ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
TestMeasuredTypical/ExpectInterpretation
2
IR (5 kV, 20 °C)350 MΩ≥100–200 MΩAcceptable but not robust
3
PI1.6≥2.0 desirableMoisture suspicion
4
Tan-δ (HV-E) @10 kV0.8%≤0.5–0.7% (age dependent)Elevated losses
5
Oil BDV42 kV/2.5 mm≥50–60 kV (new)Degraded oil
6
Moisture (oil)25 ppm<10–15 ppm (good)Wet insulation trend
7
DGA – H₂ 180 ppm; C₂H₄ 120 ppm; C₂H₂ 5 ppm
RisingThermal fault <700 °C; negligible arcingHot spot likely (OLTC? winding?)