
(0,9 x -200) + (1,2 x 56,8)= -112 ppf
or-0,11184kpf
33
Mu =-6,2k-ft
34
35
Flexural Yeilding Limit State
36
Fy =36ksi
37
Mn = FySx =
36 x 2,27 / 12 = 6,8 k-ft
38
Ma = Mn/b =
6,8 / 1.67 = 4,07 k-ft
FAIL
39
40
Lateral Torsional Buckling
41
The compression flange is continuously braced by the roofing panels,
42
therefore, this failure mode is not applicable
43
OK
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100