Automatic Capacitor Bank Sizing
6
7
SELECTING AN AUTOMATIC CAPACITOR SIZE
Example: How much kVAR is required to correct an entire
8
480V system to a 90% power factor when the peak kilowatt
9
The following calculator is used to determine the capacitor kVAR
demand month was 620kW at a 65% power factor?
10
required to improve PF of a single load or entire power system.
11
Actual power factor, peak kilowatt demand, desired PF and
Formula: kVAR = kW x kW FACTOR
12
system voltage are required. The best source for this information
13
is the monthly utility bill or other local monitoring equipment. A
From the kW FACTOR calculator below , the FACTOR
14
calculation of each months data for a 12 month period is
is 0.685
15
recommended to determine the maximum kVAR required.
16
Therefore: kVAR = 620 x .685 = 425
17
18
19
20
Existing P.F (%)
76
21
22
Desired P.F. (%)
95
23
24
Load (kW)
2000
25
26
27
28
29
Kilowatt Factor0.526
30
31
32
Required kVAR1053