Recommendations List - Inspection
2
2024 - July
3
NoChecklistInspection ItemItemRecommendationRequired time period for completionRemarks
4
3
Jetty Control Room Inspection Checklist
4.3. Battery backupJetty severNo Battery BackupDone
5
8Loading Arm Inspection ChecklistStorm locking Device and Mechanical locking systemL-6107SLD-Plate missing, MLS-Nut missingNeed to supply by ENS
6
Mechanical locking systemL-6104MLS-Locking Nuts missingDone
7
Safety ladderSafety Ladder Little Corrosion.Done
8
1020 Area Pump Inspection Checklist3.3. No lube oil leakageP-2101AOil leakageDone
9
1220 Area Tank Inspection Checklist1.2. Spiral stairway/Access platformT-2103Little RustDone
10
1.3. Hand railing T-2102/T-2103RustDone
11
1.4. Roof/shell manholeT-2102/T-2103Rust
12
1.6. Cooling pipelineT-2102/T-2103Little Rust
13
1.10. Radar level gaugeT-2102Rust
14
1.16. Sampling deviceT-2102Sampling device is lockedDone
15
3.1. Fire arresters body and meshT-2102/T-2103Little RustDone
16
1530 Area Tank Inspection Checklis3.1. Fire arresters body and meshT-3104/T-3105/T-3106/T-3107/T-3108Little RustDone
17
17Tank Farm Electric Fire Pump Inspection Checklist4.2. Pump, paintingP-4002BNeed to apply top coatDone
18
4.4. Pump, discharge pressure gaugeP-4003A/P-4003B/P-4002B Not availableNeed to supply by ENS
19
5.1. Operation panel light indicatorP-4003A/P-4003BNot availableNot applicable
20
5.3. Operation panel ammeterP-4003A/P-4003BNot availableNot applicable
21
22Sewage Treatment Plant Inspection ChecklistBlowerR-4011BOil leakageDone
22
23Tank Farm Fresh Water System Inspection ChecklistValvesHV-40125Not availableNot applicable
23
24Forklift Inspection Checklist1. Status of operator cabin (Seat and other controller)FL-3 5-2Seat damageDone
24
15. HornNot working
25
20. Paint conditionNot good condition
26
2024 - August
27
NoChecklistInspection ItemItemRecommendationRequired time period for completionRemarks
28
12 20 Area Tank Inspection Checklist1.1.Appearance of tankT-2101/T-2102Tank top rustDone
29
1.2. Spiral stairway/Access platformT-2101/T-2102/T-2103RustDone
30
1.3. Hand railing T-2102/T-2103Little RustDone
31
1.4. Roof/shell manholeT-2101/T-2102/T-2103RustDone
32
1.6. Cooling pipelineT-2101/T-2102/T-2103Pipeline support and bolts rustDone
33
2.1. Open vent, Valve bodyT-2101/T-2102RustDone
34
2.3. Open vent, Connection flanges and boltsT-2101/T-2102/T-2103RustDone
35
3.1. Fire arresters Body and meshT-2101/T-2102/T-2103RustDone
36
4.1. Manhole cover,boltsT-2102/T-2103Bolts rustDone
37
15 30 Area Tank Inspection Checklist1.1.Appearance of tankT-3105Tank top rustDone
38
1.2. Spiral stairway/Access platformT-3102/T-3107/T-3108RustDone
39
1.3. Hand railing T-3107/T-3108Little RustDone
40
1.4. Roof/shell manholeT-3102/T-3104/T-3106/T-3107RustDone
41
1.8. Dip hatchT-3106/T-3107/T-3108RustDone
42
1.14. Foam connectionT-3106RustDone
43
2.1. Open vent, Valve bodyT-3105RustDone
44
2.3. Open vent, Connection flanges and boltsT-3107RustDone
45
4.1. Manhole cover,boltsT-3106/T-3107/T-3108RustDone
46
16Tank Frm Diesel Fire Pump Inspection Checklist4.4. Battery charger's condition (Charging voltage)P-4001A/P-4001BOne charger is not applicableDone
47
22Sewage Treatment Plant InspectionBlower R4011AUnder maintenanceDone
48
Blower R4011BOil leakageDone
49
23
Tank Farm Fresh Water System Inspection
HV-40125Not availableNot Available
50
2024 - September
51
NoChecklistInspection ItemItemRecommendationRequired time period for completionRemarks
52
