ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
2
Parameter for rough computation of instantaneous heat transfer -- M:1.092
3
One version of heat transfer is calculated as M * (TS - TR) * FCFM ) -- the difference between supply and return temperatures multiplied by the airflow multiplied by the constant M.
4
The constant M combines factors for the density and specific heat of moist air and scales to an hourly rate for each minute (must divide by 60 after averaging rates)
5
6
See this post for explanation.
7
8
Period start11/7/2023 0:00:00
9
Period end3/14/2024 23:59:00
10
11
12
13
Downstairs input assumptions
14
Baseline flow estimate for downstairs unit (CFM)575
15
Fan watts at baseline94
16
17
Downstairs Results
18
Total minutes in time range185700
19
Minutes compressor active (see note 2) -- include these minutes in COP if have temps198450
20
% of time active11%
21
Average hours per 24 hours2.6
22
System active power use -- compressor (kwh)749
23
System active power use -- fan (kwh)28
24
Compressor standby power use (kwh)128
25
Fan standby power use1.1
26
Total minutes for which have both supply and return temperature185700
27
Active minutes for which have both supply and return temperature19845
28
Max temp split56.7
29
Average temp split while active33.0
30
Total BTU produced (active and have temp), using M factor above6773461.9
31
Total BTU heat converted to KWH1985.2
32
Corr. system power -- only while temp avail all compressor plus fan while active905.7
33
COP over season reported (including compressor standby but not fan standby)2.2
34
COP over season reported (excluding all standby)2.55
35
36
37
38
39
Memo: Total heat produced estimate
40
Total compressor kwh while active749
41
Total therms heat produced 65
42
Check val: Number of zero value compressor minutes6190
43
44
Notes for Columns on COP sheets
45
(1) Timebucket using Emporia power meter timeline (shifts to EST from EDST on November 5 at 2AM EDST)
46
(2) Standby compressor is <50 watts. Consider active when > x watts. 60
47
(3) Number of minutes where compressor > x but less than y where y = 200
48
This results in the following number of compressor exception minutes downstairs242
49
Many, but not all of these, are system transition minutes included by the rule.
50
(4) Checking that fan wattage never exceeds x watts when heating system is not active per (2)
51
Using sensitivity threshold of x in this test where x =2
52
This results in the following number of exception minutes downstairs83
53
Most of these occur on November 23, likely a maintenance day; some transitions
54
This column is invalid for the Upstairs COP sheet b/c fan also used for circulation
55
(9) Flow not computed using Fan law 3 from power -- closest fit for power is to square of CFM due to fan-to-air and motor inefficiency
56
(10) have both supply and return temperature measurment
57
(11) Is system active and have both supply and return temperature measurement
58
(12) In available active minutes, is supply +x > return where in degrees F x =0.5
59
Number of exception minutes, mostly apparent defrost cycles, fan watts low608
60
(13) BTU production at hourly rate computed using rough factor for heat transfer above
61
(14) BTU production using density and specific heat computed from ASHRAE library of properties
62
(18) Episode ID based on count of transitions to on state of compressor
63
64
Conversions
65
BTU to kwh -- 1/34120.0002930832356
66
So, pound force per newton4.448221909
67
Inches2 per meter 21550.0031
68
PSI/millibar0.01450377281
69
70
71
72
Notes on time consistency:
73
The power sheets use time from Emporia downloads which shows EDST until November 5 at 2AM, then falls back (line 24963) and repeats.
74
The power sheets return to EDST on March 10 at 2AM, dropping the 2AM hour (line 206462).
75
Total time period, Nov 7, 00:00 EST to March 14, 23:59 EDST. Predicted row checks:185701
76
For the TRH logging:
77
Govee is all EST
78
Hobo download from gateway is all EDST
79
Hobo data loggers transition back to EDST skipping an hour like Emporia
80
Shifted from Gateway use to direct download from loggers on December 25 (see log line # on TRH sheets)
81
Missing Temp data is BLANK -- after interpolation, only gap is supply temp upstairs from 12/31 to 2/13129Days
82
Logan data is GMT with appropriate shifts for matching to Emporia rows, Row count checks.3098
83
(Note that have extra row to match values that round to the missing EST to EDST hour.)
84
85
86
87
88
89
90
91
92