Calculate Air Ventilation for Transformer / D.G- RoomJignesh.Parmar www.electricalnotes.wordpress.com
3
4
Density of Air at air 1.099kg/m3
5
Specific Heat of Air 0.017
kWxmin/kg x °C
6
Permissible temperature rise10.8°C
7
8
EquipmentQtyRating (KVA)
Power Factor
Efficiency
Rating (Kw)Heat Loss (Kw)
9
Transformer110000.9898.0%98019.6
10
Transformer220000.9898.0%196078.4
11
0
12
0
13
0
14
0
15
98
16
Total Heat Loss98Kw
17
Total Heat Loss5576.2Btu/Min
18
Total Heat Loss334572Btu/Hr
19
Air Quantity Required for ventilation486M3/Min
20
Air Quantity Required for ventilation17150CFM
21
Ventilation System
22
Fan Capacity18000CFM
23
No's of Fan1No's
24
Fan Rating4Kw