Calculation of Room Pressure for CLEANROOMS
2
3
Room Dimensions in feet
4
Length 13.5Feet
5
Width 17FeetInputs
6
Height9Feet
7
8
Room volume 2065.5cu. ft.
9
Assuming Atmospheric pressure, Patm = 101.325kPa
10
Air changes per hourACH40Inputs
11
Room pressure need to maintain55Pa0.055kPaInputs
12
13
Supply Air SA1377cfmInputs
if you have already calculated this
14
15
Total pressure 101.38kPa
16
17
Total additional room air volume requires: 2066.62117cu. ft.
18
19
Additional air volume requires pressurizing room up to required pressure (without leakage):1.121169504cu. ft.
20
21
With 5% leakage consider1.177227979cu. ft.
Additional air volume require.
22
23
If we require pressurizing the room within second: 1sec
24
Total additional air flow (PA) / Fresh Air intake70.63367876cfm
25
26
Total supply Air SA1447.63cfm
27
Total Return Air RA1377.00cfm
28
29
30
Created by Engr.Naqqash Sajid