ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
Water Testing Results -
Tillamook Junior High
2
Action Level is 15 parts per billion (ppb)
3
Fixture Location/DescriptionFixture ID #Test DateTest Result
4
Rm.1 Storage Room Faucet21970400-001SF11/2/20221.32
5
Rm.2 Storage Room Faucet21970400-002SF11/2/20221.09
6
Rm.4 North Wall Faucet21970400-005CF11/2/20221.11
7
Rm.5 South Wall Faucet21970400-006CF11/2/20221.31
8
Rm.6 South Wall Faucet21970400-007CF11/2/20221.2
9
Rm.7 South Wall Faucet21970400-008CF11/2/20221.49
10
Rm.8 South Wall Faucet21970400-009CF11/2/20221.22
11
Boys Bathroom South Hall Left21970400-010BF11/2/20222.24
12
Boys Bathroom South Hall #221970400-011BF11/2/20221.58
13
Boys Bathroom South Hall #321970400-012BF11/2/20221.14
14
Bottle Fill Station South Hall21970400-013WB11/2/20221.02
15
Drinking Fountain South Hall21970400-014DW11/2/2022ND
16
Girls Bathroom South Hall Left21970400-015BF11/2/20221.11
17
Girls Bathroom South Hall #221970400-016BF11/2/20221.2
18
Girls Bathroom South Hall #321970400-017BF11/2/20221.14
19
Library South Wall Faucet21970400-018SF11/2/20221.13
20
Staff Breakroom Across From Rm 1721970400-019SF11/2/20224.19
21
Girls Bathroom North Hall Left21970400-020BF11/2/20222.64
22
Girls Bathroom North Hall Right21970400-021BF11/2/20221.39
23
Bottle Fill Station North Hall21970400-022WB11/2/20221
24
Drinking Fountain North Hall21970400-023DW11/2/2022ND
25
Boys Bathroom North Hall Left21970400-024BF11/2/20221.18
26
Boys Bathroom North Hall #221970400-025BF11/2/20221.45
27
Boys Bathroom North Hall #321970400-026BF11/2/20221.43
28
Rm.9 North Wall Faucet21970400-027CF11/2/20222.3
29
Rm.10 North Wall Faucet21970400-028CF11/2/20221.43
30
Rm.11 North Wall Faucet21970400-029CF11/2/20222.5
31
Rm.12 North Wall Faucet21970400-030CF11/2/20221.23
32
Rm.13 South Wall Faucet21970400-031CF11/2/20224.23
33
Rm.16 South Wall Faucet Left21970400-032KF11/2/20221.75
34
Rm.16 South Wall Faucet #221970400-033KF11/2/20225.7
35
Rm.16 South Wall Faucet #321970400-034KF11/2/20221.99
36
Rm.18 South Wall Faucet21970400-035SF11/2/2022ND
37
Main Office Faucet21970400-036SF11/2/2022ND
38
Dean of Students Office Faucet21970400-037SF11/2/2022ND
39
Principal Office Faucet21970400-038SF11/2/2022ND
40
Breakroom Faucet North Wall21970400-039SF11/2/2022ND
41
Breakroom Bathroom Faucet West21970400-040BF11/2/2022ND
42
Breakroom Bathroom Faucet East21970400-041BF11/2/2022ND
43
Bottle Fill Station Main Office Hall21970400-042WB11/2/2022ND
44
Drinking Fountain Main Office Hall21970400-043DW11/2/2022ND
45
Health Rm Bathroom Faucet21970400-044BF11/2/20222.09
46
Health Rm Nurse's Sink21970400-045NS11/2/20221.8
47
Kitchen Bathroom Faucet21970400-046BF11/2/20221.94
48
Kitchen Faucet West Wall21970400-047KF11/2/2022ND
49
Cafateria Faucet South Wall21970400-054KF11/2/2022ND
50
Band Room Faucet21970400-055CF11/2/2022ND
51
Band Room Drinking Fountain21970400-056DW11/2/2022ND
52
Girls Bathroom West Hall Left21970400-057BF11/2/2022ND
53
Girls Bathroom West Hall Right21970400-058BF11/2/2022ND
54
Boys Bathroom West Hall Left21970400-059BF11/2/2022ND
55
Boys Bathroom West Hall Right21970400-060BF11/2/2022ND
56
Bottle Fill Station West Hall21970400-061WB11/2/2022ND
57
Drinking Fountain West Hall21970400-062DW11/2/2022ND
58
Rm.22 Faucet Left21970400-063CF11/2/2022ND
59
Rm.22 Faucet Right21970400-064CF11/2/2022ND
60
Rm.23 South Wall Faucet21970400-065CF11/2/2022ND
61
Boys Locker Room Faucet Left21970400-066BF11/2/2022ND
62
Boys Locker Room Faucet Right21970400-067BF11/2/2022ND
63
Girls Locker Room Faucet Left21970400-068BF11/2/2022ND
64
Girls Locker Room Faucet Right21970400-069BF11/2/2022ND
65
Ice Machine Gym21970400-072IM11/2/2022ND
66
67
68
69
70
Any fixture testing at or above the action level of 15 ppb is immediately removed from service
and cannot be returned to service until it has been remediated and passed follow-up testing
71
RETESTS
72
73
74
75
76
77
ND = Non Detect - Lead level is below the set detection limits
of 1 ppb
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100