Calculate Size of Inveter / UPS with Battery BankJignesh.Parmar , www.electricalnotes.wordpress.com
3
4
Electrical Load Details
5
Sr.NoEquiment Name NoWattP.FType of LoadTotal (Watt)Total (VA)Starting (VA)Inverter / UPS Details
6
18890.9Resistive Loads889987.77777781975.555556Total Load987.7777778VA
7
Inductive Loads000Total Starting Load1975.555556VA
8
Capacitive Loads000Inverter efficiency92%
9
Resistive loads000Size of Invertor / UPS2.15KVA
10
000Inverter / UPS Battery Details:stringamp.hrNoTotalCFCorrection
11
000Battery Voltage24Volts DC0Series6015226.7201.59
12
000Inverter / UPS Back Up Time1Hour0Parallel300552101.1301.4
13
000Loose Connection/Wire Loss Factor:20%1Series-Parallel300552104401.3
14
000Battery Efficiency90%Select other Type of Connecion10501.19
15
000Battery Aging:20%Select other Type of Connecion15.6601.11
16
000Depth of Discharge:(DOD)50%O.K3005521021.2701.04
17
000Battery Operating Temp:4626.7801
18
000Current drain from battery 89.5AmpC°1
19
000Normal storage capacity of Battery89.5Amp.HrF°1.3
20
000Average Load143.2Amp.Hr1.00
21
000Size of Battery286.3Amp.Hr
22
000:Battery Bank Connection Detail :
23
000If You are Select Battery Volt12Volts DC0
24
000If You are Select Battery Size60Amp.Hr
25
000Batteries connection for Battery BankSeries-Parallel
26
000Selection of Batteries Connection:O.K
27
000Selection of Each Battery VoltageO.K
28
000Number of String for Battry Bank5Nos
29
000Total Amp.Hr of Each String60Amp.Hr
30
000Total No of Battery in Each String2Nos
31
000Total Battery Bank Amp.Hr300Amp.Hr
32
000Total Nos of Batteries in Battery Bank 10Nos
33
000
34
000Results:
35
000Size of Invertor / UPS2.15KVA
36
000Size of Battery286Amp.Hr
37
000Inverter / UPS Back Up Time1Hour
38
000
39
889987.77777781975.555556
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100