1
In support of S.8765 which seeks to establish consumer protection and utility meter choice
Presenters:
Les Jamieson
Member of New Yorkers 4 Wired Tech
William Bathgate
BBEC, EMRS, IEEE RFSO
Vice President of the Residential Consumer Group
Odette Wilkens
Attorney, founder of NY Wired Broadband
February 7, 2023
2
As it is, S.8765 provides benefits to utility customers with residential accounts by offering them the ability to retain use of their analog meter without fees being imposed. The following provisions would provide additional consumer protections to a broader scope of state residents:
There are many thousands of NY residents who own multi-family homes. In the interest of their rights as property owners, it is important that they be able to have analog meter choice for their entire property, not just the unit they live in. They need to be able to opt out for their rental units, and for accounts covering common areas within the building, such as hallways. Currently, hallways are designated by the utilities as being commercial. There is no opt out choice for any accounts designated as commercial
Owners of small businesses with accounts designated as commercial need to have analog meter choice. These include restaurants, and all manner of neighborhood shops. Owners and their staff spend substantial time in close proximity to utility meters.
Residents and pedestrians near buildings with digital meters installed on their exterior need protection from exposure to their RF emissions which are pulsed frequencies. This can be done with meter covers made up of a protective shielding material. Ideally, there should also be shielding behind the meter panel as well.
Large residential buildings have large panels with utility meters. These panels with digital meters also need to have meter covers made of protective shielding material. If the location of the digital meters is adjacent to living space, there needs to be shielding behind the digital meters as well.
Note: The current electronic meters as deployed today are in violation of Equipment Authorization of the FCC, which requires a minimum physical separation of 20 cm (7.8 Inches) from the surface of the meter in all directions to prevent hazardous human exposure.
Proposed additions to S.8765 or possibly a companion bill
3
The Effect of the Appeals Court Ruling on Digital Meters
Policy makers working to serve the interests of their communities and the general public would benefit from the information to follow.
But first, policy makers need to be aware that the utilities claims of compliance with FCC guidelines refer to the Telecommunications Act of 1996 are unfounded due to the United States Court of Appeals for the District of Columbia Circuit decision on Aug. 13, 2019 establishing that the FCC’s refusal to update their guidelines was “arbitrary and capricious”. This decision was upheld on Aug. 20th, 2021 when the court stated:
…the agency demonstrated “a complete failure to respond to comments concerning environmental harm caused by RF radiation.” The court found the FCC ignored numerous organizations, scientists and medical doctors who called on them to update limits and the court found the FCC failed to address these issues:
AMI Meters add to CO²/Climate Change and Higher Bills
By William Bathgate, BBEC, EMRS, IEEE RFSO
Vice President of the
Residential Consumer Group
January 25, 2023
4
Note: This report has been written in terms that a common person with limited knowledge of electricity and engineering can understand.
5
William practices as a professional in electrical engineering and mechanical engineering disciplines. He was recently employed at Fiat Chrysler Automotive on electronics systems for such things as radio communication for electric and autonomous vehicles etc. William was previously employed through late 2015 for 8 years at the Emerson Electric Company. While at Emerson Electric he was the Senior Program Manager for Power Distribution Systems and in charge of RF and IP based digitally controlled high power AC power switching system product lines in use in over 100 countries. He was also directly responsible for product certifications such as UL (USA), CE (EU), PSE (Japan) and many other countries electrical certification bodies. He is very familiar with the electrical and electronic design of the AMI meters in use because he was responsible for very similar products with over 1 Million units installed across the world. William also has over 20 years work experience with IBM and Hewlett Packard in computer systems design and manufacturing.
He holds a DOD Top Secret Clearance, serving in Cyber Security with the US Missile Defense Agency, NASA and Homeland Security. He is a Certified Building Biologists and a Certified Electro Magnetic Radiation Specialist by the Building Biology Institute https://buildingbiologyinstitute.org/. He is an IEEE Certified Radio Frequency Safety Officer and conducts radio antenna surveys for assurance to the FCC specifications.
He is Vice President of the Residential Consumer Group https://residentialcustomergroup.org/. This organization has legal representation in all Public Utility Rate Cases submitted in Michigan. To date the group has caused the cancellation of numerous rate increases in excess of over 1 Billion in increased utility costs to Michigan Residents.
