Cable Size & Voltage Drop Calculationjignesh.parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com1
3
4
:Input Data Sheet::Calculation::Results:FALSE
5
6
7
Electrical Load4.00KwTotal Electrical Load4.00KW(1) No of Parallel Run of Cable:O.K1
8
Motor Load0.00KwTotal Electrical Load in KVA5.33KVA(2) Cable Short Circuit Capacity:Not Applicable10.86
9
Total Load4.00KwTotal Full Load Curent7.42Amp(3) Cable Voltage Drop:Within Limit1
10
Type of Supply SystemThree PhaseElectrical Load Starting Current7.42Amp(4) Selection of Cable Type:O.K1
11
System Voltage V(L-L)415.00VoltElectrical Motor Starting Current0.00Amp(5) Motor Starting Voltage DropWithin Limit1
12
System Voltage V(L-N)240VoltTotal Starting Current7.42Amp1
13
Demand Factor1.00Starting CosØ 0.75
14
Power Factor0.75Starting SinØ 0.66
15
Short circuit Current(If You Know)K.AmpRuning CosØ0.75
16
Allowable voltage drop at Running5%Runing SinØ0.66
17
Allowable voltage drop at Starting10%Cable Derating Factor:
18
Motor Lock Rotor Current (If You Know):AmpCable Installation MediaGround
19
Motor Lock Rotor Current:2.00
X Full Load Current
Ground Temp. Correction Factor (K1)0.89
20
Motor Starting Power Factor:0.75Group Factor for Ground (K4)1.00
21
Cable Detail:Cable Laying Depth Factor (K3)0.96Cable Selection is ProperTRUE
22
Type of Cable:LT XLPE (Up to 1.1 KV)Soil Correction Factor for Air (K2)1.05
23
Cable Conductor:CUTotal Derating Factor0.90
24
Size of Cable:4cX 6 Cable Calculation
25
No of Parallel Run of Cable1No'sConductor Resistance. 2.19Ohm / km
26
Cable Length (Distance)200MeterConductor Reactance0.1Mho/kmMotor starter is Proper1
27
Cable Laying Method:Cable Current Capacity 55 Amp
28
Cable Installation MediaGround2Derating Current49Amp
29
Ground Temperature (K2)35°CMin.Required No of Runs of Cable1.00Nos
30
Type
Cable Laying ArrangementTrefoilVoltage Drop Calculation:
31
Distance Between each Cable0.25 mtReceving end Voltage411Volt
32
No's of Cable in Trench1Allowable voltage drop at Running20.75Volt
33
1Allowable voltage drop at Starting41.5Volt
34
Cable Laying on The Depth of1.5MeterS.C Capacity of Selected Cable 0.858 K.Amp
35
Soil Thermal ResistiivtyNot KnownKm/WattVoltage Drop at Starting1.1%
36
Nature of Soil (k3)Damp SoilVoltage Drop at Running1.1%
37
38
N.B: Enter Your Data in White Background Cell
39
Formula For % Voltage Drop:=
40
(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line VoltageXNo of RunX1000
41
42
43
44
45
46
47
48
49
50
51
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212