ABCDEFGHIJKLMNOPQRSTUVWXYZ
1
CT Phase Error Calculation
2
Formula (for editable fields)
3
ParameterUnitDescription1000
4
Core Outer DiametermmOuter diameter of core480
5
Core Inner DiametermmInner diameter of core360
6
Core HeightmmHeight of the core (axial)82
7
Cross-sectional Aream^2Calculated from OD and ID0.0049
8
Mean Magnetic Path Length
mAverage magnetic path length1.319
9
FrequencyHzOperating frequency50
10
Relative PermeabilityFor nanocrystalline material80000
11
Secondary TurnsNumber of secondary windings5000.0
12
Secondary CurrentARated secondary current1
13
Secondary VoltageVBurden voltage26.18
14
Magnetizing InductanceHLm = µ₀·µr·A·N² / l9371.4
15
Magnetizing CurrentAIm = Es / (2πfLm)0.00001
16
Phase Error (rad)radiansIm / Is0.00001
17
Phase Error (minutes)minutesRadians to minutes0.031
18
19
20
21
NameOhm
22
Resistance of Measuring Cable
0.05
23
Resistance of CT26.1240.0565
24
Resistance of Instrument0.0065