Cable Size & Voltage Drop Calculation1
3
4
Input Data SheetCalculationResultsFALSE
5
6
7
Electrical Load9.25KwTotal Electrical Load9.25KW(1) No of Parallel Run of Cable:Not Proper0
8
Motor Load0.00KwTotal Electrical Load in KVA11.56KVA(2) Cable Short Circuit Capacity:Not Applicable10.86
9
Total Load9.25KwTotal Full Load Curent50.27Amp(3) Cable Voltage Drop:High0
10
Type of Supply SystemSingle PhaseElectrical Load Starting Current50.27Amp(4) Selection of Cable Type:Not Proper0
11
System Voltage V(L-N)230.00VoltElectrical Motor Starting Current0.00Amp(5) Motor Starting Voltage DropHigh0
12
System Voltage V(L-N)230VoltTotal Starting Current50.27Amp1
13
Demand Factor1.00Starting CosØ 0.75:Required Action for Proper Cable Selection:
14
Power Factor0.80Starting SinØ 0.66=>Increase No of Run of Cable or Select Higher Capacity of Cable
15
Short circuit Current(If You Know)K.AmpRuning CosØ0.80
16
Allowable voltage drop at Running5%Runing SinØ0.60=>Select Higher Size of Cable to reduce Voltage Drop
17
Allowable voltage drop at Starting10%Cable Derating Factor:
18
Motor Lock Rotor Current (If You Know):AmpCable Installation MediaGround=>Select Other Type of Motor Starter
19
Motor Lock Rotor Current:2.00
X Full Load Current
Ground Temp. Correction Factor (K1)0.89=>Increase No's of Run of Cable to reduce Voltage Drop
20
Motor Starting Power Factor:0.75Group Factor for Ground (K4)1.00
21
Cable Detail:Cable Laying Depth Factor (K3)0.96Cable Selection is Not ProperFALSE
22
Type of Cable:LT PVC (Up to 1.1 KV)Soil Correction Factor for Air (K2)1.05
23
Cable Conductor:CUTotal Derating Factor0.90
24
Size of Cable:4cX 6 Cable Calculation
25
No of Parallel Run of Cable1No'sConductor Resistance. 2.19Ohm / km
26
Cable Length (Distance)200MeterConductor Reactance0.1Mho/km Motor Starter is not Proper2
27
Cable Laying Method:Cable Current Capacity 55 Amp
28
Cable Installation MediaGround2Derating Current49Amp
29
Ground Temperature (K2)35°CMin.Required No of Runs of Cable1.02Nos
30
Type
Cable Laying ArrangementTrefoilVoltage Drop Calculation:
31
Distance Between each Cable0.25 mtReceving end Voltage194Volt
32
No's of Cable in Trench1Allowable voltage drop at Running11.5Volt
33
1Allowable voltage drop at Starting23Volt
34
Cable Laying on The Depth of1.5MeterS.C Capacity of Selected Cable 0.858 K.Amp
35
Soil Thermal ResistiivtyNot KnownKm/WattVoltage Drop at Starting15.8%
36
Nature of Soil (k3)Damp SoilVoltage Drop at Running15.8%
37
38
N.B: Enter Your Data in White Background Cell
39
Formula For % Voltage Drop:=
40
(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line VoltageXNo of RunX1000
41
42
43
44
45
46
47
48
49
50
51
52
53
54
Single Phase
55
Three Phase
56
Air
57
Ground
58
Single Tire Horizontal
59
Multi Tire Horizontal
60
Trefoil
61
Air
62
Ground
63
Duct
64
65
66
67
68
PVC Flexible (Up to 1.1 KV)Single Phase
69
LT PVC (Up to 1.1 KV)Three Phase
70
LT XLPE (Up to 1.1 KV)
71
HT XLPE ( 6.6 KV-Earthed)
72
HT XLPE ( 11 KV-Earthed)
73
HT XLPE ( 11 KV-Un Earthed)
74
HT XLPE ( 66 KV-Earthed)
75
76
Air Temperature (K1)0.98
77
Group Correction Factor for Air (K2)
1.00
78
79
1
80
Ground Temp. Correction Factor (K1)
0.89
81
Soil Correction Factor for Air (K2)
1.05
82
Cable Laying Depth Factor (K3)0.96
83
Group Factor for Ground (K4)1.00
84
85
1.00