1 | ||||||||||||||||||||||||||
2 | Parameter for rough computation of instantaneous heat transfer -- M: | 1.092 | ||||||||||||||||||||||||
3 | One version of heat transfer is calculated as M * (TS - TR) * FCFM ) -- the difference between supply and return temperatures multiplied by the airflow multiplied by the constant M. | |||||||||||||||||||||||||
4 | The constant M combines factors for the density and specific heat of moist air and scales to an hourly rate for each minute (must divide by 60 after averaging rates) | |||||||||||||||||||||||||
5 | ||||||||||||||||||||||||||
6 | See this post for explanation. | |||||||||||||||||||||||||
7 | ||||||||||||||||||||||||||
8 | Period start | 11/7/2023 0:00:00 | ||||||||||||||||||||||||
9 | Period end | 3/14/2024 23:59:00 | ||||||||||||||||||||||||
10 | ||||||||||||||||||||||||||
11 | ||||||||||||||||||||||||||
12 | ||||||||||||||||||||||||||
13 | Downstairs input assumptions | |||||||||||||||||||||||||
14 | Baseline flow estimate for downstairs unit (CFM) | 575 | ||||||||||||||||||||||||
15 | Fan watts at baseline | 94 | ||||||||||||||||||||||||
16 | ||||||||||||||||||||||||||
17 | Downstairs Results | |||||||||||||||||||||||||
18 | Total minutes in time range | 185700 | ||||||||||||||||||||||||
19 | Minutes compressor active (see note 2) -- include these minutes in COP if have temps | 19845 | 0 | |||||||||||||||||||||||
20 | % of time active | 11% | ||||||||||||||||||||||||
21 | Average hours per 24 hours | 2.6 | ||||||||||||||||||||||||
22 | System active power use -- compressor (kwh) | 749 | ||||||||||||||||||||||||
23 | System active power use -- fan (kwh) | 28 | ||||||||||||||||||||||||
24 | Compressor standby power use (kwh) | 128 | ||||||||||||||||||||||||
25 | Fan standby power use | 1.1 | ||||||||||||||||||||||||
26 | Total minutes for which have both supply and return temperature | 185700 | ||||||||||||||||||||||||
27 | Active minutes for which have both supply and return temperature | 19845 | ||||||||||||||||||||||||
28 | Max temp split | 56.7 | ||||||||||||||||||||||||
29 | Average temp split while active | 33.0 | ||||||||||||||||||||||||
30 | Total BTU produced (active and have temp), using M factor above | 6773461.9 | ||||||||||||||||||||||||
31 | Total BTU heat converted to KWH | 1985.2 | ||||||||||||||||||||||||
32 | Corr. system power -- only while temp avail all compressor plus fan while active | 905.7 | ||||||||||||||||||||||||
33 | COP over season reported (including compressor standby but not fan standby) | 2.2 | ||||||||||||||||||||||||
34 | COP over season reported (excluding all standby) | 2.55 | ||||||||||||||||||||||||
35 | ||||||||||||||||||||||||||
36 | ||||||||||||||||||||||||||
37 | ||||||||||||||||||||||||||
38 | ||||||||||||||||||||||||||
39 | Memo: Total heat produced estimate | |||||||||||||||||||||||||
40 | Total compressor kwh while active | 749 | ||||||||||||||||||||||||
41 | Total therms heat produced | 65 | ||||||||||||||||||||||||
42 | Check val: Number of zero value compressor minutes | 6190 | ||||||||||||||||||||||||
43 | ||||||||||||||||||||||||||
44 | Notes for Columns on COP sheets | |||||||||||||||||||||||||
45 | (1) Timebucket using Emporia power meter timeline (shifts to EST from EDST on November 5 at 2AM EDST) | |||||||||||||||||||||||||
46 | (2) Standby compressor is <50 watts. Consider active when > x watts. | 60 | ||||||||||||||||||||||||
47 | (3) Number of minutes where compressor > x but less than y where y = | 200 | ||||||||||||||||||||||||
48 | This results in the following number of compressor exception minutes downstairs | 242 | ||||||||||||||||||||||||
49 | Many, but not all of these, are system transition minutes included by the rule. | |||||||||||||||||||||||||
