Available Fault Current Calculation
7
by:John SokolikVer. 4.00
8
Utility Fault Current
0amperes kVA =300
9
E =0
10
I = kVA x 1000 = trans. FLA
trans. FLA =
0
11
0
12
13
Isca = trans. FLA x 100
= PF =90%
14
transformer Z
Z =3% %
15
Isca = ampere short-circuit current RMS symmetrical.
Isca =
3,000 amperes
16
17
Point to Point Method
18
Length (distance)
L =150
19
'f ' factor = 2 x L x I (ASC) Isca =3,000
20
N x C x E L-N
# conductors per phase
N =1
21
Phase conductor constant C =0Phase Conductor
22
Volt Line to Line E L - L =0Volt
23
f =0.000
24
Neutral conductor constant C =0Neutral Conductor
25
MultiplierVolt Line to Neutral E L - N =0Volt
26
f =0.000
27
M = 1
28
1 + fLine to Line M =1.000
29
Line to Neutral
M =1.000
30
Fault Current at Service Equipment
31
32
Isca x M = fault current at terminals of main disconnect L- L =
3,000 amperes
33
Isca x M = fault current at terminals of main disconnect L- N =
0 amperes
34
35
36
37
Fault Current from
Service disc. to panel "_____"
38
39
Single Phase Feeder
Length (distance)
L =
40
'f ' factor = 2 x L x I (ASC) Isca =3,000 Phase 0 Neutral
41
N x C x E L-N
# conductors per phase
N =
42
Phase conductor constant C =0
Phase Conductor
43
Volt Line to Line
E L - L =0Volt
44
f =0.000
45
Neutral conductor constant C =0
Neutral Conductor
46
Volt Line to Neutral
E L - N =0Volt
47
Multiplier f =0.000
48
49
M = 1 Line to Line M =1.000
50
1 + f
Line to Neutral
M =1.000
51
52
Isca x M = fault current at terminals of the panel L- L =3,000 amperes
53
Isca x M = fault current at terminals of the panel L- N =0 amperes
54
55
Calculation does not include motor contribution
56
57
58
59
60
Branch Circuit Fault from
Point to Point
61
62
Error Single Phase Feeder
Length (distance)
L =
63
'f ' factor = 2 x L x I (ASC) Isca =3,000 Phase 0 Neutral
64
N x C x E L-N
# conductors per phase
N =
65
Phase conductor constant C =0
Phase Conductor
66
Volt Line to Line
E L - L =0Volt
67
f =0.000
68
Neutral conductor constant C =0
Neutral Conductor
69
Volt Line to Neutral
E L - N =0Volt
70
Multiplier f =0.000
71
72
M = 1 Line to Line M =1.000
73
1 + f
Line to Neutral
M =1.000
74
75
Isca x M = fault current at terminals of the panel L- L =3,000 amperes
76
Isca x M = fault current at terminals of the panel L- N =0 amperes
77
78
Calculation does not include motor contribution
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100