COOLING AND DEHUMIDIFYING LOAD ANALYSIS
2
3
Project NameOFFICE BUILDINGLocationNEW DELHILatitude :28.4Altitude :216
4
AddressNEW DELHIPsychrometric data:DBWB%RHDPGr/Lb
Daily Range (ᵒF)
5
Outside107.274.521.459.576.225
6
Space Used ForCOM. LABRoom 7562.55055.12564.9
7
Area of Room180Sq.ftDifference32.2124.37511.3
8
Volume of Space1800Cu.ft
9
ROOM SENSIBLE HEAT
10
Solar Gain Glass :Heat (BTU/Hr)
Ventilation air requirement
CFM
11
ITEMArea (ft2)Solar GainSHGCPeopleCFM/Person
12
Glass251650.21866.251010100.00
13
Glass70180.21264.60ACH method :
Volume (ft3)
ACH
14
Glass0.000.00
15
Glass0.00Area (ft2)CFM/ft2
16
Glass0.001800.1221.60
17
Sky light0.00total ventilation air selected121.6
18
Solar & Trans. Gain Walls & Roof :
19
ITEMArea (ft2)eq.T(F)U Factor
20
Wall143430.362213.64
Infiltration based on door usage
21
Wall140230.361159.20Door typePeopleUsageCFM
22
Wall0.00Revolving0.00
23
Wall0.00Open Door
24
Wall0.00
Infiltration based on door & Window Crack
25
Roof Sun180520.474399.20
Crack Length (ft)
CFM/FtCFM
26
Roof Shaded0.000.00
27
Trans Gain Except Walls & Roof :ACH method :
Volume (ft3)
ACHCFM
28
ITEMArea (ft2)T(F)U Factor18000.515.00
29
Glass9532.20.31948.29total infiltration air selected15
30
Partition3027.20.4326.40
31
Door0.00
32
Ceiling0.00
Effective Sensible Heat Factor
ESHF
33
Floor18027.20.452203.20ERSH :25098.64ERLH :1846.630.93
34
Infiltration & Outside Air :
Grand Sensible Heat Factor
GSHF
35
Infiltration(CFM)T(F)ConstantGSH :28904.53ERLH :2687.570.91
36
1532.21.08521.64
Apparatus dew point
37
Bypass FactorConstant
Selected ADP in F from table
54.15
38
121.632.20.11.08422.88
39
Internal Heat :Ventilation typedirect ventilation
40
People numberSensible heat gain (Btu/hr/person)
41
102452450.00Entering Coil Temperature (ᵒF), ton-coil
42
Power (Watts)Conversion usage factor
43
35003.410.55967.50Mixed Air Temperature (ᵒF), tmix(tR.A x CFMR.A)+(tF.A x CFMF.A)
44
lights (Watts)ConversionUsage factorballast factorCFMS.A
45
2523.4111.251074.15Return air temperature (ᵒF)tR.A85
46
Room Sensible Heat =22816.95Return air CFMCFMR.A627.9
47
Safety factor in percentage =
10Fresh air temperature (ᵒF)tF.A107.2
48
Effective Room Sensible Heat =25098.64Fresh air CFMCFMF.A121.6
49
ROOM LATENT HEATSupply air CFMCFMS.A749.5
50
Infiltration(CFM)humidity difference, ∆W(gr/lb)ConstantMixed Air Temperature (ᵒF), tmix88.60176117
51
1511.30.68115.26Tcoil (F) =(1-Bypass factor)(tmix - ADP)31.00658506
52
Outside Air CFM
∆W(gr/lb)constantbypass factor
53
121.611.30.680.193.44Supply Air Flow (CFM) CFMS.A sensible heat
54
PeopleLatent heat gain (Btu/hr/person)1.08 x ∆Tcoil
55
101551550.00sensible heat25098.64
56
Room Latent Heat Sub Total =1758.70Supply air flow (CFM), CFMS.A 749.50
57
Safety factor in percentage =
5safety factor in percentage =10
58
Effective Room Latent Heat =1846.63Total supply air flow in CFM824.45
59
Effective Room Total Heat =26945.27
60
Outside Air Heat
61
Sensible heat
62
Outside Air Flow (CFM)Temp Diff:constant1 - Bypass factorTr2.63
63
121.632.21.080.93805.88544
64
Latent heatCFM824.45
65
Outside Air Flow (CFM)humidity Diff:constant1 - Bypass factor
66
121.611.30.680.9840.93696ESHF0.93
67
Return Duct Gain & Pump Losses in percentage=
68
Grand Total Heat =31592.10GSHF0.91
69
70
Tonnage =2.63ADP54.15