PROJECT :
PAGE :
3
T. Li
CLIENT :
DESIGN BY :
4
JOB NO. :
DATE :
REVIEW BY :
5
Coupling Beam Design
6
7
8
INPUT DATA
9
CONCRETE STRENGTH
fc'=4ksi
10
REBAR YIELD STRESS
fy=60ksi
11
FACTORED SHEAR LOAD
Vu=254k
12
13
WIDTHb=16in
14
OVERALL DEPTH
h=72in
15
CLEAR SPAN
L=6ft
16
DIAGONAL BARS, Ad
4#9
17
DIAGONAL TIES, Ash
#4@4
18
HORIZONTAL BARS, Avh
16#4
( 2 layers @ 10 in o.c. )
19
VERTICAL TIES, Av
2legs #3@6in o.c.
20
21
ANALYSIS
22
23
CHECK DIAGONAL BARS (SEC.1921.6.10.2)
24
25
Vu<255k
[SATISFACTORY]
26
27
CHECK TIES AROUND DIAGONAL BARS (SEC. 1921.4.4)
28
29
30
0.384in2<
31
[SATISFACTORY]
32
33
34
CHECK VERTICAL TIES (SEC. 1911.8.9)
35
36
0.144in2<
37
[SATISFACTORY]
38
39
40
CHECK HORIZONAL BARS (SEC. 1911.8.10)
41
42
0.383in2<
43
[SATISFACTORY]
44
45
46
LONGITUDIANL BARS (SEC. 1910.5.1)
47
48
49
3.07in2===> ( 4#8
longitudinal bars both top & bottom)
50
51
52
These bars are not recommended by SEAOC to be used, and are not shown in figure above.
53
54
55
56
57
58
59
60
61
62
LICENSE NUMBER: ?????
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100