Cooling load calculations
4
5
Note:
6
Inputs in green boxes are to be given from psychrometric charts
7
Inputs in orange boxes are to be given from ISHRAE/ ASHRAE handbooks
8
Other inputs are to be given in grey coloured boxes only
9
Detailed notes are marked for red cornered boxes
10
11
Project locationPUNE
12
Building type COMMERCIAL
13
Project BANQUET HALL
14
15
Project area (sq.ft)4200.00
16
Ceiling height (ft)11.00
17
Space volume (Cu.ft)46200.00
18
Design conditionsSummer mean monthly max for the month of mayThe distribution changes as per the input values
19
DBT (°F)(°C)WBT (°F)(°C)RH(%)HR(GR/lb)
20
Outside design conditions
100.9438.3088.6231.4660.00175
21
Inside design conditions75.2024.0062.8517.1450.0066
22
Difference25.7425.7710.00109.00
23
24
Room sensible heat loadArea in sq.ftEqv. temp difference (ΔT)(°F)
(Btu/(hr ft2 oF)
(Btu/hr)By-pass factor (BF)0.12
25
Solar heat gain through glass
UHeat gainContact factor (CF)0.88
26
Glass- N136.00x28.00x1.2104607.68
27
Glass- NExx0.00Ventilation
28
Glass- E68.00x163.00x1.21013411.64CFM per person5.00x
No. of persons
2001000.00
29
Glass- SExx0.00CFM per sq.ft0.06x4200.00252.00
30
Glass- Sxx0.00Air change per hour=1
31
Glass- SWxx0.00Total CFM46200.00x1=770.00
32
Glass- Wxx0.00
33
Glass- NWxx0.00
34
Sum18019.32
35
36
Room sensible heat loadArea in sq.ftEqv. temp difference (ΔT)(°F)
(Btu/(hr ft2 oF)
(Btu/hr)
37
Solar heat gain through wall
UHeat gain
38
Wall- N689.00x10.00x0.3552445.95
39
Wall- NExx0.00
40
Wall- E548.00x30.00x0.3555836.20
41
Wall- SExx0.00
42
Wall- S825.00x20.00x0.3555857.50 Effective Room Sensible Heat Factor= Effective Room Sensible Heat/
43
Wall- SWxx0.00 Effective Room Total Heat
44
Wall- Wxx0.00 Effective Room Sensible Heat Factor= 0.71
45
Wall- NWxx0.00
46
Sum14139.65
47
48
Solar heat gain through roof
4200.00x14.00x0.29017052.00 Outside Air Sensible Heat (OASH)=
49
Total CFM xΔDBT xCF x1.0818836.74
50
Transmission gains except
Area in sq.ftTemp difference (ΔT)(°F)
(Btu/(hr ft2 oF)
(Btu/hr)
51
walls and roofsUHeat gainOutside Air Latent Heat (OALH)=
52
Glass204.00x25.74x1.2106353.66Total CFM xΔHR xCF x0.6850223.71
53
PartitionW-Wall 616.00x20.74x0.5046439.02
54
Floor4200.00x20.74x0.0806968.64 Outside Air Total Heat (OATH)=69060.45
55
56
Infiltration andCFMTemp difference (ΔT)(°F)FactorApparatus Dew Point (ADP)
57
outside airIndicated ADP (°F)0.00
58
Infiltrated airx25.74x1.080.00Selected ADP (°F)54.00
59
Outside air770.00x25.74x0.12962568.65
60
Dehumidified Rise
61
Internal heat gain(Room DBT- ADP) x CF (°F)18.656
62
People
No.of people
200x255
Btu/person
x51000.00
63
Lighting4200.00x1.00x3.4114322.00Dehumidified Air quantity (CFM)
64
Appliances, equipments150x3.41511.50Effective Room Sensible Heat7159.01CFM
65
sum65833.50Dehumidified Rise x 1.08
66
This parameter is useful while 3364.73L/s
67
Total137374.44selecting the capacity of AC system
68
Leak loss, Safety factor, etc5-15 % of total value6868.72
69
70
Effective room sensible heatTotal144243.16Grand Sub total heat load =271944.74
71
72
Room latent heat gainLeak gain, safety factor (1-3%)8158.34
73
Infiltrated airx109.00x0.680.00
74
Outside air770.00x109.00x0.08166848.69Grand Total Heat Load =280103.08
75
People
No.of people
200x245
Btu/person
49000.00Btu/hr
76
sum55848.69
77
Tonnage =23.34
78
Leak loss, Safety factor, etc2.5%-5% of total value2792.43TR
79
80
Effective room latent heatTotal58641.12Notes:
81
82
Effective room total heat202884.29
83
84
85
86
Source%Heat gain
87
Glass8.7024372.98
88
Walls and floor9.8327547.31
89
Roof 6.0917052.00
90
Ventilation28.0278477.78
92
People35.70100000.00
93
Lighting and equipments5.3014833.50
94
Other factors6.3617819.50
95
Total100.00280103.08Btu/hr