1 | Erstellt von Thomas Klimach (Max-Planck-Institut für Chemie Mainz t.klimach@mpic.de) | ZUM Ändern als eine eigene Kopie (z.B. als Excel-Datei) speichern | ||||||||||||||||||||||||||||||||||||
2 | Klassenraum-Szenario | Kommentare/Referenz | ||||||||||||||||||||||||||||||||||||
3 | CO2 | Aerosol | ||||||||||||||||||||||||||||||||||||
4 | Atemvolumen | 9 | l/min | Müller et. al. 2020 | ||||||||||||||||||||||||||||||||||
5 | Personen | 25 | Müller et. al. 2020 | |||||||||||||||||||||||||||||||||||
6 | Emissions Konz. | 40000 | ppm | 0,0337746555 | #/l | Lelieveld et al. Ijerv2020 | ||||||||||||||||||||||||||||||||
7 | Raumgröße V | 200 | m³ | Müller et. al. 2020 | ||||||||||||||||||||||||||||||||||
8 | Anstieg E/V | 2700 | ppm/h | 2,279789246 | #/h | |||||||||||||||||||||||||||||||||
9 | Hintergrund czu | 410 | ppm | 0 | #/m³ | Müller et. al. 2020 | ||||||||||||||||||||||||||||||||
10 | Zerfallsrate λvp | 0 | /h | 0,6 | /h | van Doremalen et al. 2020 | ||||||||||||||||||||||||||||||||
11 | Leckrate λ0 | 0,3 | /h | Fitzner und Finke 2012 | ||||||||||||||||||||||||||||||||||
12 | CO2-Sensor obere grenze | 950 | ppm | |||||||||||||||||||||||||||||||||||
13 | CO2-Sensor untere grenze | 560 | ppm | |||||||||||||||||||||||||||||||||||
14 | Transmission Maske Emitter | 100,00% | ||||||||||||||||||||||||||||||||||||
15 | Transmission Maske Empfänger | 100,00% | ||||||||||||||||||||||||||||||||||||
16 | QuelluftEffekt Anreicherung | 50% | Rietschel und Fitzner 2008 / Klimach und Helleis 2021 | Welcherbalken | Welcher Balken | |||||||||||||||||||||||||||||||||
17 | Personen verlassen den Raum in der großer Pause nach jeder Doppelstunde (15min) | 1 | Kurzschluss | 5% | 25% | Für die große Pause und die Zusätzlichen Pausen aus Spalte I | Entweder fixe Anzahl oder -1 für Lüften nach CO2-Sensor (siehe Felder B12 und B13) | Welcher Balken ist Referenz? | 1 | 16 | 16 | |||||||||||||||||||||||||||
18 | Personen verlassen den Raum nach jeder Stunde (5min) | 0 | Qi,kont. (m³/h) | ηCO2 (%) | ηaero (%) | h (%) | ηquell (%) | λvent (1/h) | Nvent | 1,00 | Mischlüftung | 2,79 | 1775 | |||||||||||||||||||||||||
