Default on hours: M-F, 6AM-9PM
Open Area lights will be on at 50% brightness and increase to 100% once occupancy is detected.
Outside of that schedule: Lights schedule to come on to 100% when occupancy is detected, and to go off complete 20 min after no more occupancy detect.
Occupancy detection: Infrared and sonar sensors
Light switches:
Break Room 402 Main Shared Conference Room
All On
Central On
Cabinet On
Nothing
All Off
Central Off
Cabinet Off
Nothing
Entry On
Entry Off
Central On
Central Off
All On
Central On
Side On
Nothing
All Off
Central Off
Side Off
Nothing
Light switches:
-Holding down on the ‘On’ button will increase brightness of the lights
-Holding down on the ‘Off’ button will decrease brightness of the lights
If room is occupied AND you manually press the off button, the light should go off and stay off until occupancy is no longer detected--then it SHOULD go back to its default behavior
Office lights are off unless occupancy detected, and should turn off after 20 min no occupancy
Offices Su Lab Conference Room
Light On
Nothing
Infrared sensor
Light Off
Sonar sensor
On
Raise bright
Dim
Off