He has done this analysis due to his own curiosity without conflict of interest of this new technology. He has 40 Years work experience in design and deployment of:
High tech power management systems, UPS and power distribution
Switched Mode Power Supplies
Electrical and Electronic hardware engineering
Computer systems engineering
Radio Systems design and testing
High Current and High Voltage switches
Internet communications using both wired and wireless technologies
UL, CE (Europe), Africa, Japan, Australia and China product safety certifications
Cyber encryption (DOD Level) and protection of Radio Communications using digital signals
RFI/EMI mitigation
BACKGROUND: William S. Bathgate
�Agenda – What you need to know�
6
It is not less than a cell phone call �The Truth on RF Smart Meter Emissions
7
µW/CM²
Note: 1µW/CM²
= 10,000 µW/M²
The Smart meter is 400,000 µW/M² peak @ 10 ft it is 100,000 µW/M² peak
Smart Phone is
0.25 µW/CM² = 2,500 µW/M² peak
Source – Dr. Daniel Hirsch on the CCST Report – is all in µW/CM²
CCST = California Council on Science and Technology
Note – Initial ERPI report but corrected for whole body exposure vs at the ear for a cell phone. The original report from CCST measured at less than 3 RF wave lengths from the source i.e. cell phone right at the ear lobe. When conducting RF measurements you must consider the recommended distance between the RF source and the instrument antenna. Typical rule is 3.
The common assertion that the Smart Meter emits less RF than a cell phone is untrue.
8
Examples of Digital Meter Installations in Apartment Buildings
Note this is exceeding the FCC equipment Grant
separation distance of 20 cm
9
Examples of Digital Meter Installations in Apartment Buildings
From the FCC Equipment Grant (ITRON Meter Example)
µw/cm² | µw/m² | Plus gain of 3.5 |
0.407 | 4,070.00 | 14,245.00 |
10
Examples of Digital Meter Installations on Exterior Walls
Albemarle St. and Nostrand Ave. in Brooklyn
51st Street between 4th and 5th Avenue in Brooklyn
Building Biology International Safety Standards for RF for Human Exposure
As anyone who walks within 3 Meters of these meters their exposure is considered an Extreme Concern @ 14,245 µW/M²
How far can the AMI meter transmit?
11
How far can the AMI meter transmit?
12
�AMI – “AMI - Smart Meters” use power from the Grid to operate – This adds to Climate Change�
13
�How much power does the AMI meter consume?�
14
My Smart Meter Test Setup
Proof - My Field Test - My Energy Insight Readings – Michigan example �Average Daily AMI kWh Use 2.37 kWh @ 0.13 per kWh = $0.31/day (865 kWh/Yr.)�
15
Note – No breakers were on and the time and reading of the meter is not a simple “Text” message these are clearly two way communication activity and the power to run the meter itself. It is not the same as a simple cell phone call.
This data was from Detroit Edison, as the reported power consumption on the home, with all the power off!
Impact to the Environment – Detroit Example
16
Annual Cost per Customer | Rev $ per Detroit Edison | Rev $ per Consumer Energy | kWh per Detroit Edison | kWh per Consumer Energy | CO² Per Detroit Edison | CO² Per Consumer Energy |
$113.15/Yr. | $235.35M | $203.67M | 1.816B | 1.521B | 3.924BT | 3.879BT |
Total Consumer Costs Yr. | Total kWh Consumed Yr. | Total CO² Per Yr. (Coal @ 2.16lbs per kWh) |
$439.02M | 3.337B | 7.803BT |
Conclusion: There is absolutely NO evidence the AMI Meter program saves CO², energy in kWh or money, in fact it only drains the bank accounts of the impoverished consumer, pads utility revenue and adds to Global Climate Change.
The only way the AMI program will save kWh’s is to use it to ration power to consumers via Demand Response/Time of Use rate structures at 5-10 X normal rates where the elderly, disabled and young families with a parent and small children at home can least afford it or do without power during the Demand Response/Time of Use period. Under this scenario the AMI program is the largest fleecing of the consumer to ever exist and a deception to our citizens regarding saving power, reducing costs, reducing CO² and protecting our environment. We would be better off taking the money to be invested in AMI meters and plant trees.
Note: Solar is 2.2 Lbs. total Embedded CO²/kWh including Mining, transport, maintenance, etc.
AMI is not Secure – It has a Physical Back Door
17
There is a special tool that is used to program the meter. A malicious actor can easily obtain one of these tools.
