Cable Size & Voltage Drop Calculationjignesh.parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com1
3
4
:Input Data Sheet::Calculation::Results:FALSE
5
6
7
Electrical Load5.00KwTotal Electrical Load5.00KW(1) No of Parallel Run of Cable:O.K1
8
Motor Load0.00KwTotal Electrical Load in KVA5.00KVA(2) Cable Short Circuit Capacity:Not Applicable10.57
9
Total Load5.00KwTotal Full Load Curent20.83Amp(3) Cable Voltage Drop:High0
10
Type of Supply SystemSingle PhaseElectrical Load Starting Current20.83Amp(4) Selection of Cable Type:Not Proper0
11
System Voltage V(L-N)240.00VoltElectrical Motor Starting Current0.00Amp(5) Motor Starting Voltage DropHigh0
12
System Voltage V(L-N)240VoltTotal Starting Current20.83Amp1
13
Demand Factor1.00Starting CosØ :Required Action for Proper Cable Selection:
14
Power Factor1.00Starting SinØ 1.00
15
Short circuit Current(If You Know)K.AmpRuning CosØ1.00
16
Allowable voltage drop at RunningRuning SinØ0.00√ Select Higher Size of Cable to reduce Voltage Drop
17
Allowable voltage drop at StartingCable Derating Factor:
18
Motor Lock Rotor Current (If You Know):
AmpCable Installation MediaAir√ Select Other Type of Motor Starter
19
Motor Lock Rotor Current:
X Full Load Current
Air Temperature (K1)0.98√ Increase No's of Run of Cable to reduce Voltage Drop
20
Motor Starting Power Factor:Group Correction Factor for Air (K2)1.00
21
Cable Detail:Cable Selection is Not ProperFALSE
22
Type of Cable:LT XLPE (Up to 1.1 KV)
23
Cable Conductor:CUTotal Derating Factor0.98
24
Size of Cable:4cX4 Cable Calculation
25
No of Parallel Run of Cable1No'sConductor Resistance. 3.69Ohm / km
26
Cable Length (Distance)50MeterConductor Reactance0.11Mho/km Motor Starter is not Proper2
27
Cable Laying Method:Cable Current Capacity 39 Amp
28
Cable Installation MediaAir1Derating Current38Amp
29
Air Temperature (K1)35°CMin.Required No of Runs of Cable1.00Nos
30
Type
Cable Laying ArrangementTrefoilVoltage Drop Calculation:Voltage Drop at Starting3.2%
31
Distance Between each Cable0.25 mtReceving end Voltage232VoltVoltage Drop at Running3.2%
32
No's of Cable per Tray or Rack1Allowable voltage drop at Running0Volt
33
No's of Tray or Rack1Allowable voltage drop at Starting0Volt
34
1.5S.C Capacity of Selected Cable 0.572 K.Amp
35
Not KnownVoltage Drop at Starting3.2%
36
Damp SoilVoltage Drop at Running3.2%
37
38
39
Formula For % Voltage Drop:=
40
(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line VoltageXNo of RunX1000
41
42
43
44
45
46
47
48
49
50
51
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212