ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
Login1234of 4335
Belangrijke settings
2
Admin Login123456
3
4
Basic Settings
5
Cell Count:16Calibrating Volt. (V):55,212
6
Battery Capacity (AH):314Calibrating Cur. (A):6,998
7
Balance Trig Volt. (V):0,001
8
9
Advance Settings
10
Start Balance Volt. (V):3,450Charge UTPR °C:4
Charge Under Temperature Protection Recovery
11
Max Balance Cur.(A):2,0MOS OIP °C:90
MOS Over Current Protection Temperature
The temperature at which the MOSFETs (the power switches) are protected from overcurrent by the BMS. If the temperature exceeds this threshold, the system will shut down the discharge or charge to protect the MOSFETs.
12
Cell OVP (V):3,650Cell Over Voltage Protection VoltageThe voltage at which the BMS will stop charging to prevent overvoltage damage to the cells.MOS OTPR °C:70
MOS Over Temperature Protection Recovery
The temperature at which the MOSFETs can resume normal operation after being shut down due to overtemperature protection. Once the MOSFETs cool down below this value, the system can recover and resume charging or discharging.
13
Vol. Cell RCV (V):3,450Cell Voltage Recovery VoltageThe voltage threshold at which the BMS will check if the cells are safe to resume charging after an overvoltage protection event. This is a recovery threshold after an overvoltage event occurs.SCP Delay (µs):1000Short Circuit Protection
14
SOC-100%Volt. (V):3,449SOC 100% VoltageThe voltage at which the battery is considered to be at 100% State of Charge (SOC).SCPR Time (S):60Short Circuit Protection Recovery time
15
Cell OVPR (V):3,448Cell Over Voltage Protection RecoveryThe voltage at which the system will allow charging to resume after a cell overvoltage event, once the cell voltage drops back down.
Dischrg. Pre. Chrg. T(S):
5Discharge Pre-Charge TimeThis setting refers to the amount of time (in seconds) that the BMS waits before starting a discharge operation after a pre-charge has been completed. Essentially, it’s a delay period before the system begins discharging after certain conditions have been met.
16
Cell UVPR (V):3,05Cell Under Voltage Protection RecoveryThe voltage at which the system will allow charging or discharging to resume after an under-voltage event. After a cell dips below the UVP (Under Voltage Protection) threshold, the system checks to see if it has recovered to this level before resuming operation.Device Addr:1
17
SOC-0% Volt. (V):2,9SOC 0% Voltage
Data Stored Period (S):
864000
18
Cell UVP (V):2,85Cell Under Voltage ProtectionThe voltage at which the BMS will stop discharging to prevent deep discharge of the cells, which could cause irreversible damage.RCV Time (H):1Recovery Check Voltage TimeThe interval (in hours) at which the BMS checks the battery for voltage recovery after it has entered a protection state (e.g., overvoltage or undervoltage).
19
Power Off VoL. (V):2,7Power Off VoltageThe voltage at which the system will turn off and stop all operations, usually to prevent deep discharge or excessive energy drain when the battery is low.RFV Time(H):9Rebalance Forced Voltage TimeThe interval (in hours) at which the BMS performs a forced voltage balancing cycle to ensure that all cells remain at similar voltages.
20
Vol. Cell RFV (V):3,35Cell Voltage Rebalance VoltageThe voltage at which the BMS will start balancing the cells. This setting is related to how the BMS triggers the balancing process if there's a voltage difference between cells.User Private Data:JK-BMS
21
Vol. Smart Sleep (V):3Voltage Smart SleepThe voltage at which the BMS enters "smart sleep" mode to reduce power consumption when the system is not in use. This feature is designed to conserve battery power while still monitoring voltage levels.User Data 2:JK-BMS
22
Time Smart Sleep(h):24UART1 Protocol No:
000-4G-GPS Remote module Common protocol V4,2
23
Continued Charge Curr.(A):120UART2 Potocol No:001-JK BMS RS485 Modbus V1.0
24
Charge OCP Delay (S):30Over Current Protection timeCAN Potocol No:004-Victron CANbus BMS protocol20170717
25
Charge OCPR Time (S):60Over Current Protection Recovery timeLCD Buzzer Trigger:09-MOSFET Over Temperature
26
Continued Discharge Curr.(A):120
LCD Buzzer Trigger Val:
100
27
Discharge OCP Delay (S):300Over Discharge Current Protection time
LCD Buzzer Release Val:
95
28
Discharge OCPR Time (S):60
Over Discharge Current Protection Recovery time
DRY 1 Trigger:08-Battery Over Temperature
29
Charge OTP °C:50Charge Over Temperature ProtectionDRY 1 Trigger Val:60
30
Charge OTPR °C:45
Charge Over Temperature Protection Recovery
DRY 1 Release Val:50
31
Discharge OTP °C:50Discharge Over Temperature ProtectionDRY 2 Trigger:00 - OFF
32
Discharge OTPR °C:45
Discharge Over Temperature Protection Recovery
DRY 2 Trigger Val:0
33
Charge UTP(°C):2Charge Under Temperature Protection.DRY 2 Release Val:0
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49