ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
Power Factor Correction Calculation
2
3
Follow the Steps Below to Calculate the Power Factor Correction required for your installation.
4
5
Click-On Cells with Blue Text to Modify Values, Results will be Displayed in Green
6
7
Step 1. Calculate Actual Load (kW)
8
9
(Load) Power kW = Volts V x √3 x Current I x Power factor Pf
10
11
400
Nominal Voltage (V)
12
Non-Corrected Load (kVA)
692.81000
Non-Corrected Current (Amps)
13
Actual Load (kW)
415.70.600
Non-Corrected Power Factor (CosΦ)
14
15
Figures for Current (Amps) and Power Factor (CosØ) can be either Measured or Calculated
16
17
Step 2. Calculate Required Power Factor Correction (kVAr)
18
19
Power Factor Correction kVAr = Power kW (TanΦi - TanΦd)
20
Φi = Cosˉ¹ Initial Power Factor Pf
21
Φd = Cosˉ¹ required Power Factor Pf
22
23
415.7
Actual Load (kW)
24
Correction Required (kVAr)
417.60.600
Non-Corrected Power Factor (CosΦ)
25
0.950
Required Power Factor (CosΦ)
26
27
Step 3. Calculate Actual Power Factor Correction (kAVr)
28
29
Actual Power Factor Correction Pf = Cos (Tanˉ¹ (TanΦi - Correction kVAr)
30
Power kW
31
32
400
Correction Applied (kVAr)
33
Corrected Power Factor (CosΦ)
0.938415.7
Original Load (kW)
34
0.600
Non-Corrected Power Factor (CosΦ)
35
36
Typical Power Factor Correction available in multiples of 25kVAR's, for further details
37
please Contact Blakley Electrics Technical Department.
38
39
Energy Savings for Above Power Factor Correction
40
41
Initial Current
1000Amps
Original Load
693kVA
42
Corrected Current
640Amps
Corrected Load
443kVA
43
Reduction in Current
360Amps
Reduction in Load
249kVA
44
Annual CO2 Savings*
62800kg CO2
45
46
*C02 Savings based on 500 hours per month.
47
48
Click to View Product Data Sheet
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
Blakley calculator (version 2.0) Blakley Electrics Ltd.
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100