50 | (4) Checking that fan wattage never exceeds x watts when heating system is not active per (2) | |||||||||||||||||||||||||
51 | Using sensitivity threshold of x in this test where x = | 2 | ||||||||||||||||||||||||
52 | This results in the following number of exception minutes downstairs | 83 | ||||||||||||||||||||||||
53 | Most of these occur on November 23, likely a maintenance day; some transitions | |||||||||||||||||||||||||
54 | This column is invalid for the Upstairs COP sheet b/c fan also used for circulation | |||||||||||||||||||||||||
55 | (9) Flow not computed using Fan law 3 from power -- closest fit for power is to square of CFM due to fan-to-air and motor inefficiency | |||||||||||||||||||||||||
56 | (10) have both supply and return temperature measurment | |||||||||||||||||||||||||
57 | (11) Is system active and have both supply and return temperature measurement | |||||||||||||||||||||||||
58 | (12) In available active minutes, is supply +x > return where in degrees F x = | 0.5 | ||||||||||||||||||||||||
59 | Number of exception minutes, mostly apparent defrost cycles, fan watts low | 608 | ||||||||||||||||||||||||
60 | (13) BTU production at hourly rate computed using rough factor for heat transfer above | |||||||||||||||||||||||||
61 | (14) BTU production using density and specific heat computed from ASHRAE library of properties | |||||||||||||||||||||||||
62 | (18) Episode ID based on count of transitions to on state of compressor | |||||||||||||||||||||||||
63 | ||||||||||||||||||||||||||
64 | Conversions | |||||||||||||||||||||||||
65 | BTU to kwh -- 1/3412 | 0.0002930832356 | ||||||||||||||||||||||||
66 | So, pound force per newton | 4.448221909 | ||||||||||||||||||||||||
67 | Inches2 per meter 2 | 1550.0031 | ||||||||||||||||||||||||
68 | PSI/millibar | 0.01450377281 | ||||||||||||||||||||||||
69 | ||||||||||||||||||||||||||
70 | ||||||||||||||||||||||||||
71 | ||||||||||||||||||||||||||
72 | Notes on time consistency: | |||||||||||||||||||||||||
73 | The power sheets use time from Emporia downloads which shows EDST until November 5 at 2AM, then falls back (line 24963) and repeats. | |||||||||||||||||||||||||
74 | The power sheets return to EDST on March 10 at 2AM, dropping the 2AM hour (line 206462). | |||||||||||||||||||||||||
75 | Total time period, Nov 7, 00:00 EST to March 14, 23:59 EDST. Predicted row checks: | 185701 | ||||||||||||||||||||||||
76 | For the TRH logging: | |||||||||||||||||||||||||
77 | Govee is all EST | |||||||||||||||||||||||||
78 | Hobo download from gateway is all EDST | |||||||||||||||||||||||||
79 | Hobo data loggers transition back to EDST skipping an hour like Emporia | |||||||||||||||||||||||||
80 | Shifted from Gateway use to direct download from loggers on December 25 (see log line # on TRH sheets) | |||||||||||||||||||||||||
81 | Missing Temp data is BLANK -- after interpolation, only gap is supply temp upstairs from 12/31 to 2/13 | 129 | Days | |||||||||||||||||||||||
82 | Logan data is GMT with appropriate shifts for matching to Emporia rows, Row count checks. | 3098 | ||||||||||||||||||||||||
83 | (Note that have extra row to match values that round to the missing EST to EDST hour.) | |||||||||||||||||||||||||
84 | ||||||||||||||||||||||||||
85 | ||||||||||||||||||||||||||
86 | ||||||||||||||||||||||||||
87 | ||||||||||||||||||||||||||
88 | ||||||||||||||||||||||||||
89 | ||||||||||||||||||||||||||
90 | ||||||||||||||||||||||||||
91 | ||||||||||||||||||||||||||
92 | ||||||||||||||||||||||||||
93 | ||||||||||||||||||||||||||
94 | ||||||||||||||||||||||||||
95 | ||||||||||||||||||||||||||
96 | ||||||||||||||||||||||||||
97 | ||||||||||||||||||||||||||
98 | ||||||||||||||||||||||||||
99 | ||||||||||||||||||||||||||
100 |