Jignesh.Parmar www.electricalnotes.wordpress.com
3
4
5
:Transformer Detail::Transformer Detail:
6
Transformer Size1000KVATransformer Size1000KVA
7
Transformer Secondary Voltage:(v2)480VoltTransformer Secondary Voltage:(v2)480Volt
8
% Impedance: (z)5.75%% Impedance: (z)5.75%
9
Allowable Voltage Drop in System:10%Allowable Voltage Drop in System:10%
10
:Motor Detail ( Only One No of Motor)::Motors Detail ( More Than One No of Motor):
11
Motor Size:300KwTotal KW of Three Phase Motors:300Kw
12
Volt (vm): (L-L)460VoltTotal KW of Single Phase Motors:5Kw
13
Power Factor:0.8Volt: (L-L)460Volt
14
Motor KVA240KVAVolt: (L-N)266Volt
15
Motor Code: (Kva/Hp)Power Factor:0.8
16
InRush Current at Starting:(Enter If you know otherwise leave it blank)Locaked Rotor Current: (Max)450%
17
Enter Motor Full Load Current(Enter If you know otherwise leave it blank )Total Three Phase Motors Full Load Current471Amp
18
Motor Full Load Current: (ILM)471AmpTotal Single Phase Motors Full Load Current24Amp
19
Locaked Rotor Current Multiplier: (Min)4.10Total Motors Full Load Current494Amp
20
Locaked Rotor Current Multiplier: (Max)4.50Motor InRush KVA At Starting1772KVA
21
Locaked Rotor Current (L1): (Min)1930Amp
22
Locaked Rotor Current (L2): (Max)2118Amp
23
Motor InRush KVA At Starting: (IrsM)1688KVA
24
How many times Motor Starts per Hours2
25
:Calculations::Calculations:
26
Full Load Current of Transformer : (ILX)1203AmpFull Load Current of Transformer : (IL)1203Amp
27
Short Circuit Current at Transformer Secondary: (Isc)20919AmpShort Circuit Current at Transformer Secondary: (Isc)20919Amp
28
Max KVA of Transformer at Isc: Q117391KVAMax KVA of Transformer at Isc17391KVA
29
Motor InRush KVA At Starting:(IrsM)1688KVAMotor InRush KVA At Starting1772KVA
30
Voltage Drop at Transformer Secondary Due to Motor inRush: (Vd)10%90%Voltage Drop at Transformer Secondary Due to Motor inRush10.2%90%
31
Transformer Secondary Voltage433VoltTransformer Secondary Voltage431Volt
32
:Result::Result:
33
(1) Motor Full Load Current <= 65% Transformer Full Load CurrentYes(1) Motor Full Load Current <= 65% Transformer Full Load CurrentYes
34
(2) Voltage Drop at Transformer Secondary Due to Motor inRushLow(2) Voltage Drop at Transformer Secondary Due to Motor inRushHigh
35
(3) Transformer Size:(20% Added due to motor starts more than once/Hour)1200Kva(3) Transformer Size:1000KVA
36
Size of Transformer is AdequateIncrease Size of Transformer
37
38
39
Calculation Formulas:
40
ILX=KVA/(1.732xv2)
41
ILM=(Kwx1000)/(1.732xVmxP.F)
42
Isc=ILx/z
43
Q1=(v2xISCxILMx1.732)/1000
44
IrsM=(VmxL2x1.732)/1000
45
Vd=IrsM/Q1
46
47
48
49
Code Letter (KVA per HP) -Locked Rotor Current
50
Motor CodeMinMax
51
1A3.15
52
2B3.163.55
53
3C3.564
54
4D4.14.5
55
5E4.65
56
6F5.15.6
57
7G5.76.3
58
8H6.47.1
59
9J7.28
60
10K8.19
61
11L9.110
62
12M10.111.2
63
13N11.312.5
64
14P12.614
65
15R14.116
66
16S16.118
67
17T18.120
68
18U20.122.4
69
19V22.5