TRANSFORMER STABILITY TEST
2
Short Circuit Calculations
3
Transformer Data
4
S =50MVA
5
VLow =13٫8kV
6
Z =21٫6%
7
VAP =380V
8
Vhigh =132kV
At Center step of tap changer
9
10
IR = S / (√3 * VLow)
11
12
ISC = IR / Z = S / (√3 * VLow * X)
13
14
IINJ = ISC * VAP / VLow = S * VAP / (√3 * VLow2 * Z)
15
16
IR Rated Current
17
SRated Power (ONAN)
18
VLow Rated Voltage of low voltage side (Injection Side)
19
ISC Short Circuit Current at Rated Voltage
20
Z Transformer Percentage Impedance
21
IINJ The Injected Current at The applied Voltage
22
VAP Voltage Applied (Test Voltage) at low voltage side
23
24
ILow =
266٫67A
25
IHigh =
27٫88A