ABCDEFGHIJKLMNOPQRSTUVWXYZAA
1
2
Property :
3
MENARA KOMPASInspeksi Bulanan
NO. WO :
NA
4
PENGOPERASIAN POMPA PEMADAM KEBAKARAN
Tanggal :
07/04/2025
5
6
PROSEDUR UJI COBA
7
8
Agenda pengoperasian
Inspeksi Bulanan
9
Nama PetugasBayu
10
11
Pengujian Electric Pump
12
Lakukan switch off power untuk Jockey Pump
YA
13
Lakukan switch off power untuk Diesel Fire Pump
YA
14
15
Pengujian Diesel Fire Pump
16
Lakukan switch off power untuk Jockey Pump
YA
17
Lakukan switch off power untuk Electric Main Pump
YA
18
19
Data Standard Operasi Pompa :
20
POMPAPressure ONPressure OFFR
Amp
S
Amp
T
Amp
21
Jockey Pump16Kg/Cm217Kg/Cm2212121
22
Electric Main Pump14Kg/Cm2OFF-Man402402402
23
Diesel Fire Pump13Kg/Cm2OFF-Man
24
25
Data Pompa selama beroperasi
26
POMPAStarting SystemPressure ONPressure OFFR
Amp
S
Amp
T
Amp
27
Jockey PumpAuto16Kg/Cm217Kg/Cm29109
28
Electric Main PumpAuto14Kg/Cm2OFF-Man395390385
29
Diesel Fire PumpTidak di Test13Kg/Cm2OFF-Man
30
31
Cara Pengoperasian
32
Jockey PumpBypass Valve
33
Electric Main PumpBypass Valve
34
Diesel Fire PumpBuka Valve Hydrant Box
35
Speed Diesel Fire Pump
Hight Idle
36
37
Jam mulai14:00
Jam Selesai
15:00
38
39
Safety Valve saat Tekanan maksimum
Bekerja
40
Status Jockey Pump setelah Pengoperasian
Auto
41
Status Electric Main Pump setelah Pengoperasian
Auto
42
Status Diesel Fire Pump setelah Pengoperasian
Auto
43
CATATAN PENTING :
44
Diesel pump off dalam perbaikan (nozle pump bermasalah)
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100