ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
Data Pemakaian Listrik dan Kualitas Daya
2
PP. Chiller ( Panel Listrik Untuk Unit Chiller )
3
Bulan : September 2019
4
5
Nama Panel= PP - CHILLER
6
Tegangan= 400 Volt
7
Daya= 1,320 kVA
8
ACB= 2000 A / 50kA
9
10
NoItemHasilSatuanBaku Mutu
11
1Tegangan Rata-Rata396,81Volt360 - 420
12
2Arus Rata-rata99,54Amps
13
3Daya Nyata Rata-rata66,18kVA
14
4Tegangan Tertinggi405Volt360 - 420
15
5Tegangan Terendah382,40Volt360 - 420
16
6Daya Nyata Tertinggi74kVA
17
7Daya Nyata Terendah46kVA
18
8THD V Tertinggi5,90%5%
19
9THD I Tertinggi69,30%8%
20
10Power Faktor (PF) Rata-rata0,860,85
21
11Power Faktor (PF) Terendah0,800,85