Cable sizing calculatin
3
4
Cable Sizing Calculation – Low Voltage
5
INPUT DATALoad detailsCable detailsCABLE SIZING CALCULATION CRITERIAShort circuit current capacityA=Cable cross-section area in Sq. mm
6
System voltage415 VPower Rating of motor90  kWLength120 mThe minimum cross section of LV voltage cables shall be calculated based on below methods:This criteria defines the minimum cross section required for the cable.=Short circuit current
7
Type of InsulationXLPESource Voltage 415  VResistance of the conductor (95mm2)0.247 ohm/km (As per Cable Catalogue)1. Short circuit current capacityK=Constant, 143 for XLPE Cu. Cable
8
Type of conductorCopperEfficiency 0.9Reactance of the conductor (95mm2)0.0734 ohm/km (As per Cable Catalogue)2. Current carrying capacityt=Duration of short-circuit in seconds
9
Maximum Ambient air temperature40°Power factor 0.853. Voltage drop of cable
10
Ground temperature30°The fault current at 415V is 40kA and the duration t is considered to be 0.1 based on relay delay time and breaker opening time.
11
Continuous temperature of the cable90°
12
Maximum short circuit temperature of the cable250°
13
14
Current carrying capacity
15
Derating Factors considered for multicore cables laid in ductCorrection FactorThe next nearest available cable size will be 95 Sq.mm
16
Installation method:Direct buriedDerating factor for variation in ground temperature at 30°Ck1:0.93(As per IEC 60364-5-52,Number of Runs / Phase:1
17
Ground temperature:30°CTable B.52.15 )Current rating for 95 Sq.mm Cu. Cable (Duct):211(As per IEC 60502-1 )
18
Soil Thermal Resistivity:2.5 K.m/WDerating factor:0.93
19
Depth of Laying:75 cmDerating factor for depth of laying of cablek2:1(As per cable catalogue)Derated current carrying capacity   I(Derated):196.23
20
Cable Grouping:
21
No. of cables in group:1Derating factor for soil and thermal resistivityk3:1(As per IEC 60364-5-52,
22
Spacing between duct centres:0 mmTable B.52.16 )
23
24
Derating factor for cable grouping factork4:1(As per IEC 60364-5-52, Table B.52.17 )
25
26
Overall correction factor for cables installed in Underground duct (k1 x k2 x k3 x k4):0.93
27
28
29
30
Voltage drop of cable
31
32
The cable has its resistance and reactance causing some voltage drop. Motor takes 6 to 12 times the full load current during starting. The voltage drop criteria has to be checked in order to have sufficient voltage to develop load torque.
33
34
35
Number of Runs / Phase:1
36
Resistance of the conductor (95mm2):0.247ohm/km(As per Cable catalogue)
37
Reactance of the conductor (95mm2):0.0734ohm/km(As per Cable catalogue)
38
Voltage:415V
39
40
41
The three phase voltage drop
42
43
44
45
46
47
48
L=Length of cable (m)
49
R=Cable resistance at 90°C – Ohm/km
50
X=Cable reactance at 50 Hz
51
I=Rated current (A)
52
n=No. of Parallel runsVdrop2.039877063by Formula
53
cos ø=Power factor
54
Ist=Starting current
55
cos øst=Power factor at starting
56
57
58
59
60
61
62
63
64
The voltage drop during running must be less than 3% (V(Running) < 3%)

The voltage drop during starting must be less than 10 to 15% ( V(Starting) <10-15%)

According to three major criteria, the cable size selected is 95mm2
65
66
67
68
69
70
International standard wire size Chart (IEC 60228)
71
0.75 mm²4 mm²0.5 mm²1 mm²2.5 mm²1.5 mm²
72
70 mm²6 mm²25 mm²185 mm²35 mm²400 mm²
73
95 mm²1000 mm²10 mm²800 mm²150 mm²50 mm²
74
300 mm²120 mm²500 mm²16 mm²630 mm²240 mm²
75
76
77
Electrical Cables Size & Current Rating Chart
78
Cross Section (mm2)Approximate Overall Diameter (mm)Current Rating
79
Single Phase (Amps)Three Phase (Amps)
80
1.52.917.515.5
81
2.53.532421
82
44.43228
83
64.684136
84
105.985750
85
166.957668
86
258.710189
87
3510.08125110
88
5011.8151134
89
7013.5192171
90
9515.7232207
91
12017.4296239
92
15019.3300262
93
18521.5341296
94
24024.6400346
95
30027.9458394
96
40030.8546467
97
50033.8626533
98
63037.6720611
99