Calculation Size of Neutral Earthing Transformer (NET)
3
4
5
Generator Details::Calculate Size of Neutral Earthing Transformer:
6
Generator Voltage (VL) (L-L)11KVPhase to Neutral Voltage (Vp1)6.35KVVL/1.732
7
Maximum Over Voltage14.3KV% of Force field condition for Neutral Earthing Transformer30%130%
8
Frequency50HzPhase to Neutral Voltage under Force Field Condition (Vf)8.26KVVf=Vp1x 1.3
9
Generator Transformer Details:Capacitive charging current/phase (Ic)1.24AmpIc=Vf / Xc
10
Transformer Primary Voltage33KVTotal Capacitive charging current (It)3.71AmpIt=3xIc
11
Transformer Secondary Voltage11KVRating of Neutral Earthing Transformer (Pr)40.83KVAPr=VpxIt
12
Capacitance Per Phase:Neutral Earthing Transformer overloading factor2.6
13
Generator Winding Capacitance / Phase0.22µ FaradSize of Neutral Earthing Transformer (P)16KVAP=Pr/ 2.6
14
Generator Connection Capacitance / Phase0.001µ FaradResidual Capacitive reactance (Xct)2224.12ΩXct=Xc / 3
15
Generator Transformer Capacitance / Phase0.006µ FaradRequired Resistance value at secondary side (Rsec)1.059Ω
Rsec=Xct / (NxN)
16
Generator Transformer Connection Capacitance / Phase0µ FaradRequired Grounding Resistor value at primary side (Rp)2224.12ΩRp=Xct
17
Transformer Cabale Capacitance / Phase0.0003µ FaradNeutral Earthing Transformer Secondary Current65.44Amp
18
Surge Arrestor Capacitance / Phase0.25µ FaradNeutral Earthing Transformer Secondary Resistor Current (for 30 Seconds)221.18Amp
19
Other Capacitance / Phaseµ FaradNeutral Earthing Transformer Reactance Base(Base X):3.67Ω
20
Total Zero Sequence Capacitance (C):0.47730µ FaradNeutral Earthing Transformer Reactance (X)0.15Ω
X=Xpu x Base X
21
Total Zero Sequence Capacitance Reactance to Ground (Xc):6672.35Ω/PhaseNeutral Earthing Transformer X/R Ratio0.14
22
Neutral Earthing Transformer Size:Fault current through Neutral (single line to ground fault) (If)2.86AmpIf=Vp1/Rp
23
Primary Voltage of the Grounding Transformer (Vp)11KV:Results:
24
Secondary Voltage of the Grounding Transformer (Vs)240VoltRating of Neutral Earthing Transformer (P)16KVA
25
Turns Ratio of the Grounding Transformer (N)45.83Short time Rating of Neutral Earthing Transformer 41KVA
26
Neutral Earthing Transformer % Reactance (X%)4%4%Ratio of Neutral Earthing Transformer 11000 /240Volt
27
Neutral Earthing Transformer Reactance in PU (Xpu)0.04PUNeutral Earthing Transformer Secondary Current65.44Amp
28
Neutral Earthing Transformer Base KV (Bv)0.24KVRequired Grounding Resistor value at primary side (Rp)2224.12Ω
29
Required Resistance at secondary side (Rsec)1.06Ω
30
Jignesh.Parmar, www.electricalnotes.wordpress.com, jiguparmar@yahoo.comNeutral Earthing Transformer Secondary Resistor Current (for 30 Seconds)221.18Amp
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100