EquipmentStandard Reference (IEC/ISO)Calibration MethodRangeToleranceFrequencyTraceability RefResponsibilityRemarks
2
HV DividerIEC 60060-2, ISO/IEC 17025Apply known HV, compare with reference divider0–1000 kV±0.5%YearlyNABL Accredited Std.Calibration EngineerRecord temp/humidity
3
CT/PTIEC 60044, ISO/IEC 17025Ratio & phase error test using reference standard0–400 kVAs per IECYearlyAccredited CT/PT Std.Test EngineerReport errors
4
Standard CapacitorIEC 60358Bridge comparison with reference capacitor1 nF – 10 µF±0.2%2 YearsNMI Ref.Lab EngineerMaintain humidity <50%
5
HV MeterIEC 61083Compare with reference meter under HV0–1000 kV±1%YearlyTraceable Std. MeterCalibration Eng.Store in dry place