Steel Stair Design Based on AISC-ASD 9th
6
7
INPUT DATA & DESIGN SUMMARY
8
COLUMN SECTION (Tube or Pipe)
= >
HSS4X4X1/4
9
TubeArminth
10
3.371.520.234.00
11
FLOOR BEAM - 1= >W16X26
12
A dIxSx
13
7.6815.70301.0038.40
14
STRINGER - 1 (Channel or Tube)
= >MC8X8.5
15
ChannelA dIxSx
16
2.508.0023.305.82
17
STRINGER - 2 (Channel or Tube)
= >
C12X20.7
18
ChannelA dIxSx
19
6.0812.00129.0021.50
20
LANDING BEAM - 1 (Channel or Tube)
= >
C8X18.75
21
ChannelA dIxSx
22
5.518.0043.9011.00
23
LANDING BEAM - 2 (Channel or Tube)
= >
C8X18.75
24
ChannelA dIxSx
25
5.518.0043.9011.00
26
27
DIMENSIONSH =16
ft, story Ht
28
L1 =12ft
29
L2 =6ft
30
L3 =10ft
31
32
NUMBER OF STORIES
n =2
33
34
GRAVITY LOADDL =50psf
35
LL =100psf
36
37
38
THE STAIR DESIGN IS ADEQUATE.
39
40
41
ANALYSIS
42
43
STRINGER - 1
44
45
46
q =33.69
deg, from horizontal
47
w = 0.25 (DL / Cos q + LL) L3 =
400
plf , projected
48
R = 0.5 w L1 =
2.40kips
49
M = w L12 / 8 =
7.20ft-kips
50
fb = M / Sx =
14.85ksi
51
Fb = 0.6 Fy =
21.60ksi>fb
[Satisfactory]
52
E =29000ksi
53
12
DLL = 5 (wLL Cos q) (L1 / Cos q)4 / (384 E I) =
0.46in
54
6<
(L1 / Cos q) / 240 =
0.72in
[Satisfactory]
55
56
57
58
59
60
LANDING BEAM - 1
61
62
w = 0.5 (DL + LL) L2 =
450plf
63
P =2.40
kips, from STRINGER - 1
64
R = 0.5 w L3 + P =
4.65kips
65
M = w L32 / 8 + P L3 / 2 =
17.63ft-kips
66
fb = M / Sx =
19.23ksi
67
Fb = 0.6 Fy =
21.60ksi>fb
[Satisfactory]
68
DLL = 5 wLL L34 / (384 E I) + PLL L33 / (24 E I) =
0.14in
69
<L3 / 240 =0.50in
[Satisfactory]
70
71
72
(cont'd)
73
STRINGER - 2
74
75
76
w = 400
plf , projected, from STRINGER - 1
77
P = 4.65
kips, from LANDING BEAM - 1
78
RL = [w L1 (0.5 L1 + L2) + P L2] / (L1 + L2) =
4.75kips
79
RR = [w L1 (0.5 L1) + P L1] / (L1 + L2) =
4.70kips
80
X = RL / w =
11.87
ft, from left
81
Mmax = RL X - (0.5 w X2 ) =
28.21ft-kips
82
fb = Mmax / Sx =
15.75ksi
83
Fb = 0.6 Fy =
21.60ksi>fb
[Satisfactory]
84
DLL = 5 wLL (L1 + L2)4 / (384 E I) + PLL (L1 +L2)3 / (48 E I) =
0.24
85
<
(L1 + L2) / 240 =
0.90in
[Satisfactory]
86
87
88
LANDING BEAM - 2
89
90
w =450
plf, from LANDING BEAM - 1
91
R = 0.5 w L3 =
2.25kips
92
M = w L32 / 8 =
5.63ft-kips
93
fb = M / Sx =
6.14ksi
94
Fb = 0.6 Fy =
27.60ksi>fb
[Satisfactory]
95
DLL = 5 wLL L34 / (384 E I) =
0.05in
96
<L3 / 240 =0.50in
[Satisfactory]
97
98
FLOOR BEAM - 1
99
100
L =12ft