19 | Position in Plot | Bezeichnung | kont. Luftdurchsatz (Qi) m³/h | Frischluft Anteil bzgl. CO2 (ηCO2) | Frischluftanteil bzgl. Aerosol (ηaero) | Hauben Effekt (Anteil abgeführter Emissionen vor Mischen) | Quellluft Effekt (Erhöhung in Abluft gegenüber Mittelwert im Raum) | zusätzliche RLWR Stoßlüftens während großer und kleiner Pausen (0-kein Stoßlüften) (1/h) | kleine Pausen zum Lüften pro Doppel-Stunde (0-nur in großer Pause Stoßlüften) | kont. Lüftungseffizienz CO2 | kont. Lüftungseffizienz Aerosole | äqivalente RLWR Aerosol | Column in Simulation Sheet | Dosis | relative Dosis | Max CO2 | Verbesserungsfaktor | effek wechselrate co2 | medianCO2 | Anteil unter 1000 | Anteil unter 2000 | unter 800 | unter 1400 | Reduktion | Verb.F med CO2 | Pos. | Daten BalkenPlot | maxco2 | verbesserung | median | unter 800 | 800 bis 1000 | 1000 bis 1400 | 1400 bis 2000 | über 2000 | Reduktion | ||
20 | 6 | Stoßlüften UBA-Empfehlung | 0 | 100% | 100% | 0% | 0% | 30 | 3 | 1,0000 | 1,0000 | 0,9 | 16 | 1,03 | 103,35% | 1412,76 | 1,4 | 0,3 | 884 | 0,615 | 1 | 0,405 | 0,984 | 40% | 2,393060452 | 1 | Mischlüftung | 100% | 990 | 53% | 974 | 17% | 83% | 0% | 0% | 0% | 9% | |
21 | 8 | Dauerlüften Kippfenster | 860 | 100% | 100% | 0% | 50% | 0 | 0 | 1,5000 | 1,5000 | 7,4 | 22 | 0,73 | 73,17% | 809,99 | 1,8 | 6,8 | 807 | 1 | 1 | 0,394 | 1 | 25% | 2,345026051 | 2 | Quelllüftung + Filterung | 71% | 1195 | 145% | 975 | 31% | 23% | 46% | 0% | 0% | 15% | |
22 | 2 | Quelllüftung + Filterung | 800 | 48% | 95,0% | 0% | 50% | 30 | 1 | 0,7125 | 1,4249 | 6,6 | 4 | 0,71 | 70,66% | 1194,53 | 1,5 | 3,2 | 975 | 0,537 | 1 | 0,31 | 1 | 15% | 1,525240206 | 3 | UV-C-Luftreiniger | 66% | 1413 | 189% | 884 | 41% | 21% | 37% | 2% | 0% | 19% | |
23 | 4 | Filter-Luftreiniger | 1200 | 0% | 94,9% | 0% | 0% | 30 | 3 | 0,0000 | 0,9491 | 6,6 | 10 | 0,55 | 54,75% | 1412,76 | 2,7 | 0,3 | 884 | 0,615 | 1 | 0,405 | 0,984 | 23% | 2,744416797 | 4 | Filter-Luftreiniger | 55% | 1413 | 272% | 884 | 41% | 21% | 37% | 2% | 0% | 23% | |
24 | 3 | UV-C-Luftreiniger | 800 | 0% | 94,1% | 0% | 0% | 30 | 3 | 0,0000 | 0,9405 | 4,7 | 7 | 0,66 | 65,66% | 1412,76 | 1,9 | 0,3 | 884 | 0,615 | 1 | 0,405 | 0,984 | 19% | 2,744416797 | 5 | Stoßlüften reguläre Pausen | 188% | 2372 | 48% | 1.371 | 20% | 11% | 21% | 31% | 18% | 33% | |
25 | 1 | Mischlüftung | 870 | 100% | 100% | 0% | 0% | 0 | 0 | 1,0000 | 1,0000 | 5,3 | 1 | 1,00 | 100,00% | 990,39 | 0,5 | 4,7 | 974 | 1 | 1 | 0,167 | 1 | 9% | 0,5617485189 | 6 | Stoßlüften UBA-Empfehlung | 103% | 1413 | 141% | 884 | 41% | 21% | 37% | 2% | 0% | 40% | |
26 | 10 | FLS verteilte Hauben | 800 | 100% | 100% | 60% | 50% | 0 | 0 | 1,5000 | 1,5000 | 15,9 | 28 | 0,31 | 31,05% | 581,42 | 4,5 | 15,3 | 580 | 1 | 1 | 1 | 1 | 11% | 5,379842964 | 7 | Stoßlüften CO2-Monitor | 63% | 976 | 161% | 670 | 76% | 24% | 0% | 0% | 0% | 13% | |
