Cable Size & Voltage Drop Calculation1
3
4
Input Data SheetCalculationResultsFALSE
5
6
7
Electrical Load9.25KwTotal Electrical Load9.25KW(1) No of Parallel Run of Cable:OK1
8
Motor Load0.00KwTotal Electrical Load in KVA12.33KVA(2) Cable Short Circuit Capacity:Not Applicable10.86
9
Total Load9.25KwTotal Full Load Curent17.16Amp(3) Cable Voltage Drop:Within Limit1
10
Type of Supply SystemThree PhaseElectrical Load Starting Current17.16Amp(4) Selection of Cable Type:OK1
11
System Voltage V(L-L)415.00VoltElectrical Motor Starting Current0.00Amp(5) Motor Starting Voltage DropWithin Limit1
12
System Voltage V(L-N)240VoltTotal Starting Current17.16Amp1
13
Demand Factor1.00Starting CosØ 0.75
14
Power Factor0.75Starting SinØ 0.66
15
Short circuit Current(If You Know)K.AmpRuning CosØ0.75
16
Allowable voltage drop at Running5%Runing SinØ0.66
17
Allowable voltage drop at Starting10%Cable Derating Factor:
18
Motor Lock Rotor Current (If You Know):AmpCable Installation MediaGround
19
Motor Lock Rotor Current:2.00
X Full Load Current
Ground Temp. Correction Factor (K1)0.89
20
Motor Starting Power Factor:0.75Group Factor for Ground (K4)1.00
21
Cable Detail:Cable Laying Depth Factor (K3)0.96Cable Selection is ProperTRUE
22
Type of Cable:LT XLPE (Up to 1.1 KV)Soil Correction Factor for Air (K2)1.05
23
Cable Conductor:CUTotal Derating Factor0.90
24
Size of Cable:4cX 6 Cable Calculation
25
No of Parallel Run of Cable1No'sConductor Resistance. 2.19Ohm / km
26
Cable Length (Distance)200MeterConductor Reactance0.1Mho/kmMotor starter is Proper1
27
Cable Laying Method:Cable Current Capacity 55 Amp
28
Cable Installation MediaGround2Derating Current49Amp
29
Ground Temperature (K2)35°CMin.Required No of Runs of Cable1.00Nos
30
Type
Cable Laying ArrangementTrefoilVoltage Drop Calculation:
31
Distance Between each Cable0.25 mtReceving end Voltage405Volt
32
No's of Cable in Trench1Allowable voltage drop at Running20.75Volt
33
1Allowable voltage drop at Starting41.5Volt
34
Cable Laying on The Depth of1.5MeterS.C Capacity of Selected Cable 0.858 K.Amp
35
Soil Thermal ResistiivtyNot KnownKm/WattVoltage Drop at Starting2.4%
36
Nature of Soil (k3)Damp SoilVoltage Drop at Running2.4%
37
38
N.B: Enter Your Data in White Background Cell
39
Formula For % Voltage Drop:=
40
(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line VoltageXNo of RunX1000
41
42
43
44
45
46
47
48
49
50
51
52
53
54
Single Phase
55
Three Phase
56
Air
57
Ground
58
Single Tire Horizontal
59
Multi Tire Horizontal
60
Trefoil
61
Air
62
Ground
63
Duct
64
65
66
67
68
PVC Flexible (Up to 1.1 KV)Single Phase
69
LT PVC (Up to 1.1 KV)Three Phase
70
LT XLPE (Up to 1.1 KV)
71
HT XLPE ( 6.6 KV-Earthed)
72
HT XLPE ( 11 KV-Earthed)
73
HT XLPE ( 11 KV-Un Earthed)
74
HT XLPE ( 66 KV-Earthed)
75
76
Air Temperature (K1)0.98
77
Group Correction Factor for Air (K2)
1.00
78
79
1
80
Ground Temp. Correction Factor (K1)
0.89
81
Soil Correction Factor for Air (K2)
1.05
82
Cable Laying Depth Factor (K3)0.96
83
Group Factor for Ground (K4)1.00
84
85
1.00