TOUCH VOLTAGE & GROUND CURRENT CALCULATIONJignesh.Parmar jiguparmar@yahoo.com www.electricalnotes.wordpress.com
3
4
5
:Three Phase System::Single Phase System:
6
7
Line-to-Neutral Volts (Vn)230VoltsCircuit Voltage230Volts
8
Line 1 Calculated Load (A1)50AmpCircuit Ampere16Amp
9
Line 2 Calculated Load (A2)60AmpLoad Resistance14.38
10
Line 3 Calculated Load (A3)60Amp
11
Service Neutral Impedance Z10.1Ground Resistance1
12
Ground Resistance (3-point method) R100Electrode Resistance25
13
Body Resistance1000
14
15
RESULTSRESULTS
16
Neutral/Ground Parallel Resistance 0.10Total Resistance38.77
17
Line 1 Resistance4.600Total Current5.93Amp
18
Line 2 Resistance3.83Load Voltage Drop85.29Volts
19
Line 3 Resistance3.83
22
23
Line 1 - Actual Load49.58Amp
24
Line 1 Watts11307.72WattsGround/Body Voltage Drop144.71Volts
25
Line 1 - Loads Operates at Volts228.07VoltsBody Resistance1000.00
26
Body Current 144.71mA
27
Line 2 - Actual Load59.74AmpCircuit Current14.96Amp
28
Line 2 Watts13678.53Watts
29
Line 2 - Loads Operates at Volts228.99Volts
30
31
Line 3 - Actual Load59.74Amp
32
Line 3 Watts13678.53Watts
33
Line 3 - Loads Operates at Volts228.99Volts
34
35
Parallel Neutral/Ground Path69.89Amp
36
Neutral Watts487.98Watt
37
Neutral Current69.82Amp
38
Ground Current0.07Amp
39
Touch Voltage from Metal Parts to Earth6.98Volts
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102