GENERATOR ROOM VENTILATION CALCULATION
2
3
Diesel Generator capacity =
750KVA
4
5
Ventilating air (cu.m/min.) = H +Engine Combustion Air
6
Dx SHxDt
7
8
9
Where :-
10
H =
Total Heat Radiation in (KW) (for engine + generator)
11
H =125.5KW
(Ref. To specs. Sheet)
12
V =
Ventilating air (cu.m/min.)
13
D =
Density of air (kg/m3)
14
=1.07
At 54 deg. C
15
SH =
Specific heat of air ( kw.min/Kg.C)
16
=0.017
17
d T =
Temp. Rise inside engine room ( deg.C)
18
=10deg.C
19
ECA =
Engine Combustion Air (Exhaust gas flow )
20
=120
cu.m/min
(Ref. To specs. Sheet)
21
7,182
cu.m/hr.
22
23
Radiator fan air flow =
17.6cu.m/sec.
(Ref. To specs. Sheet)
24
=1056cu.m/min
25
= 37,256
cu.ft/min.
26
27
28
THEN :-
29
30
Ventilating air ( V ) =125.5 +120
31
1.07x0.017x10
32
33
34
V =810
cu.m/min
35
36
V = 28,564
cu.ft/min.
37
38
39
INTAKE LOUVER SIZE
40
41
-
Consider Air Velocity =
1000
ft/min.
42
Total Air Quantity =
28,564
cu.ft/min.
43
Louver Area =
29
Sq.ft
44
2.7
Sq.m
45
46
Important Notes :-
47
1-clean , cool , dry air circulates around the switchgear , flows through the rear of the generator , across the engine , and discharges through the radiator
48
49
2-
Cool air shoul always be available for the engine air cleaner (air filter ).
50
3-For best ventilation results , air should flow first across the generator then to both sides of the engine .
51
52
4-Inlets located at the end of the room will provide adequate ventilation only to the engine nearast the inlet.
53
54
5-
Air flow restriction should be 0.5 inch W.G