ITEM
NO.
SCOPE OF WORKS, TECHNICAL SPECIFICATIONS & REQUIREMENTSMIMOS’ REQUIREMENT LEVEL
M - Mandatory Requirement
G - General requirement
2
3
1Bidder MUST fully comply with the scope of works on Provision of Chiller Optimizer System and Its Related Services for MIMOS Berhad based on Delivery Duty Paid (DPP) as specified in the Competitive Bidding document and Bill of Quantities (BQ)M
4
1.1Bidders MUST comply with the following minimum specification and requirements.M
5
6
2TECHNICAL SPECIFICATIONS & REQUIREMENTS
7
2.1The system hardware MUST have the following minimum specifications:M
8
2.1.1Main Control Unit
9
(a) Processor: Intel® Celeron® Processor J1900 Quad Core 2GHzM
10
(b) System Memory: 8GB, DDR3 1333MHz SDRAMM
11
(c) Display: 12.1" LED Panel with Projective Capacitive Touch DisplayM
12
(d) I/O Interface: At least 1 RS-485 port, 3 RS-232 port, 2 USB 3.0, 2 USB 2.0, 1 8-pin Digital I/O (DB-9) connectorM
13
(e) Ethernet: Dual GbE, 10/100/1000 MbpsM
14
15
2.1.2Outstation Control Unit
16
(a) Communication Interface: RS-485, Modbus RTU ProtocolM
17
(b) Programming: Conforms to IEC 61131-3 standardM
18
19
2.1.3Dashboard Display Unit
20
(a) Size: At least a 40" LEDM
21
(b) Resolution: Full HD Resolution 1920x1080pM
22
(c) Connectors: Minimum 2 HDMI and 2 USBM
23
24
2.1.4Digital Input/Output Module
25
(a) Channels: 6 x Independent Channel, 2 x Common Ground ChannelM
26
(b) Digital Input Level: Logic Level 0: +1V Max, Logic Level 1: +4V to +30VM
27
(c) Communication Interface: RS-485, Modbus RTU ProtocolM
28
2.1.5Relay
29
(a) Relay Current Rating: 10AM
30
(b) Relay Voltage Rating: 250VACM
31
(c) Relay Contact Form: DPDTM
32
33
2.1.6Digital Power Meter
34
(a) Conform to accuracy class 1.0 as per IEC 62053-21M
35
(b) Tested in accordance to IEC 62052-11 for energy test requirementsM
36
(c) EMI/EMC compliance as per IEC 61326-1M
37
(d) Sampling rate of at least 32 sample/cycle for 50/60 Hz electrical networkM
38
(e) Measurement parameter of Voltage, Current, Power, Energy and DemandM
39
(f) Communication Interface: RS-485, Modbus RTU ProtocolM
40
41
2.1.7Temperature Sensor
42
(a) Type: RTD (PT100) SensorM
43
(b) Conforms to minimum standard of IEC 60751 Class B : 2008 minimumM
44
(c) Application: In-pipe water temperature monitoringM
45
(d) Operational temperature range: At least 0°C to 100°CM
46
(e) Able to withstand flow rate of between 4500L/min and 5200L/minM
47
48
2.1.8Communication Protocol Repeater
49
(a) Input (Master): 1 RS-485 Channel: Data+,Data-M
50
(b) Output (Slave): 4 RS-485 Channels: Data+,Data-M
51
(c) Input Voltage: +10VDC ~ +30VDCM
52
53
2.1.9Power Supply
54
(a) Voltage Output: 24VDCM
55
(b) Current rating: 10AM
56
57
2.2The system software MUST have following minimum features:M
58
2.2.1All data acquisition MUST be in real-time and continuous mode.M
59
2.2.2All data acquisition MUST be at 1 minute interval or less.M
60
2.2.3MUST be able to subscribe to attributes and telemetry data from MIMOS backend server using websocket protocol.M
61
2.2.4All data MUST be stored either on site and/or to a cloud based serverM
62
2.2.5MUST be able to analyze and interpret all data in real-time and provide autonomous, real-time control of the chiller functionsM
63
2.2.6Dashboard MUST be able to:
64
a) Provide real-time display of data from ChillersM
65
(b) Provide real-time display of data from MIMOS Wireless SensorsM
66
(c) Provide real-time display of data from RTD PT100 Temperature SensorsM
67
(d) Provide real-time display of data from AHU/FCU on/off statusM
68
(e) Provide overall chiller energy baseline and real time consumptionM
69
(f) Provide historical trends and statisticsM
70
(g) Have alert/alarm indicator capabilityM
71
2.2.7MUST be able to improve the operational efficiency of the Chillers by a minimum of 12%.M
72
2.2.8MUST be able to provide real-time, continuous and autonomous control of 3 Chillers
- 400RT x 2 units (Manufacturer: Carrier)
- 750RT x 1 unit (Manufacturer: York)
M
73
2.2.9The system MUST ensure that the temperature and humidity condition for comfort, precision, chilled water and process cooling in MIMOS Fabrication Plant MUST be maintained according to the following requirements:M
74
(a) Comfort Cooling - To meet MIMOS space temperature set point of 24°C ± 2°C and humidity set point of 50% ± 10%.M
75
(b) Precision Cooling - To meet MIMOS Clean Room ambient temperature set point of 23°C ± 1°C and humidity set point of 45% ± 5%.M
76
(c) Chilled Water - To meet MIMOS Chilled Water temperature set point of 6°C to 8°CM
77
(d) Process Cooling - To meet MIMOS process cooling temperature set point of 18°C to 20°CM
78
2.2.10MUST be able to be accessed by MIMOS for sensor data collectionM
79
80
3INSTALLATION AND COMMISSIONING
81
3.1Bidder MUST provide full installation and system/equipment setup upon delivery.M
82
3.2Installation of the proposed chiller optimisation system MUST not disrupt operation of existing system/machinery/equipment.M
83
3.3Any downtime of chiller operation MUST not exceed a maximum of 4 hours.M
84
3.4Prefered method of installation of RTD PT100 temperature sensor is via "Hot Tapping" methodG
85
3.5Bidder MUST establish the energy consumption baseline of MIMOS Fab's chillers that adheres to IPMVP protocol for M&V, taking into account of changes in weather, building heat load etcM
86
3.6The baseline and savings/improvement MUST be verified and validated by an independent body and/or relevant authorityM
87
88
4COMPLETION PERIOD
89
4.1Bidder MUST complete the all the required tasks above not later than 6 months from the date of issuance of Letter of Acceptance or Purchase OrderM
90
91
5WARRANTY & SUPPORT
92
5.1Bidder MUST provide standard Twelve (12) months warranty and technical support for hardware and software platformM
93
5.2Bidder shall provide extended Twenty Four (24) months warranty and technical support for hardware and software platformG
94
5.3Bidder MUST provide training on the usage of equipment for at least 2 persons on-site for at least 1 full day within 2 weeks of system installation.M
95
96
6BIDDER'S ASSESSMENT
97
6.1Bidder's Experience
98
6.1.1Bidder should have technical support engineer(s) and office in Malaysia. Bidder to provide resume of minimum of 2 technical support engineers’ resume and address of technical support office in Malaysia.G
99
6.1.2Bidder MUST have installed the tendered item at a minimum of 3 different locations, with 3 different customers. The installation's baseline and savings/improvement data MUST be verified and validated by an independent body and/or relevant authority. Bidder MUST provide proof and supporting documents.M
100
6.1.3Bidder should have minimum 5 years experience in terms of providing support on the tendered items. Bidder to provide the evidence.G