27 | 7 | Stoßlüften CO2-Monitor | 0 | 0% | 0% | 0% | 0% | 30 | -1 | 0,0000 | 0,0000 | 0,9 | 19 | 0,63 | 62,59% | 976,50 | 1,6 | 0,3 | 670 | 1 | 1 | 0,762 | 1 | 13% | 3,406540584 | 8 | Dauerlüften Kippfenster | 73% | 810 | 184% | 807 | 39% | 61% | 0% | 0% | 0% | 25% | |
28 | 5 | Stoßlüften reguläre Pausen | 0 | 100% | 100% | 0% | 0% | 30 | 1,00 | 1,0000 | 1,0000 | 0,9 | 13 | 1,88 | 187,87% | 2371,98 | 0,5 | 0,3 | 1371 | 0,313 | 0,825 | 0,203 | 0,518 | 33% | 0,8461956449 | 9 | FLS Abluft-Ventilator | 55% | 700 | 194% | 700 | 100% | 0% | 0% | 0% | 0% | 12% | |
29 | 9 | FLS Abluft-Ventilator | 1200 | 1 | 1 | 0 | 50% | 0 | 0 | 1,5000 | 1,5000 | 9,9 | 25 | 0,55 | 55,30% | 700,32 | 1,9 | 9,3 | 700 | 1 | 1 | 1 | 1 | 12% | 2,568819135 | 10 | FLS verteilte Hauben | 31% | 581 | 454% | 580 | 100% | 0% | 0% | 0% | 0% | 11% | |
30 | 11 | Stoßlüften großen Pausen | 0 | 1 | 1 | 0 | 0 | 30 | 0 | 1,0000 | 1,0000 | 0,9 | 31 | 3,02 | 301,79% | 3814,12 | 0,1 | 0,3 | 2170 | 0,202 | 0,454 | 0,149 | 0,302 | 11% | 0,2141850416 | 11 | Stoßlüften großen Pausen | 302% | 3814 | 9% | 2.170 | 15% | 5% | 10% | 15% | 55% | 11% | |
31 | unter 800 | 800 bis 1000 | 1000 bis 1400 | 1400 bis 2000 | über 2000 | |||||||||||||||||||||||||||||||||
32 | 17 | Stoßlüften UBA-Empfehlung | 0 | 100% | 100% | 0% | 0% | 6 | 3 | 1,0000 | 1,0000 | 0,9 | 49 | 2,16 | 112,45% | 1006,13 | 1,3 | 0,3 | 1723 | 0,093 | 0,764 | 0,028 | 0,265 | 23% | 1,351356346 | 12 | Mischlüftung | 24% | 141 | 225% | 1.097 | 10% | 18% | 72% | 0% | 0% | 56% | |
33 | 19 | Dauerlüften Kippfenster | 430 | 100% | 100% | 0% | 25% | 0 | 0 | 1,2500 | 1,2500 | 3,6 | 55 | 1,42 | 68,42% | 499,56 | 2,0 | 3,0 | 1246 | 0,163 | 1 | 0,036 | 1 | 49% | 2,123755035 | 13 | Quelllüftung + Filterung | 41% | 440 | 249% | 1.508 | 3% | 2% | 28% | 67% | 0% | 60% | |
34 | 13 | Quelllüftung + Filterung | 800 | 38% | 75% | 0% | 25% | 0 | 0 | 0,4688 | 0,9375 | 4,6 | 37 | 1,12 | 41,14% | 439,90 | 2,5 | 2,2 | 1508 | 0,056 | 1 | 0,033 | 0,334 | 60% | 1,615592172 | 14 | UV-C-Luftreiniger | 53% | 2028 | 236% | 2.185 | 3% | 2% | 12% | 22% | 61% | 58% | |
35 | 15 | Filter-Luftreiniger | 800 | 0% | 75% | 0% | 0% | 6 | 1 | 0,0000 | 0,7493 | 3,9 | 43 | 1,18 | 62,90% | 2028,16 | 2,4 | 0,3 | 2185 | 0,046 | 0,388 | 0,028 | 0,167 | 58% | 1 | 15 | Filter-Luftreiniger | 63% | 2028 | 237% | 2.185 | 3% | 2% | 12% | 22% | 61% | 58% | |
