COINCIDENCE FACTORS
1 0.5 0.1 1, 0.5, 0.1
4
(X)(Y)(Z)
5
EQUIPMENT
6
VENR
kW = ABSORBED LOAD(kVA) * COSp / EFFICIENCY
kVAr = kW * TANp
7
ISOEPOWER
kW = ABSORBED LOAD(HP) * 0,746 / EFFICIENCY
8
TSNSEFFICIENCYFACTOR
9
AE-T(PF)
10
EQUIPMENT
DESCRIPTION
LNEA ABSORBEDNON- MOTOR MOTORLOAD AT LOADAT LOAD
11
NO.TSR LOADRATING RATINGFACTORFACTOR FACTOR CONTINUOUS INTERMITTENT STAND - BYREMARKS
12
IST AND SPARES
13
AEI
14
LNN
15
TGkVA or HPkVAHP kWkVAr kWkVArkWkVAr
16
1XXX-YY-1LOAD 1X40.50 45.00 0.90 0.90 0.90 40.50 19.62
17
2XXX-YY-2LOAD 2X9.49 10.55 0.90 0.90 0.85 8.96 5.55
18
3XXX-YY-3LOAD 3X18.00 20.00 0.90 0.90 0.88 17.60 9.50
19
4XXX-YY-4LOAD 4X18.00 20.00 0.90 0.88 0.88 15.25 8.23
20
5XXX-YY-5LOAD 5X54.00 60.00 0.90 0.90 0.90 44.74 21.67
21
6XXX-YY-6LOAD 6X112.50 125.00 0.90 0.93 0.93 90.21 35.65
22
7XXX-YY-7LOAD 7X112.50 125.00 0.90 0.93 0.93 90.21 35.65
23
8XXX-YY-8LOAD 8X4.50 5.00 0.90 0.85 0.85 3.95 2.45
24
9XXX-YY-9LOAD 9X9.00 10.00 0.90 0.90 0.85 7.46 4.62
25
10XXX-YY-10LOAD 10X9.00 10.00 0.90 0.88 0.85 7.63 4.73
26
11XXX-YY-11LOAD 11X135.00 150.00 0.90 0.93 0.93 108.25 42.78
27
12XXX-YY-12LOAD 12X135.00 150.00 0.90 0.93 0.93 108.25 42.78
28
13XXX-YY-13LOAD 13X4.50 5.00 0.90 0.85 0.85 3.95 2.45
29
14XXX-YY-14LOAD 14X4.50 5.00 0.90 0.85 0.85 3.95 2.45
30
15XXX-YY-15LOAD 15X4.50 5.00 0.90 0.85 0.85 3.95 2.45
31
16XXX-YY-16LOAD 16X4.50 5.00 0.90 0.85 0.85 3.95 2.45
32
17XXX-YY-17LOAD 17X4.50 5.00 0.90 0.85 0.85 3.95 2.45
33
18XXX-YY-18LOAD 18X4.50 5.00 0.90 0.85 0.85 3.95 2.45
34
19XXX-YY-19LOAD 19X9.00 10.00 0.90 0.88 0.85 7.63 4.73
35
20XXX-YY-20LOAD 20X9.00 10.00 0.90 0.88 0.85 7.63 4.73
36
21XXX-YY-21LOAD 21X18.00 20.00 0.90 0.88 0.85 15.25 9.45
37
22XXX-YY-22LOAD 22X9.00 10.00 0.90 0.88 0.85 7.63 4.73
38
23XXX-YY-23LOAD 23X9.00 10.00 0.90 0.88 0.85 7.63 4.73
39
24XXX-YY-24LOAD 24X13.50 15.00 0.90 0.88 0.90 10.30 4.99
40
25XXX-YY-25LOAD 25X112.50 125.00 0.90 0.93 0.93 90.21 35.65
41
26XXX-YY-26LOAD 26X22.50 25.00 0.90 0.90 0.93 23.25 9.19
42
MAX NORM RUNNING PLANT LOAD:
PEAK LOAD:
PF W/O COMPENSATION ( COSp ):
0.91
43
( X * CONTINOUS LOAD + Y * INTERMITTENT LOAD )
( X * CONTINOUS LOAD + Y * INTERMITTENT LOAD + Z * STAN-BY AND SPARES LOAD )
TOTAL364.41 165.99 150.44 67.50 221.33 92.61
44
482.88 kVA439.64 kW506.88
kVA
461.77 kW
PF W/ COMPENSATION ( COSpd1 ):
0.91
45
199.74 kVAr209.00
kVAr
46
kW; kVAr; kVA =(kW2 + kVAr2)1/2
kW; kVAr; kVA =(kW2 + kVAr2)1/2
kVA =(kW2 + kVAr2)1/2
400.44 164.89 239.93
REQUIRED CAPACITOR RATING :
0
47
COINCIDENCE FACTORS X,Y AND Z SHALL EQUAL
1, 0.5, 0.1
RESPECTIVELY.
kVAr = kW * (TANp - TANpd1 )
48
NOTES:
49
A) ABSORBED LOADS:
B) CONSUMED LOADS:
"STAND - BY AND SPARES": LOADS REQUIRED
50
- FOR PUMPS, SHAFT LOAD ON DUTY POINT;
"CONTINUOUS": ALL LOADS THAT MAY CONTINUOUSLY
IN EMERGENCIES, SUCH AS FIRE - WATER
51
- FOR INSTRUMENT., COMPUTERS, COM., AIR COND.,
BE REQUIRED FOR NORMAL OPERATION, INCLUDING
PUMPS. STAND-BY ELECTRIC MOTORS FOR
52
THE REQ'D LOAD DURING FULL OPER. OF PLANT;
LIGHTING AND AIR-CONDITIONING.
TURBINE-DRIVEN EQUIPMENT. ALL SPARE
53
- FOR LIGHTING DURING DARK HOURS;
" INTERMITTENT " THE LOADS REQUIRED FOR
ELECTRIC MOTORS.
54
- FOR WORKSHOPS, THE AVERAGE TOTAL LOAD
INTERMEDIATE PUMPING, STORAGE, LOADING, ETC. AND
55
IN NORMAL FULL OPERATION.
CONVENIENCE RECEPTACLES AND WORKSHOP LOADS.
CONTR. JOB NO.
56
PROJECT TITLE:
PRINCIPLE: CONSIGNEE:
57
FIRST ISSUE
REV. LETTER
0 12 340
UTILITY DATA - ELECTRICAL
58
DATE
DOCUMENT No.
SHEET No
59
REV.
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100