Earthing Design.
3
Assume Fault MVA at 11 KV side of the transformer is 150 MVAUnit
4
Duration of fault (t) in sec3sec
5
Soil Resistivity (q)53ohm.mtr
6
Power of Transformer 150MVA
7
High Voltage11KV
8
Fault Current7873A
9
Permissible Current density of an electrode (Id)600.34A/m^2
10
Total Area of Earth Electrode (Fault current/Id)13.1145m^2
11
Area of standard Earth Electrode for both side1.2mx1.2x12 mm
12
Area of Earth Plate2.88m^2
13
Number of Earth Plate Required4.553662939Nos