NEC Standard Electrical Load Calculation for Single Family Dwellings
3
4
5
Owner:Location:
6
7
8
Total Floor Area of Dwelling (NEC 220.12)
SQFT
9
10
11
FactorQuantityVolt Amperes (VA)
12
"General Lighting"
13
1. General Lighting (SQFT x 3 VA/SQ FT (Table 220.12)3 Xsq. ft.0
14
2. Small Appliance Circuits (1500 VA per circuit) NEC 220.52(A)) (Minimum 2)1500x 23000
15
3. Laundry Circuit (1500 VA per circuit) (NEC 220.52(B))1500x 11500
16
4. Total General Lighting Load (Add lines 1, 2, & 3):4500
17
5. First 3000 VA @ 100%3000
18
6. Total General Lighting Load - 3000 =1500 @ 35%525
19
7. Net General Lighting Load (Per NEC 220.42) (Add lines 5 & 6)3525
20
21
* Fixed Appliances
22
Garbage Disposal
23
Microwave
24
Fridge
25
Dishwasher
26
Other (Not Installed)
27
Other (Not Installed)
28
Other (Not Installed)
29
Total0
30
8. 3 or less Appliances, Total Appliance VA; 4 or more Appliances, 75% of Total Appliance VA (NEC 220.53):0
31
32
* Other Loads (Including motors, EV charger(s), etc)
33
9. Electric Range (8000VA or nameplate)** (Not Installed)
34
10. HVAC or Space Heater
35
Dryer
36
Water Heater (3 units, demand factor 54,000W Demand Factor 90% 220.54)
37
Water Heater 2
38
Water Heater 3
39
Minisplit
40
Minisplit
41
16. 25% of largest motor (NEC 430.24)
42
43
Total Service Load Volt-Amperes (VA) (Add lines 7, 8 & 9 thru 16) =
3525
44
Total Service Load Volt-Amperes / 240-volts =
15Amperes
45
46
Minimum Service Rating
Amperes
47
48
** Nameplate rating must be used if larger
49
*** Service Rating Shall be greater than or equal to the Service Load
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100