Recommendations List - Five-fixed Evaluation
2
2024 - August
3
#EvaluatorFacilityRemarkRequired Time PeriodRemarks
4
1Mr. Pavithra(60 & 70) Jetty Fire Pump HouseCorrosion in exhaust silencers of diesel fire pumps, No tags in some valves.-Waiting for Heat Resistance paints from ENS
5
2Mr. Pavithra(60 & 70) Jetty 01Damaged wind sock
Corroded valves in MGO and VLSFO pipelines
MGO valves with paint coating removed.
Done
6
3Mr. Pavithra(60 & 70) Jetty 02Corroded valves in MGO & MFO pipelines
valves with paint coating removed.
-New valve- Done. Old valve- LPG.
7
4Mr. Poojitha(20) 20 Pump House4.1) P-2101B oil level is low.
4.2) Some valve tags are missing.
4.3) Uploaded inspection checklists missing 'Approved By' signature.
Done
8
5Mr. Poojitha(20) 20 Gantry5.1) Name tags are missing in some equipment.
5.2) Unnecessary items were seen on the platform.
5.3 ) Corrosion is seen in platform ladder in some devices at gantry.
Done
9
6Mr. Poojitha(20) 20 Control Room6.1) 2 mice are missing.
6.2) Emergency light is not working.
6.3) Emergency items cabinet missing items.
-6.1) Need to purchase
6.2) ENS need to supply
6.3) -
10
7Mr. Dimuth(20) CCRHoenywell panel triggering issue was not yet rectifiedDone
11
8Mr. Poojitha(20) CCR8.1) No marker pen stand and a/c remote holder.
8.2) Fungi is seen in soffit.
8.3) Cement filled sunk boxes near CCTV big screens are not finished well.
Done
12
9Mr. Poojitha(20) 20 Tanks9.1) Wheels of hand valves of the tanks are corroded.
9.2) Name tags are missing especially in Nitrogen pipeline.
9.3) Tank dewatering valve tags are missing.
9.4) 'Approved By' signature is missing in uploaded inspection checklists.
9.5) Corroded flexible hoses.
9.2&9.3) Done according to the P&ID
9.1) Need paint
9.5) Plan B
13
10Mr. Poojitha(20) 20 Admin Building20 admin building is at a glance seen not properly organized.ENS
14
11Mr. GeethENS Admin AreaOne of urinator push buttons is not working properly at 1st floor washroomDone
15
12Mr. Prabath(40 & 50) TF Substation RoomFew window locks have been brokenDone
16
13Mr. Randika(40 & 50) TF Fire Pump HouseA breakdown of an electric pump was reported during the period of evaluation and it was rectified.Done
17
14Mr. Randika(40 & 50) Warehouse14.1) A/C was not working during the time of evaluation.
14.2) PICs of some of the Five fixed signboards infront of the rooms needs to be changed.
14.1) Done
14.4) Waiting for 5Fix board from ENS
18
15Mr. Randika(40 & 50) Maintenance Workshop15.1) Hil T machine is not repaired yet.
15.2) Suggest to maintain good house keeping inside the tool room of workshop.
Done
19
16Mr. Randika(40 & 50) Water Treatment PlantAn air blower is out of order.No spare parts
20
2024 - September
21
#EvaluatorFacilityRemarkRequired Time PeriodRemarks
22
17Mr. Jihan(60 & 70) Jetty Fire Pump HouseFire pump 1 out of order
Need to clean cob webs
Done
23
18Mr. Pavithra(60 & 70) Jetty Fire Pump HouseCorroded exhaust silencers of fire pumpsNeed Heat Resistance paint, ENS Supply.
24
19Mr. Jihan(60 & 70) Jetty Control RoomUnnecessary material found on the rackDone
25
20Mr. Pavithra(60 & 70) Jetty Control RoomFault fire alarm issue - Battery replacementDone
26
21Mr. Jihan(60 & 70) Jetty Substation RoomOld exhaust openings to be properly sealed
Need to do some derusting
Done
27
22Mr. Pavithra(60 & 70) Jetty Substation RoomCompleted inspection checklist has not been handed over to the ENS Division as per the deadline.DoneOn 07/10/2024
28
23Mr. Jihan(60 & 70) Jetty Generator RoomNeed derusting
Steel tape to be place in a proper place
DoneSteel tape in CCR
29
24Mr. Jihan(60 & 70) Jetty 01Manifold, Mounting bolts to be derustDone
30
25Mr. Pavithra(60 & 70) Jetty 01Corroded MGO, MFO pipeline valvesDone
31
26Mr. Jihan(60 & 70) Jetty 02Mounting bolts to be derust
need cleaning
Done
32
27Mr. Pavithra(60 & 70) Jetty 02Corroded MGO & MFO pilpeline valvesDone
33
28Mr. Jihan(60 & 70) Jetty 01 Tool RoomTool room not locked, need cleaningDoneKeys in CCR
34
29Mr. Pavithra(60 & 70) Jetty 01 Tool RoomFFMS Sign board has been dismantled. Need to fix.Done
35
30Mr. Wang(60 & 70) High Mast LightingSome cable cabinet were corrosionDone
36
31Mr. Wang(30) 30 TanksBirds nest were observed on the tanks.DoneKeep removing
37
32Mr. Poojitha(20) 20 Pump HouseLog sheets at document box is not long filled.