36 | 14 | UV-C-Luftreiniger | 800 | 0% | 74% | 0% | 0% | 6 | 1 | 0,0000 | 0,7425 | 3,9 | 40 | 1,18 | 52,62% | 2028,16 | 2,4 | 0,3 | 2185 | 0,046 | 0,388 | 0,028 | 0,167 | 58% | 1 | 16 | Stoßlüften reguläre Pausen | 91% | 1069 | 100% | 2.185 | 3% | 2% | 12% | 22% | 61% | 0% | |
37 | 12 | Mischlüftung | 870 | 79% | 75% | 0% | 0% | 0 | 0 | 0,7895 | 0,7500 | 4,2 | 34 | 1,24 | 23,71% | 141,46 | 2,3 | 3,7 | 1097 | 0,283 | 1 | 0,102 | 1 | 56% | 2,584666048 | 17 | Stoßlüften UBA-Empfehlung | 112% | 1006 | 129% | 1.723 | 3% | 7% | 17% | 50% | 24% | 23% | |
38 | 21 | FLS verteilte Hauben | 800 | 100% | 100% | 30% | 25% | 0 | 0 | 1,2500 | 1,2500 | 8,0 | 61 | 0,63 | 31,80% | 185,12 | 4,4 | 7,4 | 760 | 1 | 1 | 1 | 1 | 77% | 5,07380701 | 18 | Stoßlüften CO2-Monitor | 35% | 15 | 285% | 931 | 15% | 86% | 0% | 0% | 0% | 65% | |
39 | 18 | Stoßlüften CO2-Monitor | 0 | 0% | 0% | 0% | 0% | 6 | -1 | 0,0000 | 0,0000 | 0,9 | 52 | 0,98 | 35,36% | 15,10 | 2,8 | 0,3 | 931 | 1 | 1 | 0,145 | 1 | 65% | 3,407182317 | 19 | Dauerlüften Kippfenster | 68% | 500 | 197% | 1.246 | 4% | 13% | 84% | 0% | 0% | 49% | |
40 | 16 | Stoßlüften reguläre Pausen | 0 | 100% | 100% | 0% | 0% | 6,0 | 1 | 1,0000 | 1,0000 | 0,9 | 46 | 2,79 | 90,89% | 1068,94 | 1,0 | 0,3 | 2185 | 0,046 | 0,388 | 0,028 | 0,167 | 0% | 1 | 20 | FLS Abluft-Ventilator | 34% | 219 | 311% | 910 | 21% | 79% | 0% | 0% | 0% | 68% | |
41 | 20 | FLS Abluft-Ventilator | 800 | 100% | 100% | 0% | 25% | 0,0 | 0 | 1,2500 | 1,2500 | 5,9 | 58 | 0,90 | 34,47% | 219,03 | 3,1 | 5,3 | 910 | 1 | 1 | 0,206 | 1 | 68% | 3,551664907 | 21 | FLS verteilte Hauben | 32% | 185 | 444% | 760 | 100% | 0% | 0% | 0% | 0% | 77% | |
42 | 22 | Stoßlüften großen Pausen | 0 | 100% | 100% | 0% | 0% | 6,0 | 0 | 1,0000 | 1,0000 | 0,9 | 64 | 3,34 | 31,75% | 492,94 | 0,8 | 0,3 | 2645 | 0,043 | 0,304 | 0,028 | 0,132 | -20% | 0,7941423699 | 22 | Stoßlüften großen Pausen | 32% | 493 | 84% | 2.645 | 3% | 2% | 9% | 17% | 70% | -20% | |
43 | ||||||||||||||||||||||||||||||||||||||
44 | ||||||||||||||||||||||||||||||||||||||
45 | ||||||||||||||||||||||||||||||||||||||
46 | ||||||||||||||||||||||||||||||||||||||
47 | ||||||||||||||||||||||||||||||||||||||
48 | ||||||||||||||||||||||||||||||||||||||
49 | Trenner | .. | ||||||||||||||||||||||||||||||||||||
