PROYECTO=CONGRESSRES.DEL TERR=1.43Nv =6.00Ep =2825
RESULTADOS :
2
UBICACION=PLANTA VICTORIA SUBESTACION 3Ig =2,107.46La =12.40Es =742Em <= EcOK
3
PROPIETARIO=PRODUCTOS KRAFTÞs =1.00Lb =7.35Ec =829Es <= EpOK
4
BANCO DE TRANS=
1,500 KVA.Ts =0.50Lv =3.05Em =732Rg =3.46
5
TENSION=
23,000 V.X/R =20.00D =3.10R "NOM" <=10.00
6
IMPEDANCIA Z%=
6.70Cp =1.00h =0.60
7
FACTOR ASIMETRIA=
1.25Tm =450.00ho =1.00
8
ELECTRODOS EN ESQ.=
SIhs =0.10
9
N°.DE ELEC. PRUEBA=
4.00Na =4.00
10
LARGO ELEC.PRUEBA=
0.30Nb =5.00
11
12
PROYECTO : CONGRESS5/4/2026
13
14
15
16
UBICACION : PLANTA VICTORIA SUBESTACION 3
17
18
PROPIETARIO :PRODUCTOS KRAFT
19
CALCULO DE LA RED DE TIERRAS PARA SISTEMA TRIFASICO, CON UNA CAPACIDAD INSTALADA
20
(O BANCO DE TRANSFORMACION ) EN SUBESTACION DE 1500 KVA., A 23000 V., 3F, 3H, 60Hz.
21
22
23
OBJETIVOS :
24
25
1.- VERIFICAR QUE LOS POTENCIALES DE CONTACTO Y DE PASO EN LA
26
RED DE TIERRAS DE LA SUBESTACION NO EXCEDAN LOS VALORES
27
LIMITE DE LOS POTENCIALES TOLERABLES POR EL CUERPO HUMANO.
28
29
2.- VERIFICAR Y GARANTIZAR QUE LA RESITENCIA A TIERRA DE LA RED,
30
SE ENCUENTRE DENTRO DEL RANGO DE VALORES RECOMENDADOS
31
Y ESTABLECIDOS POR LA "NOM-001-SEDE-1999".
32
33
34
PROCEDIMIENTO DE CALCULO :
35
36
UTILIZAREMOS EL METODO APROBADO POR LA "IEEE" EN "GUIDE FOR
37
SAFETY IN A.C. SUB-STATION GROUNDING", SEGUN LA NORMA : 80-1986,
38
AUTORIZADO Y CONGRUENTE CON LA NORMA OFICIAL MEXICANA VI -
39
GENTE, "NOM-001-SEDE-1999".
40
41
NORMAL =Q45
42
1.43
CONSIDERACIONES Y ABREVIATURAS :
43
TENSIONPOTENCIARESISTENCIA
44
0.14
RESISTENCIA DEL TERRENO ( * )
R=1.43ohm.
(VERIFICADO EN FORMA PRACTICA EN LA OBRA)
23,000.001,500.00
45
1.002.0010.0025.0010.005.00
46
SEPARACION ENTRE ELECTRODOS ADYACENTES ( ** )
a=6.00m.
47
48
PROFUNDIDAD DE ELECTRODOS ( ** )
b=0.30m.
49
( ** ) VALORES Y DATOS DE PRUEBAS DE CAMPO, ESTIMADOS.
50
RESISTIVIDAD DEL TERRENO
Þ =54.03ohm/m.
51
52
RESISTIVIDAD SUPERFICIAL
Þs =4657.50ohm/m.
(CONSIDERANDO CONCRETO)
53
2,107.46
54
CORRIENTES DE FALLAS MONOFASICAS
Ig=2107A.
55
56
TIEMPO DE DURACION DE LA FALLA
Ts=0.50seg.
57
58
RELACION X/R EN EL BUS DE ACOMETIDA
X/R=20.00
59
60
FACTOR DE DECREMENTO
Df=1.051
61
62
FACTOR DE PROYECCION
Cp=1.00TsX/R=10X/R=20X/R=30X/R=40
63
1.001.011.031.041.05
64
CORRIENTE MAXIMA DE MALLA
IG=2215A.0.501.031.051.081.10
65
66
TEMPERATURA MAXIMA EN LOS CONECTORES
Tm=450.00° C.
67
68
FACTOR PARA CALCULAR Cmils/Amp.
Factor=6.60
69
70
AREA REQUERIDA DEL CONDUCTOR (Cmils)
Ar=Cmils.
71
72
AREA DEL CONDUCTOR A USAR (Cmils)
Ac=211600Cmils.
73
74
CALIBRE DEL CONDUCTOR A USAR EN LA RED
Cc=4/0 AWG
75
76
DIAMETRO DEL CONDUCTOR EN LA RED
d=0.01168m.
77
78
FACTOR DE REFLEXION
K=-0.9771
81
82
ESPESOR DE LA CAPA SUPERFICIAL
hs=0.1000m.
83
84
FACTOR DE REDUCCION
Cs=0.5805
85
86
POTENCIAL DE PASO TOLERABLE
Ep=2825V.
87
88
POTENCIAL DE CONTACTO TOLERABLE
Ec=829.31V.
89
90
N° DE CONDUCTORES EN PARALELO
Na=4.00
91
92
N° DE CONDUCTORES TRANSVERSALES
Nb=5.00
93
94
N° DE VARILLAS DE LA RED
Nv=6.00
95
96
LONGITUD DE LOS PARALELOS DE LA RED
La=12.40m.
97
98
LONGITUD DE LOS TRANSVERSALES DE LA RED
Lb=7.35m.
99
100
LONGITUD DE LAS VARILLAS DE TIERRAS
Lv=3.05m.
101
102
ESPACIAMIENTO ENTRE COND. PARALELOS
D=3.10m.