Fixed gas detector hasn't been working. (Now rectified)
Vent valve name tags not seen.
-Some valves name tags were not in the P&ID.Available tags already done.
38
33Mr. Dimuth(20) 20 GantryCorroded step ladder and light hanging chainsDone
39
34Mr. Poojitha(20) 20 GantryNo name tags for the strainer and flow meter of the pipeline.
Lights on/off switch has no name tag and on/off switch position tag.
DoneCan not mark On/Off of Rotory switch
40
35Mr. Dimuth(20) 20 Control RoomUPS problem-Waiting for New UPS, ENS supply.
41
36Mr. Poojitha(20) 20 Control RoomBird nest at washroom.
Broken wall at washroom.
Done
42
37Mr. Kamal(20) 20 TanksCorrosion was found on outer layer of flexible hoses connected to the tanks.Done
43
38Mr. Poojitha(20) 20 TanksNo name plates for some valves. ex: dewatering lines.
Valve handles corroded
DoneSome instrument does not indicating on given P&ID
44
39Mr. Geeth(40 & 50) Fresh Water SystemGrass has grown around system.Done
45
40Mr. GeethOutside Pipeline AreaGrass has grown between the pipelines.Done
46
41Mr. Geeth(60 & 70) Jetty 02 Tool RoomSome material has not been kept in the designated location.
Need to fix jetty 01 five fixed board.
Done5Fix board need to supply by ENS
47
42Mr. Xu(30) 30 Pump HouseCable pipe under 1# pump's filter and filter's exhaust hose corrosion.
The reflective sticker around the fire extinguisher was damaged.
DonePaint & sticker need to sypplu by ENS
48
43Mr. Prabath(30) 30 Pump HouseThere are dust and debris in the pump houseDoneDone during 5Fix
49
44Mr. Xu(30) 30 Control RoomThe washroom exhaust fan had a bird's nest.
Fibre cables are not properly set up in electrical cabinets.
Done
50
45Mr. Xu(40 & 50) TF Substation Roomseveral lamp tubes can't light.Done
51
46Mr. Xu(40 & 50) TF Generator RoomThe safety exit light on the side door is missing.
The generator SOP should be updated with the addition of the new air compressor.
DoneExit light need to supply be ENS
52
47Mr. Xu(40 & 50) Nitrogen Generation SkidThere Should be a cabinet for ear protection and other equipment.
After the phone installation, some of the parts were not properly installed.
Pressure gauges are not marked in red for limits.
Done
53
48Mr. Prabath(40 & 50) Nitrogen Generation SkidNeither FFM sign board nor person assigned for the facility-ENS will attend
54
49Mr. Randika(40 & 50) TF Fire Pump HouseFire pump house floor needs to be cleaned.
Grass is grown heavily around the pump house.
-
Done
Grass removal completed. Fire PH inside cleaning by ERU.
55
50Mr. Randika(40 & 50) WarehouseFive fixed sticker displayed at the front door needs to be replaced with an updated one.DoneSticker need to supply by ENS
56
51Mr. Randika(40 & 50) Water Treatment PlantAir blower is not replaced yet.
Cobwebs and dust found in chemical dosing room.
DoneWaiting for spares for Air blower
57
2024 - October
58
#EvaluatorFacilityRemarkRequired Time PeriodRemarks
59
52Mr. Jihan(60 & 70) Jetty Fire Pump HouseFP 01 is under repair for a long time.
Need house keeping
Done
60
53Mr. Pavithra(60 & 70) Jetty Fire Pump HouseCobwebs & dust on valve surfaces of fire pipeline inside FPH
Poor housekeeping near Foam supply unit
Some dismantled parts have been kept near PAGA box inside FPH
Name tags are not clear and rusted in FD 01 (Fire control panel)
FFMS sign board is not properly aligned
Fire diesel water pump 01 breakdown.
Done
61
54Mr. Pavithra(60 & 70) Jetty Control RoomWall damage inside Jetty CCR
Displays of the remote release control systems are not clear.
