Transformer Losses Calculation (As per Transformer Test Results)
3
4
5
Transformer Specifications:Actual load on Transformer:
6
Output kVA800kVAActual Connected load520kVA
7
High voltage Volts6600VoltsActual loading of Transformer65%65%
8
Low voltage Volts400VoltsVoltage, VL427Volts
9
Full load current-secondary Amp1154AmpMeasured load current, IL1000Amp
10
Full load current primary Amp70AmpWinding temperature, T75°C
11
Efficiency %%Total Working Hours/Annum8760
12
Reference temperature °C75°CCO2 emission at Rate of 0.4Kg/Kwh
13
Frequency Hz50 Hz
14
No load test:Results (Actual Load Current):
15
R.M.S. Voltage, Vrms 429VoltsForm factor, k p.u1.13
16
Average voltage, Vavg 403VoltsCorrected no load losses 1919.47Watts
17
Frequency, f 50 HzTotal Core loss at actual voltage and freq.12650Watts
18
No load Current, Inl A9.96AmpTotal Copper loss estimated at test current 45Watts
19
No load power input, Pnl Watts1960WattsStray losses at test current 22Watts
20
Winding resistance of secondary (L.V.) side (Rph-2)0.00111ΩTotal Copper loss at full load current11101Watts
21
Winding resistance of primary (H.V.) side,(Rph-1)1.03ΩStray losses at full load current3893Watts
22
Ambient temperature 75°CTotal Copper loss at actual load current8336Watts
23
Total Stray losses at actual load current2923Watts
24
Short circuit test:Total No Load losses at actual load12650Watts
25
Applied reduced voltage on H.V, Vsc (Average of three currents measured)36.6VoltsTotal Load Load losses at actual load11259Watts
26
H.V. side phase current, ( Average of three currents measured) Is12.78AmpTotal Losses at actual load23909Watts
27
Power measured ( average of three power measured), Wsc-m44.3WattsEfficiency at actual load97.1%
28
Total power input at short circuit, Wsc66.45Watts
29
Results (Full Load Current):
30
Form factor, k p.u. 1.13
31
Corrected no load loss1919.471608WattsJignesh.Parmar
32
Total Core loss at rated voltage and freq. Watts2207.884214Wattsjiguparmar@yahoo.com
33
Total Copper loss estimated at test current 44.90028443Wattswww.electricalnotes.wordpress.com
34
Stray losses at test current 21.54971557Watts
35
Total Copper loss at full load current 11100.69437Watts
36
Total Stray losses at full load current 3893.23802Watts
37
Total losses at full load Watts 17201.8166Watts
38
Efficiency at full load 97.9%
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100