Tail end >>>> To Source End (Radial System)
:IDMT Over Current Relay Grading Calculation (50/51):Jignesh.parmar, www.electricalnotes.wordpress.com, jiguparmar@yahoo.com
3
Enter Data in White Background Cells
4
5
Trail end Last Bus BarDBus Bar LocationCBus Bar LocationBBus Bar LocationABus Bar LocationE
6
Load Current (IL)160AmpLoad Current200AmpLoad Current200AmpLoad Current200AmpLoad Current200Amp
7
Min Fault Current2000AmpMin Fault Current3500AmpMin Fault Current3500AmpMin Fault Current3500AmpMin Fault Current3500Amp
8
Max Fault Current3000AmpMax Fault Current4000AmpMax Fault Current4000AmpMax Fault Current4000AmpMax Fault Current4000Amp
9
CT Ratio (Amp) for Relay-D1001CT Ratio (Amp) for Relay-C3001CT Ratio (Amp) for Relay-B3001CT Ratio (Amp) for Relay-A3001CT Ratio (Amp) for Relay-E3001
10
Curve Selection for Relay-DNormal Inverse (NI)Curve Selection for Relay-CNormal Inverse (NI)Curve Selection for Relay-BNormal Inverse (NI)Curve Selection for Relay-ANormal Inverse (NI)Curve Selection for Relay-ENormal Inverse (NI)
11
Plug Setting of Relay-D200%Plug Setting of Relay-C100%Plug Setting of Relay-B100%Plug Setting of Relay-A100%Plug Setting of Relay-E100%
12
TMS of Relay-D0.100SecTMS of Relay-C0.28SecTMS of Relay-B0.42SecTMS of Relay-A0.54SecTMS of Relay-E0.67Sec
13
Relay Error (%)7.5%Relay Error (%)7.5%Relay Error (%)7.5%Relay Error (%)7.5%Relay Error (%)7.5%
14
CT Error (%)10.0%CT Error (%)10.0%CT Error (%)10.0%CT Error (%)10.0%CT Error (%)10.0%
15
Over shoot0.05SecOver shoot0.05SecOver shoot0.05SecOver shoot0.05SecOver shoot0.05Sec
16
C.B Interrupting Time0.17SecC.B Interrupting Time0.10SecC.B Interrupting Time0.10SecC.B Interrupting Time0.10SecC.B Interrupting Time0.10Sec
17
Safety 0.33SecSafety 0.10SecSafety 0.10SecSafety 0.10SecSafety 0.10Sec
18
Total Time Grading:0.58SecTotal Time Grading:0.28Total Time Grading:0.32Total Time Grading:0.35Total Time Grading:0.38
19
Expected Operaion Time of Relay-D0.25SecExpected Operaion Time of Relay-C0.83SecExpected Operaion Time of Relay-B1.10SecExpected Operaion Time of Relay-A1.42SecExpected Operaion Time of Relay-E1.78Sec
20
21
O/L Relay Setting for Section: DO/L Relay Setting for Section: C-DO/L Relay Setting for Section: B-CO/L Relay Setting for Section: A-BO/L Relay Setting for Section: E-A
22
Primary Protection for C-DPrimary Protection for B-CPrimary Protection for A-BPrimary Protection for E-A
23
Operating Time of Relay D at Max Fault at DOperating Time of Relay C at Max Fault at DOperating Time of Relay B at Max Fault at COperating Time of Relay A at Max Fault at BOperating Time of Relay E at Max Fault at A
24
Over Load Current :125%X ILOver Load Current :125%X ILOver Load Current :125%X ILOver Load Current :125%X ILOver Load Current :125%X IL
25
Over Load Current :(In)200AmpOver Load Current :(In)250AmpOver Load Current :(In)250AmpOver Load Current :(In)250AmpOver Load Current :(In)250Amp
26
Required Over Current Relay Plug Setting22 A X InRequired Over Current Relay Plug Setting0.830.8 A X InRequired Over Current Relay Plug Setting0.830.8 A X InRequired Over Current Relay Plug Setting0.830.8 A X InRequired Over Current Relay Plug Setting0.830.8 A X In
27
Actual Plug Setting of Over Current Relay (PMS): (I>)22 A X InActual Plug Setting of Over Current Relay (PMS): (I>)11 A X InActual Plug Setting of Over Current Relay (PMS): (I>)11 A X InActual Plug Setting of Over Current Relay (PMS): (I>)11 A X InActual Plug Setting of Over Current Relay (PMS): (I>)11 A X In
28
Plug Setting Multiplier (PSM):15Plug Setting Multiplier (PSM):10Plug Setting Multiplier (PSM):13Plug Setting Multiplier (PSM):13Plug Setting Multiplier (PSM):13