DoneDisplay need to replace
62
55Mr. Pavithra(60 & 70) Jetty Substation RoomChecklist has not been uploaded through the QR code.Done
63
56Mr. Jihan(60 & 70) Jetty Generator RoomNeed derustingDone
64
57Mr. Pavithra(60 & 70) Jetty Generator RoomSome dismantled parts have been kept on floor inside the Generator room.Done
65
58Mr. Jihan(60 & 70) Jetty 01Loading arm nameboards damaged, Need derustngENS Supply
66
59Mr. Pavithra(60 & 70) Jetty 01Paint removed (MGO 8") & corroded valves in the process pipelines.Done
67
60Mr. Jihan(60 & 70) Jetty 02Manifolds Need derustingDone
68
61Mr. Pavithra(60 & 70) Jetty 02Insulation cover damage: MFO 20" pipeline
Pipeline sticker damages: MFO,MGO
Fire pipeline section near fire hose boxes need painting
Fresh water pipeline end area has been corroded
No valve tags: MGO 12" pipeline
Ship-shore earthing connection panel lock has been damaged - Need to fix
Ex proof switch inside Ship-shore earthing connection box is loose - Need to fix properly.
Done
69
62Mr. Jihan(60 & 70) Jetty 01 Tool RoomNeed house keepingDone
70
63Mr. Pavithra(60 & 70) Jetty 01 Tool RoomEach compartment in the storage rack should be labelled separately
Housekeeping / 5S inside the Tool room should be improved
Some plants grown inside top of the water drain line.
Done
71
64Mr. Wang(60 & 70) High Mast LightingHigh master tower nearby SR cable need to be clected.Done
72
65Mr. Wang(30) 30 TanksSome equipments are corrosion.Done
73
66Mr. Kamal(20) 20 Pump HouseThe facility was maintained to an acceptable level
74
67Mr. Dimuth(20) 20 Pump HouseVents were not taggedDone
75
68Mr. Poojitha(20) 20 Pump HouseLog sheets at document box is not long filled and document box is not clean.
Vent valves name tags not seen.
Floor cleanliness is average.
Done
76
69Mr. Kamal(20) 20 GantryThe facility was maintained to an acceptable level
77
70Mr. Dimuth(20) 20 GantryPreviously identified issues were not addressed
78
71Mr. Poojitha(20) 20 GantryNo name tags for the strainer and flow meter of the pipeline.
Lights on/off switch has no name tag and on/off switch position tag.
Corrosion: Gantry ladder, support chains of lights, static discharge pole hose clip.
Drain of the L-2101 inlet strainer has no end cap.
Done
79
72Mr. Kamal(20) 20 Control RoomThe facility was maintained to an acceptable level
80
73Mr. Dimuth(20) 20 Control RoomWall beeding was broken in few places??
81
74Mr. Poojitha(20) 20 Control RoomDamaged UPS is not replaced yet for more than 1 month.
1 wall outlet was found without frame.
Tile skirting has fallen down from few places.
1 raised floor tile is missing.
Washroom squatting pan is dirty and not cleaned.
1 electrical cabinet has no tag, desktops, keyboards, mice are not tagged.
Waiting for UPS from ENS
82
75Mr. Kamal(20) CCRThe facility was maintained to an acceptable level
83
76Mr. Poojitha(20) CCRMost of the issues identified in September are rectified except the fabrication of a marker holder for the white board.Done
84
77Mr. Kamal(20) 20 TanksThe facility was maintained to an acceptable level
85
78Mr. Dimuth(20) 20 TanksFire water and foam line support brackets & N2 supply line in T2103 were corrodedDone
86
79Mr. Poojitha(20) 20 TanksNo name plates for some valves. ex: dewatering lines.
Flexibles hoses of the product lines are also corroded.
Maximum allowable pressure of a PG at T-2102 is not seen.
Done
87
80Mr. Kamal(20) 20 Admin BuildingThe facility was maintained to an acceptable level
88
81Mr. Dimuth(20) 20 Admin BuildingDown floor wash room commed issue was not yet resolvedDone
89
82Mr. Poojitha(20) 20 Admin BuildingThe wall of the staircase from ground floor to 1st floor is not clean.
Outside staircase wall is damaged due to raining and bad weather.
Done
90
83Mr. Geeth(40 & 50) Fresh Water SystemOne of valves is heavily corrodedDone
91
84Mr. Geeth(40 & 50) IOMA Rest RoomAC outdoors has corrodedDone
92
85Mr. GeethENS Admin AreaThe monkey ladder has corroded in 1st floorDone
93
86Mr. Danushka(30) 30 Pump HouseNeed to improve housekeepingDone
94
87Mr. Randika(40 & 50) TF Fire Pump HouseN/A
95
88Mr. Randika(40 & 50) WarehousePIC of the 5 fixed signboard displayed at the front needs to be replaced.Done
96
89Mr. Randika(40 & 50) Maintenance WorkshopKeys of the key hanging board needs to be tagged.
One of the welding machine is out of order.
Done
97
90Mr. Randika(40 & 50) Water Treatment PlantAir blower is out of order.Done
98
2024 - November
99
#EvaluatorFacilityRemarkRequired Time PeriodRemarks
100
91Mr. Cheng(60 & 70) Jetty Fire Pump HouseSome parts are rusted