Voltage Drop Calculation
2
Example 2
3
Voltage drop of cable
4
VdSQRT(3)*Ib*L(RcosQ+X.SinQ))/(V*N)*100
5
The cable has its resistance and reactance causing some voltage drop. Motor takes 6 to 12 times the full load current during starting. The voltage drop criteria has to be checked in order to have sufficient voltage to develop load torque.
6
7
3.221284041
8
Number of Runs / Phase:1
9
Resistance of the conductor (95mm2):0.247ohm/km(As per Cable catalogue)
10
Reactance of the conductor (95mm2):0.0734ohm/km(As per Cable catalogue)
11
Voltage:415V
12
Ib 163.67A
13
L0.12KmtrResults
14
CosQ0.85
15
SinQ0.53
16
L=Length of cable (m)2.0379413
17
R=Cable resistance at 90°C – Ohm/km
18
X=Cable reactance at 50 Hz
19
I=Rated current (A)
20
n=No. of Parallel runs
21
cos ø=Power factor
22
Ist=Starting current
23
cos øst=Power factor at starting
24