29
Time Multiplier Setting: (TMS)0.100Time Multiplier Setting: (TMS)0.28Time Multiplier Setting: (TMS)0.418Time Multiplier Setting: (TMS)0.540Time Multiplier Setting: (TMS)0.674
30
Time of Operation of Relay2.52SecTime of Operation of Relay2.97SecTime of Operation of Relay2.63SecTime of Operation of Relay2.63SecTime of Operation of Relay2.63Sec
31
Actual Operaion Time of Relay D: (t>)0.25SecActual Operaion Time of Relay C: (t>)0.83SecActual Operaion Time of Relay B: (t>)1.10SecActual Operaion Time of Relay A: (t>)1.42SecActual Operaion Time of Relay E: (t>)1.78Sec
32
Time Grading:0.58SecTime Grading:0.28SecTime Grading:0.32SecTime Grading:0.35SecTime Grading:0.38Sec
33
Required Operaiting Time of Relay D at Max Fault at Bus-D0.83SecRequired Operaiting Time of Relay D at Max Fault at Bus-C1.10SecRequired Operaiting Time of Relay C at Max Fault at Bus-B1.42SecRequired Operaiting Time of Relay B at Max Fault at Bus-A1.78SecRequired Operaiting Time of Relay A at Max Fault at Bus-E2.16Sec
34
Backup Protection for D-Backup Protection for C-DBackup Protection for B-CBackup Protection for A-B
35
Operating Time of Relay D at Min Fault at DOperation Time of Relay C at Min Fault at DOperation Time of Relay B at Min Fault at COperation Time of Relay A at Min Fault at BOperation Time of Relay E at Min Fault at A
36
Over Current Setting (PMS):2Over Current Setting (PMS):1Over Current Setting (PMS):1Over Current Setting (PMS):1Over Current Setting (PMS):1
37
Plug Setting Multiplier (PSM):10Plug Setting Multiplier (PSM):6.67Plug Setting Multiplier (PSM):11.67Plug Setting Multiplier (PSM):11.67Plug Setting Multiplier (PSM):11.67
38
Time Multiplier Setting0.100Time Multiplier Setting0.28Time Multiplier Setting0.42Time Multiplier Setting0.54Time Multiplier Setting0.67
39
Time of Operation of Relay2.97Time of Operation of Relay3.62Time of Operation of Relay2.78Time of Operation of Relay2.78Time of Operation of Relay2.78
40
Actual Operaion Time of Relay 0.30Actual Operaion Time of Relay 1.01Actual Operaion Time of Relay 1.16Actual Operaion Time of Relay 1.50Actual Operaion Time of Relay 1.87
41
Operating Time of Downsteam Relay0.100Operating Time of Downsteam Relay0.10Operating Time of Downsteam Relay0.28Operating Time of Downsteam Relay0.42Operating Time of Downsteam Relay0.54
42
Time Grading:0.58Time Grading:0.28Time Grading:0.32Time Grading:0.35Time Grading:0.38
43
Actual Operaion Time of Relay D at Min Fault at Bus-D0.8Actual Operaion Time of Relay C at Min Fault at Bus-C0.38Actual Operaion Time of Relay B at Min Fault at Bus-B0.60Actual Operaion Time of Relay A at Min Fault at Bus-A0.77Actual Operaion Time of Relay E at Min Fault at Bus-E0.92
44
:Results::Results::Results::Results::Results:
45
Pick Up Setting of Over Current Relay (I>):OKPick Up Setting of Over Current Relay (I>):OKPick Up Setting of Over Current Relay (I>):OKPick Up Setting of Over Current Relay (I>):OKPick Up Setting of Over Current Relay (I>):OK
46
Pick Up Setting of Over Current Relay (I>):2 A X InRelay Pick up Setting: (I>)1 A X InRelay Pick up Setting: (I>)1 A X InRelay Pick up Setting: (I>)1 A X InRelay Pick up Setting: (I>)1 A X In
47
Time Multiplier Setting: (TMS)0.100SecTime Multiplier Setting: (TMS)0.278SecTime Multiplier Setting: (TMS)0.418SecTime Multiplier Setting: (TMS)0.540SecTime Multiplier Setting: (TMS)0.674Sec
48
Expected Operaion Time of Relay:0.25SecExpected Operaion Time of Relay:0.83SecExpected Operaion Time of Relay:1.10SecExpected Operaion Time of Relay:1.42SecExpected Operaion Time of Relay:1.78Sec
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100