Default on hours: M-F, 6AM-9PM

Open Area lights will be on at 50% brightness and increase to 100% once occupancy is detected.

Outside of that schedule: Lights schedule to come on to 100% when occupancy is detected, and to go off complete 20 min after no more occupancy detect.

​

Occupancy detection: Infrared and sonar sensors

​

Light switches:

Break Room 402 Main Shared Conference Room

All On

​

Central On

Cabinet On

​

Nothing

All Off

​

Central Off

​

Cabinet Off

​

Nothing

Entry On

​

Entry Off

​

Central On

​

Central Off

All On

​

Central On

Side On

​

Nothing

All Off

​

Central Off

​

Side Off

​

Nothing

2 of 2

Light switches:

​

-Holding down on the ‘On’ button will increase brightness of the lights

-Holding down on the ‘Off’ button will decrease brightness of the lights

​

If room is occupied AND you manually press the off button, the light should go off and stay off until occupancy is no longer detected--then it SHOULD go back to its default behavior

​

Office lights are off unless occupancy detected, and should turn off after 20 min no occupancy

​

Offices Su Lab Conference Room

​

​

​

Light On

​

Nothing

Infrared sensor

​

​

Light Off

​

Sonar sensor

On

​

Raise bright

​

Dim

​

Off