ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
Transformer Fault Current Calculation
2
3
Transformer Impedance
4
Transformer Impedance is measured in Percent Impedance, this is the Percentage of Rated Primary
5
Voltage applied to the Transformer's primary winding in order for the rated secondary Full Load Current to
6
flow in the secondary winding (this test is preformed with the primary winding connected to a Variac
7
or variable supply and the secondary winding shorted-out).
8
Transformer Impedance values may vary but typically Blakley Electrics transformers will be between
9
4 to 5% of primary Voltage. For further details please contact Blakley Electrics' Technical department.
10
11
Impedance Voltage Vz =Primary Volts V x Percent Impedance Z%
12
100
13
Click-On Cells with Blue Text to Modify Values, Results will be Displayed in Green
14
Any Warnings will be Displayed in Red and Full Results are Displayed Below.
15
16
Primary Volts (V)
10000Vp
17
Secondary Volts (V)
400Vs
18
Transformer Rating (VA)
1000VA
19
Transformer Configuration
Three
20
Percent Impedance (Z%)
6Z%
21
Impedance Voltage (Vz)600.00
22
23
Transformer Maximum Fault Current
24
25
Transformer Secondary Fault Type
Line to Earth
26
27
Maximum Fault Current A=100x Secondary Full Load Current I
28
Impedance Volts Vz%
29
30
Maximum Fault Current (A)
23.3
31
Maximum Fault Current (kA)
0.021.44
Secondary Current (I)
32
33
This is the Maximum Current that can be achieved at the Transformer's Secondary Terminals and
34
doesn’t allow for any Impedance in the primary or secondary circuitry to and from the transformer.
35
36
Transformer Maximum Fault Current Allowing for Loop Impedance
37
To Calculate the Maximum Fault Current that can be achieved in a circuit fed by a transformer
38
we refer to the below formula. This formula calculates the loop impedance at the end of a circuit fed
39
from the secondary winding of a transformer.
40
When calculating Fault Loop Impedance Select the Correct Transformer Type Above.
41
Three Phase Transformers Divide the Values for Vs secondary Voltage by √3 and the VA by 3
42
For Centre Tapped to Earth (CTE) transformers halve the values for Vs and VA .
43
For RLV / 110V CTE Disconnection Times & Zs figures refer to BS7671:2008, 411.8 Table 41.6
44
45
Zsec = Zp x Vs ² VpZ%Vs²+ (R1 + R2)
46
100VA
47
0.46Ω
Zp = Loop impedance of primary circuit including Source (Ze + 2R1)
48
10000V
Vp = Primary Voltage
49
230.9V
Vs = Secondary Voltage
50
333VA
VA = Transformer Rating
51
6%
Z% = Transformer percentage Impedance
52
0.2Ω
(R1 + R2) = Resistance of Secondary circuit Phase and Protective conductor
53
54
Primary Circuit Impedance (Ze + 2R1)
0.46
Zp (Ze + 2R1) Ohms
55
Secondary Circuit Impedance (R1 + R2)
0.2
(R1 + R2) Ohms
56
Total Impedance (Zsec)
9.8065Ohms
57
58
Transformer Actual Earth Fault Current
59
60
To calculate the Actual Fault Current in a transformer we can refer to the below formula taken from
61
BS7671:2008, 411.4.5 and use the above figure for the transformers Total Impedance (Zsec).
62
63
Earth Fault loop Impedance Zs = Voltage to Earth UoFault Current Ia = Voltage to Earth Uo
64
Fault Current IaLoop Impedance Zs
65
66
Actual Secondary Fault Current (Ia)
23.5Amps
67
Primary Fault Current I = Secondary Fault Current Ia xSecondary Voltage Vs
68
Primary Voltage Vp
69
Actual Primary Fault Current (I)
0.9Amps
70
71
72
73
Blakley calculator (version 2.0) Blakley Electrics Ltd.
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100