1120 Control Room Inspection3.3 Available mouse and KeyboardTwo mouses are missingDone
53
1220 Area Tank Inspection 1.4 Roof/shell manhole2102/2103RustDone
54
1.6 Cooling pipeline2101/2102/2103Rust(Nut and Bolts)Done
55
1.7 Fire Line Filters2101/2102/2103Rust(Nut and Bolts)Done
56
2.3 Connection flanges and bolts2101/2103RustDone
57
4.1 Manhole-Cover,bolts2101/2103Rust(Nut and Bolts)Done
58
1.1 Appearance of tank2102/2101Tank top rustDone
59
1.4 Roof/shell manhole2102Rust(Support and bolt)Done
60
2.1 Valve Body2102RustDone
61
2.2 Ground wire connection2102RustDone
62
16Tank Farm Diesel Fire Pump Inspection Checklist4.4 Battery Charger conditionP.4001BOne charger is not working.Done
63
4.4 Battery Charger conditionP-4001AOne charger is not working.Done
64
1530 Area Tank Inspection Checklist4.1 Cover bolts/Spiral stairway/access paltform-Roof/Shell Manhole3105/3102/3103/3104/3105/3106/3107/3108Little RustDone
T3106,3107 & 3108 Completed. T3103 in progress
65
22Sewage Treatment Plant InspectionR 4011 BOil LeakDone
66
23
Tank Farm Fresh Water System Inspection
HV40125 is not availableN/A
67
2024 - October
68
NoChecklistInspection ItemItemRecommendationRequired time period for completionRemarks
69
1Jetty Diesel Fire Pump InspectionF-034.4- 24.8v/24.8vDone Indicated figures were OK
70
4.3 - 1.25/1.25/1.25/1.25Done Indicated figures were OK
71
F-014.3 - 1.28/1.27/1.27/1.26Done Indicated figures were OK
72
4.4 - 24.81v/24.80vDone Indicated figures were OK
73
2Jetty Generator Inspection400KVA4.4 - 13.32v/ 13.30vDone Indicated figures were OK
74
4.3- Battery water levels and specific gravity - Battery damage
Done Replaced
75
3Loading Arm Auxiliaries InspectionTT is not working. Need to replace.Done Jetty #2 Replaced.
76
430 Area Tank InspectionT-3107/T-3106/T-3102/T-3104/T-3105/T-3103/T-3101/T-31081.2 Spiral staiwayRustDone T3106,3107 & 3108 Completed.
77
1.3 Hand railingRustDone T3106,3107 & 3108 Completed.
78
1.4 Roof/Shell manholeRustDone T3106,3107 & 3108 Completed.
79
1.8 Dip hatchRustDone T3106,3107 & 3108 Completed.
80
2.1 Valve BodyRustDone T3106,3107 & 3108 Completed.
81
2.3 Connection flanges and bolts RustDone T3106,3107 & 3108 Completed.
82
4.1 Cover,boltsRustDone T3106,3107 & 3108 Completed.
83
16Tank Farm Diesel Fire Pump InspectionP-4001B4.3 - 1.26/1.26/1.27/1.25Done Indicated figures were OK
84
4.4 Battery chargers condition - One charger is not working
Need to supply by ENS
85
P-4001A4.3 - 1.26/1.25/1.27/1.27DoneIndicated figures were OK
86
4.4 Battery Chargers condition - One charger is not applicable.
Need to supply by ENS
87
19Tank Farm Generator Inspection1500KVA4.3 - 1.26/1.26/1.27/1.28DoneIndicated figures were OK
88
4.4 - 26.3doneIndicated figures were OK
89
22Sewage Treatment Plant InspectionR-4011A pump is under maintenance Done
90
R 4011B Pump - oil leakDone
91
HV-40125 is not availableDone
92
23
Tank Farm Fresh water System Inspection
30 area Pipeline has a small leak.Done
93
2024 - November
94
NoChecklistInspection ItemItemRecommendationRequired time period for completionRemarks
95
1Jetty Diesel Fire Pump Engine under maintenanceF-01ENS
96
2Jetty Fresh water PumpLWP-04Light indicatorsIndicator light is not workingDone
97
3Loading Arm AuxiliariesJetty No"02
Hydaulic station one pressure guage is not clear
Need to supply by ENS
98
420 Control RoomUPSUPS Is not availableNeed to supply by ENS
99
520 Area tank1.4-Roof shelf,Radar level guage,Foam connection,cover,boltsT-2103Little RustDone
100
630 Area Pump 3.3 No lube oil leakageP-3104Bsmall leakDone