LOCATIONAir fllow rate (EACH) (CMH)External Static Pressure (pa)
2
1basement car parkCSF-B-01A & 01BBASEMENT210700600
3
CEF-B-01A & 01B210700600
4
2Sprinkler pump roomSF-B-01A & 01B27100500
5
EF-B-01A & 01B27100500
6
3Domestic Water Transfer PumpSF-B-02A & 02B213700500
7
EF-B-02A & 02B213700500
8
4CSRSF-B-0317000500
9
EF-B-0317000500
10
5MDFSF-B-0411200500
11
EF-B-0411200500
12
6GREASE INTERCEPTORSF-B-0512200350
13
SF-B-0512200350
14
7F&B STORAGE SF-B-06A & 06B21600350
15
EF-B-06A & 06B21600350
16
8HOUSE KEEPINGSF-B-07A & 07B21300350
17
EF-B-07A & 07B21300350
18
9CLEAN LINENSP-B-08A & 08B2600350
19
EF-B-08A & 08B2600350
20
10DIRTY LINENSF-B-09A & 09B2400350
21
EF-B-09A & 09B2400350
22
11EJECTOR PITSF-B-1011000350
23
EF-B-1011000350
24
12SERVER ROOMEF-B-111500350
25
13BASEMENT TOILET TEF-B-0111200350
26
14STAIRCASE 01ASF-1-01A & 01B1ST STOREY2600250
27
15STAIRCASE 02ASF-1-02A & 02B2600250
28
16COACH PARKINGSF-1-03A & 03B231300500
29
17TRANSFORMER ROOMSF-1-04A & 04B221000500
30
EF-1-01A & 01B221000500
31
18BIN CENTERSF-1-0511800300
32
EF-1-0211800300
33
19PANTRY KEF-1-01180001000
34
KSF-1-0117200500
35
20TOILETTEF-1-011400250
36
21SWITCH GEARSF-2-01A & 01B2ND STOREY26000500
37
EF-2-01A & 01B26000500
38
22ALL DAY DAINNNING KITCHENKEF-2-011320001000
39
KSF-2-01128800500
40
232nd Storey DUBBLE SLABSF-2-0218100500
41
EF-2-0218100500
42
24ALL DAY DAINNNING TOILETTEF-2-0111200300
43
25SERVER ROOMEF-13-0113TH STOREY1500350
44
26STARECASE01SPF-R-01A & 01B230000500
45
27STARECASE02SPF-R-02A &02B230000500
46
28STARECASE01SF-R-0114100500
47
29STARECASE02SF-R-0214100500
48
30FIRE LIFT LOBBYSF-R-03A & 03B25450/10900500
49
31SMOKE STOP LOBBYSF-R-04A & 04B 21650/3300500
50
32HOTEL CORIDORCPF-R-01A & 01B234400600
51
33GYMEF-R-11600300
52
34GUEST ROOM TOILET TEF-R-01 TO 03312060600