requirements for sprinkler hangers
 Share
The version of the browser you are using is no longer supported. Please upgrade to a supported browser.Dismiss

 
View only
 
 
ABCDEFGHIJKLMNOPQRSTUVWX
1
VDSFMLPCUL 203EN 12845
2
3
Thickness (mm)cross sectionThickness (mm)corrosion protected/
stainless steel and non ferrous (mm)
Non corrosion protected ferrous other then stainless steel (mm)Thickness (mm)Pipe SupportsPipe Clips
4
DNmmmm(mm2)cross section (mm2)galvanized dimension (mm)ungalvanized dimension (mm)
5
Material for Pipe Supports3/8”1017.0corrosion protection
> 2,5
without corrosion protection
> 3,0
30corrosion
protection £ 3,18
without corrosion protection
> 3,18
20x1,220x3,0
corrosion protection £ 4,8
without corrosion protection > 4,83025x1,525x3,0
6
1/2”1521.33020x1,220x3,03025x1,525x3,0
7
3/4”2026.93020x1,220x3,03025x1,525x3,0
8
1”2533.73020x1,220x3,03025x1,525x3,0
9
1 1/4”3242.43020x1,220x3,03025x1,525x3,0
10
1 1/2”4048.33020x1,220x3,03025x1,525x3,0
11
2”5060.33020x1,220x3,03025x1,525x3,0
12
2 1/2”6576.173.025020x1,220x3,05025X2,525x3,0
13
3”8088.95025x1,225x3,05025X2,525x3,0
14
3 1/2"94101.65025x1,225x3,05025X2,525x3,0
15
4”100114.35025x1,225x3,05025X2,525x3,0
16
5”125139.7141.307032x1,632x3,07025X2,525x3,0
17
6”150168.3165.107032x1,632x3,07025X2,525x3,0
18
8”200219.112540x2,040x3,012525X2,525x3,0
19
10”250273.015050x2,050x3,0
20
12”300323.9180
21
22
Attachment3/8”1017.0M83/8" - M10M10 / hole 11 mm3/8" - M10M8
23
1/2”1521.3M83/8" - M10M10 / hole 11 mm3/8" - M10M8
24
3/4”2026.9M83/8" - M10M10 / hole 11 mm3/8" - M10M8
25
1”2533.7M83/8" - M10M10 / hole 11 mm3/8" - M10M8
26
1 1/4”3242.4M83/8" - M10M10 / hole 11 mm3/8" - M10M8
27
1 1/2”4048.3M83/8" - M10M10 / hole 11 mm3/8" - M10M8
28
2”5060.3M83/8" - M10M10 / hole 11 mm3/8" - M10M8
29
2 1/2”6576.173.02M103/8" - M10M10 / hole 11 mm3/8" - M10M10
30
3”8088.9M103/8" - M10M10 / hole 11 mm3/8" - M10M10
31
3 1/2"94101.6M103/8" - M10M10 / hole 11 mm3/8" - M10M10
32
4”100114.3M103/8" - M10M10 / hole 11 mm3/8" - M10M10
33
5”125139.7141.30M121/2" - M12M12 / hole 13 mm1/2" - M12M12
34
6”150168.3165.10M121/2" - M12M12 / hole 13 mm1/2" - M12M12
35
8”200219.1M161/2" - M12M16 / hole 18 mm1/2" - M12M16
36
10”250273.0M205/8" - M16M20 / hole 22 mm5/8" - M16
37
12”300323.95/8" - M165/8" - M16
38
39
DeflectionMax allowable deflection is 5 mm measured between pre-load and workloadMax allowable deflection is 4,76 mm between pre load and Test loadMax allowable deflection less than 5 mm between pre-measurement nominal load and proof loadnot applicable
40
60 sec2 min +30 sec - 0 sec60 sec
41
42
Upwards thrust1512 N without a displacement of more than 3,2 mm
43
44
Loads in Newton"DNmmmmpre-load (N)work load (N)break load (N)pre-load (N)test load (N)pre-load (N)proof load (N)required load (N)minimum load capacity (N)
45
steel pipeCPVC pipe
46
3/8”1017.02002000400015015002000
47
1/2”1521.320020004000150150015122000
48
3/4”2026.9200200040008915121501500333615122000
49
1”2533.72002000400013318241501500333615122000
50
1 1/4”3242.42002000400020019131501500333615122000
51
1 1/2”4048.32002000400024523131501500333615122000
52
2”5060.32002000400035628251501500333615122000
53
2 1/2”6576.173.023503500700053441812001650378117793500
54
3”8088.93503500700077847154003400467022243500
55
3 1/2"94101.6350350070008905583500520055603500
56
4”100114.335035007000111265615005200667233365000
57
5”125139.7141.305005000100001557889610001020088965000
58
6”150168.3165.10500500010000211311632100010200117875000
59
8”200219.1850850017000333616903100016250180148500
60
10”250273.01000100002000049822604410002500026020
61
12”300323.968083514135139
62
63
Material behaviour when heatedWhen the material is heated up to 200°C, the load bearing capacity should not deteriorate more than 25%When the material is heated up to 200°C, the load bearing capacity should not deteriorate more than 25%
64
65
Commentsto avoid contact corrosion copper pipes must be protected against direct contact with the hanger
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
Loading...
 
 
 