Calculation of IDMT Over Current Relay Settings(50/51):Calculation of IDMT Earth Fault Relay Settings(50N/51N):Jignesh.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com
3
4
5
Name of FeederName of Feeder
6
Load Current: (IL)384AmpLoad Current: (IL)384Amp
7
Min Fault Current ( Line-Line):11000AmpMin Fault Current ( Line-Ground):11000Amp
8
Max Fault Current ( Line-Line):22000AmpMax Fault Current ( Line-Ground):22000Amp
9
Relay TypeRelay TypeNormal Inverse (NI)
10
Relay CodeRelay CodeVery Inverse (VI)
11
Relay NoRelay NoExteremely Inverse (EI)
12
CT Primary Current600AmpCT Primary Current600AmpLong Time Inverse
13
CT Secondary Current1AmpCT Secondary Current1Amp
14
Relay Error (%)7.5%Relay Error (%)7.5%
15
CT Error (%)10.0%CT Error (%)10.0%
16
Over shoot0.05SecOver shoot0.05Sec
17
C.B Interrupting Time0.17SecC.B Interrupting Time0.17Sec
18
Safety 0.33SecSafety 0.33Sec
19
Total Grading Time0.58SecTotal Grading Time0.58Sec
Enter Data in White Background Cells
20
Expected Operating Time of Relay0.271SecExpected Operating Time of Relay0.176Sec
21
Over Current Relay Setting Earth Fault Relay Setting
22
Low Over Current Setting: (I>)Low Earth Fault Setting: (Ie>)
23
Over Load Current :125%X ILEarth Fault Current :20%X In
24
Over Load Current :(In)480AmpEarth Fault Current96Amp
25
Required Over Current Relay Plug Setting0.80.8 A X InRequired Earth Fault Relay Plug Setting0.20.2 A X In
26
Actual Plug Setting of Over Current Relay0.800.8 A X InActual Plug Setting of Earth Fault Relay0.160.2 A X In
27
Time Dial Setting of Over Current Relay (TMS)0.125SecTime Dial Setting of Earth Fault Relay (TMS)0.125Sec
28
Curve Selection for RelayNormal Inverse (NI)Curve Selection for RelayNormal Inverse (NI)
29
Pick Up Setting of Over Current Relay (PMS): (I>)0.8AmpPick Up Setting of Earth Fault Relay (PMS): (Ie>)0.16Amp
30
Plug Setting Multiplier (PSM):22.92Plug Setting Multiplier (PSM):114.58
31
Operation Time of Relay2.17SecOperation Time of Relay1.41Sec
32
Actual Operating Time of Relay : (tI>)0.271SecActual Operating Time of Relay : (te>)0.18Sec
33
Total Grading Time0.58SecTotal Grading Time0.58Sec
34
Operating Time of Previous Up steam Relay0.85SecOperating Time of Previous Up steam Relay0.76Sec
35
High Over Current Setting: (I>>)High Earth Fault Setting: (Ie>>)
36
Actual Plug Setting of Relay2.502.5 A X InActual Plug Setting of Relay2.502.5 A X In
37
Time Dial Setting of Over Load Relay (TMS)0.100SecTime Dial Setting of Over Load Relay (TMS)0.100Sec
38
Curve Selection for RelayNormal Inverse (NI)Curve Selection for RelayNormal Inverse (NI)
39
Pick UP Setting of Over Load Relay (PMS): (I>>)2.5Amp
Pick UP Setting of Earth Fault Relay (PMS): (Ie>>)
2.5Amp
40
Plug Setting Multiplier (PSM):7.33Plug Setting Multiplier (PSM):7.33
41
Time of Operation of Relay3.44SecTime of Operation of Relay3.44Sec
42
Actual Operating Time of Relay : (tI>>)0.34SecActual Operating Time of Relay : (te>>)0.34Sec
43
Total Grading Time0.58SecTotal Grading Time0.58Sec
44
Operating Time of Previous Up steam Relay0.92SecOperating Time of Previous Up steam Relay0.92Sec
45
Summary of Over Current Relay Setting:Summary of Earth Fault Relay Setting:
46
Pick Up Setting of Over Current Relay (PMS): (I>)OK
Pick Up Setting of Over Current Relay (PMS): (I>)
OK
47
Low Over Current Setting: (I>)0.8 A X InAmpLow Earth Fault Setting: (Ie>)0.2 A X InAmp
48
Actual Operating Time of Relay(tI>)0.271SecActual Operating Time of Relay(te>)0.176Sec
49
High Over Current Setting: (I>>)2.5 A X InAmpHigh Earth Fault Setting: (Ie>>)2.5 A X InAmp
50
Actual Operating Time of Relay(tI>>)0.34SecActual Operating Time of Relay(te>>)0.34Sec