50 | Bezeichnung | kont. Luftdurchsatz (Qi) m³/h | Frischluft Anteil bzgl. CO2 (ηCO2) (%) | Frischluftanteil bzgl. Aerosol (ηaero) (%) | Hauben Effekt (Anteil abgeführter Emissionen vor Mischen) (%) | Quellluft Effekt (Erhöhung in Abluft gegenüber Mittelwert im Raum) (%) | kontinuierliche äquivalente Luftwechselrate Aerosol (/h) | kontinuierliche äquivalente Luftwechselrate CO2 (/h) | zusätzliche RLWR Stoßlüftens während großer und kleiner Pausen (0-kein Stoßlüften) (1/h) | kleine Pausen zum Lüften pro Doppel-Stunde (0-nur in großer Pause Stoßlüften) | ||||||||||||||||||||||||||||
51 | 1 | Mischlüftung | 870 | 79 .. 100 | 75 .. 100 | 0 | 0 | 4,2 .. 5,3 | 3,7 .. 4,7 | 0 | 0 | |||||||||||||||||||||||||||
52 | 2 | Quelllüftung + Filterung | 800 | 38 .. 48 | 75 .. 95 | 0 | 25 .. 50 | 4,6 .. 6,6 | 2,2 .. 3,2 | 0 .. 30 | 0 .. 1 | |||||||||||||||||||||||||||
53 | 3 | UV-C-Luftreiniger | 800 | 0 | 74 .. 94 | 0 | 0 | 3,9 .. 4,7 | 0,3 | 6 .. 30 | 1 .. 3 | |||||||||||||||||||||||||||
54 | 4 | Filter-Luftreiniger | 800 .. 1200 | 0 | 75 .. 95 | 0 | 0 | 3,9 .. 6,6 | 0,3 | 6 .. 30 | 1 .. 3 | |||||||||||||||||||||||||||
55 | 5 | Stoßlüften reguläre Pausen | 0 | 100 | 100 | 0 | 0 | 0,9 | 0,3 | 6 .. 30 | 1,00 | |||||||||||||||||||||||||||
56 | 6 | Stoßlüften UBA-Empfehlung | 0 | 100 | 100 | 0 | 0 | 0,9 | 0,3 | 6 .. 30 | 3 | |||||||||||||||||||||||||||
57 | 7 | Stoßlüften CO2-Monitor | 0 | 0 | 0 | 0 | 0 | 0,9 | 0,3 | 6 .. 30 | (5 .. 12) | |||||||||||||||||||||||||||
58 | 8 | Dauerlüften Kippfenster | 430 .. 860 | 100 | 100 | 0 | 25 .. 50 | 3,6 .. 7,4 | 3 .. 6,8 | 0 | 0 | |||||||||||||||||||||||||||
59 | 9 | FLS Abluft-Ventilator | 800 .. 1200 | 100 | 100 | 0 | 25 .. 50 | 5,9 .. 9,9 | 5,3 .. 9,3 | 0 | 0 | |||||||||||||||||||||||||||
60 | 10 | FLS verteilte Hauben | 800 | 100 | 100 | 30 .. 60 | 25 .. 50 | 8 .. 15,9 | 7,4 .. 15,3 | 0 | 0 | |||||||||||||||||||||||||||
61 | 11 | Stoßlüften großen Pausen | 0 | 100 | 100 | 0 | 0 | 0,9 | 0,3 | 6 .. 30 | 0 | |||||||||||||||||||||||||||
62 | ||||||||||||||||||||||||||||||||||||||
63 | Trenner | ; | Zeitanteile | |||||||||||||||||||||||||||||||||||
64 | relative inhalierte Dosis (%) | max. CO2-Konzentration (ppm) | Verbesserungsfaktor | Reduktion (%) | unter 800 | 800 bis 1000 | 1000 bis 1400 | 1400 bis 2000 | über 2000 | Median CO2 | ||||||||||||||||||||||||||||
65 | Mischlüftung | 100 ; 124 | 990 ; 1132 | 2,8 ; 2,3 | 64 ; 56 | 17 ; 10 | 83 ; 18 | 0 ; 72 | 0 | 0 | 974 ; 2071 | |||||||||||||||||||||||||||
66 | Quelllüftung + Filterung | 71 ; 112 | 1195 ; 1634 | 3,9 ; 2,5 | 75 ; 60 | 31 ; 3 | 23 ; 2 | 46 ; 28 | 0 ; 67 | 0 | 975 ; 2483 | |||||||||||||||||||||||||||
