ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
4-side air blowing fan coil unit
2
model2 tube systemMFP-68FM-(Q)MFP-85FM-(Q)MFP-272FM-(Q)MFP-300FM-(Q)
3
power supply220V,50Hz,1Ph
4
air volumeHm3/h68085027203000
5
M52066020402300
6
L37043013601600
7
static pressurePa0000
8
cooling capacityTHHW380047001500017000
9
BTU/h11940147674713053414
10
SHW283035001117512665
11
BTU/h9660119423812943212
12
THMW308038001215013770
13
SHW24303000960010878
14
THLW24002960945010710
15
SHW1950243077498782
16
heating capacityHW570070502250025500
17
MW440054301730019600
18
LW345042601360015400
19
noiseH0PadB(A)41435354
20
power inputH0PaW5865180193
21
waterflow volumem3/h0.650.812.582.92
22
water pressure droppingkPa22285158
23
dimension of water(in & out)connection pipeinZG3/4"ZG3/4"ZG3/4"ZG3/4"
24
outZG3/4"ZG3/4"ZG3/4"ZG3/4"
25
coiltypehigh efficient copper pipe to wear Hydrophilic aluminum coil
26
dimension of water drain pipemm26262626
27
net dimensionunitL×W×H mm590*590*314944*944*316
28
net weightwholekg2041
29
30
Testing condition:
2-tube system
Cooling
Entering air temperature: Dry bulb 27ºC, Wet bulb 19.5ºC
Entering/out water temperature: 7ºC/ 12
Heating
Entering air temperature: 20ºC
Entering water temperature: 60ºC, Same water flow rate as for the cooling
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100