Transformer Losses & Efficiency Calcualation
3
4
:Three Phase Transformer Detail: NAME PLATE
:I²R Losses Calculation:
5
Transformer MakeDemo Transformer HV Full load current :0.87Amps
6
Transformer Serial NoTipsENGINEER/001LV Full load current :20.87Amps
7
KVA rating of Transformer15000VAHV Side I2R losses 237.389Watts
8
Primary voltage 10000VoltsLV Side I²R losses 143.72Watts
9
Secondary voltage415VoltsTotal I² R lossses @ Amb temp381.10Watts
10
Primary side ConnectionDELTATotal Stray losses @ Amb temp 13.90Watts
11
Scondary side ConnectionSTARI² R lossses @75° c temp 445.82Watts
12
No load losses71WattsStray losses @ 75° c temp 11.88Watts
13
No load current0.6AmpsTotal Full load losses at @75° c 457.70Watts
14
Full load losses395WattsTotal Impedance at ambient temp 869.95Ohms
15
Impedance voltage435VoltsTotal Resistance at amb temp 508.11Ohms
16
Lv resistance in milli ohms220m OhmsTotal Reactance (X) : 706.14Ohms
17
Hv resistance in ohms 211OhmsResistance at@ 75° c594.39Ohms
18
Amb temperature 30Deg c Impedance at 75° c 923.00Ohms
19
Total Connected Load on Transformer
9000VAPercentage Impedance 4.62%
20
% Loading of Transformer60%Percentage Resistance 2.97%
21
Percentage Reactance 3.53%
22
Tips Engineer Zone
23
www.tipsengineerzone.in
24
https://www.tipsengineerzone.in/2020/12/transformer-design-online-course-for.html
25
https://tipsengineerzone.myinstamojo.com/
:Efficiency Calculation:
26
Efficiency at P.F of Unity
27
EMAIL ID - tipsandtricksengineerzone@gmail.com
At Transformer Loading 125%96.57%
28
Visit Website : www.tipsengineerzone.in
At Transformer Loading 100%97.07%
29
MOBILE - 9798760634At Transformer Loading 75%97.53%
30
ADDRESS - GurgaonAt Transformer Loading 50%97.83%
31
At Transformer Loading 25%97.53%
32
Efficiency at P.F of 0.8
33
At Transformer Loading 125%99.49%
34
At Transformer Loading 100%96.37%
35
At Transformer Loading 75%96.93%
36
At Transformer Loading 50%97.30%
37
At Transformer Loading 25%96.94%
38
39
40
FormulasRemarks
41
HV Full load current = VA / (1.732xVolt)VL - LINE VOLTAGE
42
LV Full load current = VA / (1.732xVolt)
43
HV Side I2R losses = I²R x1.5IL - LINE CURRENT , Resistance Ph- Ph
44
LV Side I²R losses = I²R x0.5x3IL - LINE CURRENT , Resistance Ph- Ph
45
Total I² R lossses @ Amb temp = Hv losses+ Lv losses
46
Total Stray losses @ Amb temp =Measured losses -I² R losses
47
I² R lossses @75° c temp = ((235+75) x losses) / (225+ Amb temp)Copper
48
Stray losses @ 75° c temp=((235+Amb temp)(Stray losses at amb)) / 310
RT=R0(235+T)/(235+Amb Temp)
49
Total Full load losses at @75° c = I²R losses at 75°c+Stray losses at 75°c
50
Total Impedance at ambient temp =(Imp voltage x1.732) / Full load current
51
Total Resistance at amb temp = I²R losses / I²
52
Total Reactance (X) =SQRT(Impedance ²- Resitance ²)
53
Resistance at@ 75° c =(310 x resistance at amb ) /(235+Amb temp)
54
Impedance at 75° c =SQRT(R² at 75 + X²)
55
Percentage Impedance =(Z at 75° c x I x 100)/V1
56
Percentage Resistance =( R 75° c x I x 100)/V1
57
Percentage Reactance =(X x I x 100) / V1
58
59
Efficiency at Unity P.F
60
At 125 % of Transformer Loading =(Kva x 1.25 x 100)/((kva x 1.25)+(I²R losses x 1.25²)+(No Load Losses))
61
Efficiency at 0.8 P.F
62
At 125 % of Transformer Loading =(Kva x 1.25xp.f x 100)/((kva xp.fx 1.25)+(I²R losses x 1.25²)+(No Load Losses))
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100