67 | UV-C-Luftreiniger | 66 ; 118 | 1413 ; 3441 | 4,2 ; 2,4 | 76 ; 58 | 41 ; 3 | 21 ; 2 | 37 ; 12 | 2 ; 22 | 0 ; 61 | 884 ; 3069 | |||||||||||||||||||||||||||
68 | Filter-Luftreiniger | 55 ; 118 | 1413 ; 3441 | 5,1 ; 2,4 | 80 ; 58 | 41 ; 3 | 21 ; 2 | 37 ; 12 | 2 ; 22 | 0 ; 61 | 884 ; 3069 | |||||||||||||||||||||||||||
69 | Stoßlüften reguläre Pausen | 188 ; 279 | 2372 ; 3441 | 1,5 ; 1 | 33 ; 0 | 20 ; 3 | 11 ; 2 | 21 ; 12 | 31 ; 22 | 18 ; 61 | 1371 ; 3556 | |||||||||||||||||||||||||||
70 | Stoßlüften UBA-Empfehlung | 103 ; 216 | 1413 ; 2419 | 2,7 ; 1,3 | 63 ; 23 | 41 ; 3 | 21 ; 7 | 37 ; 17 | 2 ; 50 | 0 ; 24 | 884 ; 2607 | |||||||||||||||||||||||||||
71 | Stoßlüften CO2-Monitor | 63 ; 98 | 976 ; 992 | 4,5 ; 2,8 | 78 ; 65 | 76 ; 15 | 24 ; 86 | 0 | 0 | 0 | 670 ; 1601 | |||||||||||||||||||||||||||
72 | Dauerlüften Kippfenster | 73 ; 142 | 810 ; 1310 | 3,8 ; 2 | 74 ; 49 | 39 ; 4 | 61 ; 13 | 0 ; 84 | 0 | 0 | 807 ; 2053 | |||||||||||||||||||||||||||
73 | FLS Abluft-Ventilator | 55 ; 90 | 700 ; 919 | 5 ; 3,1 | 80 ; 68 | 100 ; 21 | 0 ; 79 | 0 | 0 | 0 | 700 ; 1610 | |||||||||||||||||||||||||||
74 | FLS verteilte Hauben | 31 ; 63 | 581 ; 767 | 9 ; 4,4 | 89 ; 77 | 100 ; 100 | 0 | 0 | 0 | 0 | 580 ; 1340 | |||||||||||||||||||||||||||
75 | Stoßlüften großen Pausen | 302 ; 334 | 3814 ; 4307 | 0,9 ; 0,8 | -8 ; -20 | 15 ; 3 | 5 ; 2 | 10 ; 9 | 15 ; 17 | 55 ; 70 | 2170 ; 4815 | |||||||||||||||||||||||||||
76 | ||||||||||||||||||||||||||||||||||||||
77 | ||||||||||||||||||||||||||||||||||||||
78 | ||||||||||||||||||||||||||||||||||||||
79 | ||||||||||||||||||||||||||||||||||||||
80 | ||||||||||||||||||||||||||||||||||||||
81 | ||||||||||||||||||||||||||||||||||||||
82 | ||||||||||||||||||||||||||||||||||||||
83 | ||||||||||||||||||||||||||||||||||||||
84 | ||||||||||||||||||||||||||||||||||||||
85 | ||||||||||||||||||||||||||||||||||||||
86 | ||||||||||||||||||||||||||||||||||||||
87 | ||||||||||||||||||||||||||||||||||||||
88 | ||||||||||||||||||||||||||||||||||||||
89 | ||||||||||||||||||||||||||||||||||||||
90 | ||||||||||||||||||||||||||||||||||||||
91 | ||||||||||||||||||||||||||||||||||||||
92 | ||||||||||||||||||||||||||||||||||||||
93 | ||||||||||||||||||||||||||||||||||||||
94 | ||||||||||||||||||||||||||||||||||||||
95 | ||||||||||||||||||||||||||||||||||||||
96 | ||||||||||||||||||||||||||||||||||||||
97 | ||||||||||||||||||||||||||||||||||||||
98 | ||||||||||||||||||||||||||||||||||||||
99 | ||||||||||||||||||||||||||||||||||||||
100 | ||||||||||||||||||||||||||||||||||||||