A physical connection to the meter directly by-passes encryption, allowing privacy to be violated and hacking risk; insertion of code, altering the network traffic and injecting malicious code. They can even shut down the power. The default passwords are published in the meter documentation.
Network Weak Link
18
A malicious actor can send a strong RF broadband signal (multiple frequencies all at once) pointed at this network point, blocking transmission and no readings can be sent to the utility. The AMI meters have tamper protection in them and when they do not get an acknowledgment back from the utility over a certain period of time they begin to shut down. You do not need to know the encryption key, just block the transmission to the network access point with an overwhelming RF signal
Back Door to the Data, Zigbee Net
19
Once access via the gateway is enabled there is no firewall to block data access, so personal email, video downloads data, etc. can be accessed by utilities and hostile actors. If you can get on the ZIGBEE network you can observe all this type of data. I can easily hack my neighbors ZIGBEE 2.45 GHz network and see all his information Realtime.
Smart Meter - Day Old Data - will never let a consumer help prevent a “Brown Out” �
20
Note – These are the readings of my electric use coming from DTE. This data is a day old. It is impossible to adjust my usage today based on usage from yesterday. Yesterday is gone and nothing can be done about it. Unless the meter information is “Continuously Real Time” there is no purpose in building out this capability. The utility costs to provide day old data is pointless. It is cute to see this information but the consumer cannot change behavior to effect a result to something that has already occurred.
�AMI versus Analog Meter Accuracy�
21
Key Differences
AMI versus Analog Meter Accuracy�
22
Key Differences
AMI versus Analog Meter Accuracy
23
Key Differences
AMI versus Analog Meter Accuracy�
24
Key Differences
AMI versus Analog Meter�
25
Key Differences
Meter accuracy and your bill
26
Meter accuracy and your bill
27
Electric Motor Current Draws are different than a light bulb
�Conducted Emissions “on the wire” �
28
SMPS with Common Mode Filter – Principles You Need to Understand
29
The Standard Single Phase 60 Cycle/Second Waveform with EMI/RFI introduced by the SMPS
This waveform displayed is the same as an oscilloscope trace would look like, you cannot see this on a common voltmeter. Now we have introduced the effects of EMI/RFI via the SMPS to the same wire carrying the house current. This effect can be less depending on the environment, especially how good the house earth ground is magnetically coupling the house voltage currents Especially if they are using the water pipe as a ground reference which makes it worse. There are many variables that affect this waveform. The image in red should never be there, I have found this pattern consistent with every AMI meter, including the AMI meter with the radios off and the various digital meter alternatives. It is typically not compliant to FCC rules over all required frequencies for “conducted” Emissions Class A or Class B.
The claim the meter meets FCC specs, maybe not true
30
Here is an example:
This the section of a report on a Sensus brand meter that is non compliant at 300 KHz note they are over spec for both FCC QP and AV Class B specs
I have the full reports of each example I present here. These are the parameters for “Conducted Emissions” not the RF 900 MHz transmissions
How does the utility get a non- compliant meter accepted as compliant?
31
Here is an second example:
The previous section of a report on the same Sensus brand meter that is non compliant at 300 KHz where they are over spec for both FCC QP and AV Class B spec. They then submitted a second report to the Iowa Commission for the same meter a report that obviously “Cherry Picks” the data points avoiding the 300-320 KHz frequency range to make it appear to be compliant. They avoided the graph shown in the previous chart. I find this be a common ploy in submission for approvals to state commissions. Since the meter companies pay the certification service they can be easily influenced to create a report favorable to outcome the meter company desires.
AMI meter without Common Mode Filter – Principles You Need to Understand
32
The Standard Single Phase 60 Cycle/Second Waveform with EMI/RFI introduced by the SMPS
The image in red is for both AMI meters (with the radios on or off) and the various forms of “Electronic Meters." They are not compliant to FCC rules for “conducted” Emissions Class A or Class B. Shown here are the limits for CONDUCTED emissions not Radio Emissions, which is a different specification, which are being fed back into the home wiring at the load panel. This is placing stress on all electronics and electric motors in the home, causing early appliance motor failures, appliance electronic control failures and radio interference, in addition to health effects such as insomnia, tinnitus, headaches, high blood sugar levels and nervous disorders such as neuropathy and heart arrhythmia. In order to become compliant the meter manufactures would have to scrap the current SMPS design, and include one that connects to an earth ground path to sink the oscillations to the home ground rod.
Class A
limits
What can be done to remove conducted emissions within the meter?
33
Summary
34